EBV Vertical fuse switch disconnector
·Fibreglassstrenghtened,self extinguishing thermoplasticsofV0 flammability class
·Double clearance between open contacts
·Arc chutes with deionisation plates over every contact
·Reversible - top/bottom cable terminal connection
·Wide range of accessories
EBV Introduction 54-55
EBV Technical data 55
EBV Catalogue numbers structure 56
EBV00 1 0 0 ~ { {mm } } busbar system 57-58
EBV00185mmbusbarsystem 59-60
EBV2185 mm busbar system 61-62
EBV3185 mmbusbarsystem 61 and 63
EBV2and EBV3 Fuse disconnectorwith 64
lateralbusbarterminal
EBV with electronic fuse monitoring 65-66
module
Outline drawings 67-71
Accessories 72-73
Applications
EBVverticalfuseswitchdisconnectorsaredesignedfordistributionofelectricityandprotectionagainstshortcircuitsandverlads inthreephase.TheyaredesignedtobeusedwithNHfuselinksandaremeantfordirectistalltiononhorizontalorverticalbusbar systems.
EBVfuseswitchdisconnectorsconformtoIEC60947-1-andIEC60947-3standards.EBVfuseswitchdisconnectorsaredesignedfo applicationswhicequireelablitndsafetylikelowvoltagedistrbutionboardsinstalldinransformersubstatiosindustriallow voltagedistributionboardsand cablecabinets.
Removaloffuselinksissimpleandsafe.Oncethefuselinksareremoedthereisaargeisoatingdistanceclearlyible.Mounting and cable termination is simple and can be accomplished byone person only using insulated equipment.
EBV fuse switch disconnectors are designed to perform the following functions:
. Protection,
. Energy distribution, . Earthing,
· Switching,
· Touch protection.
Sizes
EBVfuse switch disconnectors are designed for installation onto 1 8 5 ~ \mathsf {mm } busbar system.They are available in following sizes (according torated current):
00 (160 A)
2 (400 A)
3 (630 A and 1250 A upon request)
EBV size 00 are manufactured in two versions depending on busbar system:
·EBV00/100mm fuse switch disconnector (160 A) for installation on 1 0 0 ~ \mathsf {mm } busbar system.Installation on 185 mm busbar system is possible by using an adaptor.
·EBV00 fuse switch disconnector (160 A) for installation on 1 8 5 ~ \mathsf {mm } busbar system.
Construction
EBV fuse switch disconnectors are manufactured in two versions:
One-pole switching (separately each pole) Three-pole switching (three poles simultaneously)
Theyare manually operated,consequently making and breaking is dependant on the speed of operatior
MainbaseoffuseswitchdisconnectorEBVismadeofhalogenfree,fibreglassstrengthened,selfextinguishing,tmoset polyesterofVflammabilityclass.OtherplasticpartsoffuseswitchdisconnectorsEBVaremadeof halogenfreefibreglass strengthened, thermoplastic polyamides.
Silverplatedcotactsprovidelowowerloss.ependingonmptyeEBVuseichdisonectorsablesrtocticular orsector-shapedconductorswithbusbarendsorconductorswithlugterminals.Arcchutewithdeionzationplatesareinstalldover eachcontactensuring beterarcextinctionand exhaustofarcplasma.Protectiondegreeof IP30fromthefrontisprovided.
AdditionalaccessorseabletoinstallEBVfuseswichdisonectorsofifrentssonommonbusbarsystems.AllssofEBV fuseswitchdscoectorsareprovidedompleteithamps(iesVternals,Vtrinals)androdsforabletna
The making and breaking operations hasto be done with adequate force since these are manuall operated switches
Parallel moving,double contact system.
Fuse switch disconnectors width:50,100 and 2 0 0 ~ { {mm } }
Suitable for top cable terminal connection.
Flexiblity toterminatecircularorsector-shapedbusbarconductorsforVor2Vterminals.Conductors with lugs can be terminatedwithscrewterminals.
Voltage test can be performed through test holes leading to blade contacts.
Operating conditions
To be installd in a room free of any dust,aggressive or explosive gases Altitudeupto 20o0metersabovesea level Outdoor-in cabinets with protection degree > IP34 Ambient temperature from - 2 5 ^ { \circ } C to + 5 5 ^ { \circ } \mathsf { C } (20 + Relative humidity of the air should not be higher than 50 percent at temperature of + 4 0 ^ { \circ } \mathsf C
Technicaldata
| Description | Rated voltage | EBVOO 100mm | EBVOO | EBV2 | EBV3 | EBV3-1250 |
| Rated thermal current I=l with fuse links | 1 | 160A | 160A | 400A | 630A | : |
| Rated thermal current lwith solid links | 600A | 750A | 1250A | |||
| Rated voltage Un | 690Va.c. | 690Va.c. | 690Va.c. | 690Va.c. | 400Va.c. | |
| Utilisation category | 690Va.c. | AC-22B | AC-22B | AC-22B | AC-21B | |
| 500Va.c. | : | AC-22B | : | |||
| 400V a.c. | AC-23B | AC-23B | AC-23B | AC-23B | AC-22B | |
| Rated switching current l | : | 160A | 160A | 400A | 630A | 1250A |
| Rated short-circuit making current | 690Va.c. | 25kA | 80kA | 100 kA | 80kA | |
| 500V a.c. | 25kA | 100 kA | 100 kA | · | ||
| 400 Va.c. | 25kA | 100 kA | 100 kA | 100kA | : | |
| Rated short-circuit withstand current | 690Va.c. | 100 kA | 80kA | 100 kA | 80kA | : |
| 500V a.c. | 100 kA | 100 kA | 100 kA | |||
| 400V a.c. | 100 kA | 100 kA | 100 kA | 100 kA | : | |
| Rated insulation voltage U | 1000 | 1000 | 1000 | 1000 | 1000 | |
| Rated impulse withstand voltage Uimp | 8kV | 12 kV | 12kV | 12 kV | 12 kV | |
| Rated short time withstand current l | : | 121/15² kA | 141)/16² kA | 15/20³ kA | ||
| Rated frequency | 50-60 Hz | 50-60 Hz | 50-60 Hz | 50-60 Hz | 50-60 Hz | |
| Mechanical durability (Number of cycles) | 1600 | 1600 | 1000 | 1000 | 600 | |
| Electrical durability (Number of cycles) | 200 | 200 | 200 | 200 | 100 | |
| IP degree of protection (IP) | 30 | 20 | 30 | 30 | 30 | |
| Compatible NH Fuse links body size | 00 | 0 | 1,2 | 3 | solid links |
| Verticalfuse switch disconnector | NHFuse linksize | Mounting type | Poles | Switching type | Terminalclampsdetails | ElectronicmoduleorLateral busbar |
| EBV | 00 | 11=185 mm busbar with heightened rails | 1= one- pole | S= Each phase switching separately | M1= Screw terminals with pressed nuts | -E= Electronic fuse monitoring module |
| 2 3 | 23= 100 mm busbar | 3= three- pole | T= Simultaneous 3 phase switching | M2= Screw terminals with pressed nuts M12 S8= Screw terminals with M8 Screws | -L = Lateral busbar terminal - Left | |
| system 33=185 mm busbar | VO = V-terminals without V-clamps | side | ||||
| system | V1 = V-terminals with V-clamps | - R = Lateral busbar terminal - Right side | ||||
| WO= 2-V Terminals without double V-clamps W1 = 2-V Terminals with double V-clamps |
CataloguenumberEBV233SV1 representsavertical fuseswitch disconnector,for NHFuse link size2, suitable for 185 mm busbarsystem33, each phase switching separatelyS,with V-terminals and V-clamps V1.
| Ordering code information | Typedesignation | |||
| Product type | ||||
| NH Fuse link size | 2 | |||
| Mounting type | 3 | |||
| Number of poles | ||||
| Simultaneous or separate switching | ||||
| Terminal clamps | ||||
| Complete part numbers | EBV 2 | 3 | S | V1 V1 |
EBV00 Vertical fuse switch disconnector,size 00,160A,690 V,100 mm busbar system
For installation on 1 0 0 ~ { {mm } } busbar system Fuse switch disconnector's width 5 0 ~ \mathsf {mm } Three pole switching-all phases simultaneously
EBV00 Vertical fuse switch disconnector,size 00,160A,690V,100 mm busbar system
| Description | EBV00/100mm |
| Rated thermal current I=l | 160A |
| Rated voltage Un | 690Va.c. |
| Utilisation category | AC-22B AC-23B |
| Rated switching voltage Ue | 690Va.c. 400 Va.c. |
| Rated switching current l。 | 160A |
| Rated short circuit making current | 25kA |
| Rated short circuit withstand current | 100 kA |
| Rated insulation voltage U | 1000V |
| Wited imdvotage Umg | 8kV |
| Rated frequency | 50-60 Hz |
| Mechanical durability (number of cycles) | 1600 |
| Electrical durability (number of cycles | 200 |
| IP degree of protection (IP) | 30 |
| Compatible NH Fuse link body size | 00 |
| Accessories see page 72 |
| 100mmbusbarsystem | Weight |
| Three poleswitching -allphases simultaneously (for installationon 100 mm busbar system) | |
| EBV0023TS8 cable terminals: bridge terminals with bridge clamps (S)4-70 mm²,screw terminals with M8 screws | 1.3kg |
| EBV0023TV1 cable terminals: V-terminals with V-clamps 25-120 SW | 1.5kg |
| EBV0023TV0 cable terminals: V-terminals, without V-clamps | 1,3kg |
EBV0o Terminal clampsdetails
| Description Clamp | S-bridgeclamp2xM5x25 | M8screw* | V-clamp25-120SW | HM10-120 |
| Outline drawing | ||||
| Cross-section of conductors | 4- 70 mm² | Conductorwith max185mm² | re 16 mm²-95 mm² se 25 mm² - 120 mm² rm 16mm²-95mm² | re 10 mm²-70 mm² se 20 mm² - 120 mm² rm 10 mm²-70 mm² |
| Tightening torque | 3Nm** | 12Nm** | sm25mm²-120mm² 20Nm** | sm 25mm²-95mm² 15Nm** |
EBV00 Vertical fuse switch disconnector, size 00,160 A, 690 V,185 mm busbar system
For installation on 1 8 5 ~ \mathsf {mm } busbar system
Fuse switch disconnector's width 5 0 ~ \mathsf {mm }
Three pole switching -all phases simultaneously - two-hand operation
or one pole switching -each phase independently
| Description | EBV00/185mm |
| Rated thermal current I=l | 160A |
| Rated voltage Un | 690Va.c. |
| Utilisation category | AC-22B AC-23B |
| Rated switching voltage Ue | 690V 400V |
| Rated switching current l。 | 160A |
| Rated short circuit making current | 80 kA (690 V a.c.) |
| 100 kA (400 V a.c.) | |
| Rated short circuit withstand current | 80 kA (690 V a.c.) |
| 100 kA (400 Va.c.) | |
| Rated insulation voltage Ui | 1000Va.c. |
| Wited ingygtag uig | 12 kV |
| Rated frequency | 50-60 Hz |
| Mechanical durability (Number of cycles) | 1600 |
| Electrical durability (Number of cycles) | 200 |
| IP degree of protection (IP) | 20 |
| Compatible NH Fuse link body size | 00 |
| Accessories see page 72 |
| 185mmbusbarsystem | Weight |
| Three-pole switching -each phase independently | |
| EBV0033SS8 | Cable terminals: bridge terminals with bridge clamps (S)4-70 mm²,screw terminals with M8 screws 2.6 kg |
| EBV0033SV1 | Cable terminals: V-terminals with V-clamps 25-120 SW |
| EBV0033SV0 Cable terminals: V-terminals, without V-clamps | 2.7kg 2.6kg |
| Three-pole switching -all phases simultaneously | |
| EBV0033TS8 | Cable terminals: bridge terminals with bridge clamps (S)4-70 mm²,screw terminals with M8 screws 2.7kg 2.8kg |
| EBV0033TV1 | Cable terminals:V-terminals with V-clamps 25-120 SW |
| EBV0033TV0 | Cable terminals: V-terminals, without V-clamps |
| EBVOOwith heightenedrailsadjusted to front lineandterminal cover of EBV 2,3 | |
| One-pole switching-each phase independently | |
| EBV0011SS8 Cable terminals: bridge terminals with bridge clamps (S)4-70 mm²,screw terminals with M8 screws | 2.7kg |
| EBV0011SV1 | Cable terminals: V-terminals with V-clamps 25-120SW |
| EBV0011SV0 Cable terminals: V-terminals,without V-clamps | |
| One-pole switching -all phases simultaneously | |
| EBV0011TS8 | Cable terminals: bridge terminals with bridge clamps (S)4-70 mm² screw terminals with M8 screws 2.8 kg |
| EBV0011TV1 | Cable terminals: V-terminals with V-clamps 25-120 SW |
| EBV0011TV0 Cable terminals: V-terminals, without V-clamps | |
:BV00 Vertical fuse switch disconnector, size 00, 160A, 69o V, 185 mm busbar system
EBV00/185 mm busbar system-Terminal clamps details
| Description Clamp | S-bridgeclamp2xM5×25 | M8screw* | V-clamp25-120SW | HM10-120 |
| *亲* | ||||
| Outline drawing | ||||
| Cross-section of conductors | 4 - 70 mm² | Conductorwith max 185mm² | re 16 mm² -95 mm² se 25mm²-120mm² rm 16mm2-95mm² | re 10 mm²-70 mm² se 25mm²-120mm² |
| Tightening torque | 3Nm** 12 Nm** | sm25mm²-120mm² 20Nm** | rm 10mm2-70mm² sm25mm²-95mm² 15Nm** | |
Vertical fuse switch disconnector,EBV2size 2,400Aand EBV3 size3630A,690Va.c. 185 mm busbar system
For installation on 1 8 5 ~ \mathsf {mm } busbar system
Fuse switch disconnector's width 1 0 0 ~ { {mm } }
Three pole switching-allphases simultaneously or one pole switching -each phase independently
Description
1-Main base
2- Hooked clamp-for installation on busbar system
3-Terminal shroud for fuse switch disconnector with
doubleV-clamps ( 2 x 2 4 0 ~ \mathsf {mm } ^ { 2 } ) (2
4 -Terminal shroud (long)
5 -Terminal shroud (short)
6 - Bottom adjusting shroud
7- Cable terminal protective cover
8-protective busbar barrier
EBV2 Vertical fuse switch disconnector, size 2, 400 A, 69o V, 185 mm busbar system
Designed for operation with NH1 and NH2 fuse links
| Description | EBV2/185mm |
| Rated thermal current I=lwith fuse links | 400A |
| Rated thermal current lwith solid links | 600A |
| Rated voltage U | 690Va.c. |
| Utilisation category | AC-22B AC-23B |
| Rated switching voltage U | 690Va.c. 400Va.c. |
| Rated switching current I | 400A |
| Rated short circuit making current | 100kA |
| Rated short circuit withstand current | 100kA |
| Rated insulation voltage Ui | 1000Va.c. |
| Rated impulse withstand voltage U | 12kV |
| Rated short time withstand current I | 121/152kA |
| Rated frequency | 50-60 Hz |
| Mechanical durability (number of cycles) | 1000 |
| Electrical durability (number of cycles) | 200 |
| IP degree of protection (IP) | 30 |
| Compatible NH Fuse link body size | 1,2 |
| Accessories see page 73 |
| 185mmbusbarsystem | Weight |
| Three-pole switching -each phase independently | |
| EBV233SV1 Cable terminals: V-terminals with V-clamps 240 mm2 | |
| EBV233SM1 Cable terminals: screw terminals with pressed nuts M10 | 5.8kg 5.7kg |
| EBV233SW1 Cable terminals: 2V-terminals with double V-clamps 240 mm² | 6,4kg |
| EBV233SV0 Cable terminals: V-terminals without V-clamps | 5.5kg |
| EBV223SW0 Cable terminals: 2V-terminals without double V-clamps | 6.9kg |
| Three-pole switching -all phases simultaneously | |
| EBV233TV1 Cable terminals: V-terminals with V-clamps 240 mm² | |
| EBV233TM1 Cable terminals: screw terminals with pressed nuts M10 | 5.8kg |
| EBV233TW1 Cable terminals:2V-terminalswith double V-clamps 240 mm² | 5,7kg 6,4kg |
| EBV233TVO Cable terminals: V-terminals without V-clamps | 5.5kg |
| EBV233TW0 Cable terminals: 2V-terminals without double V-clamps | 5.9kg |
| Description EBV2V-Clamps (400A) | EBV2Double V-Clamps | |||
| Clamp | V-clamp | V-clamp HS M10 screw (pressed nut)* | ||
| Outline drawing | 品 | 电 | ||
| Crnsusectionof Tightening torque | V-clamp for direct fixing of conductor with busbar end with crosssection of: | |||
| 35-185mm² 35-240mm² | 35 - 185 mm² | 35 -240 mm² | ||
| 35-240mm² 35-300 mm² 30 Nm | 35-240 mm² 35-300mm² 40 Nm | 32Nm | ||
EBV3 Vertical fuse switch disconnector,size 3,630A,690 V,185 mm busbar system
| Description | EBV3/185mm |
| Rated thermal current I=lwith fuse links | 630A |
| Rated thermal current I with solid links | 750A |
| Rated voltage U | 690Va.c. |
| Utilisationcategory | AC-22B AC-23B AC-21B |
| Rated switching voltage U | 500Va.c. 400Va.c. |
| Rated switching current l | |
| Rated short circuit making current | 630A 80 kA (690Va.c.) |
| 100 kA (500 Va.c.) | |
| Rated short circuit withstand current | 100 kA |
| Rated insulation voltage U | 1000Va.c. |
| Rated impulse withstand voltage Ui | 12 kV |
| Rated short time withstand current I | 121/15²kA |
| Rated frequency | 50-60 Hz |
| Mechanical durability (Number of cycles) | 1000 |
| Electrical durability (Number of cycles) | 200 |
| IP degree of protection | 30IP |
| Compatible NH Fuse link body size | 3 |
| 185mmbusbarsystem | Weight | |
| Three-pole switching-each phase independently | ||
| EBV333SV1 | Cable terminals:V-terminals with V-clamps 240 mm² | 6,6kg |
| EBV333SM2 | Cable terminals: screw terminals with pressed nuts M12 | 6.5kg |
| EBV333SW1 | Cable terminals: 2V-terminals with double V-clamps 240 mm² | 7.2kg |
| EBV333SV0 | Cable terminals: V-terminals without V-clamps | 6,3kg |
| EBV333SW0 | Cable terminals: 2V-terminals without double V-clamps | 6,7kg |
| Threepole switching-allphases simultaneously | ||
| EBV333TV1 | Cable terminals: V-terminals with V-clamps 240 mm² | 6,6kg |
| EBV333TM2 | Cable terminals: screw terminals with pressed nuts M12 | 6.5kg |
| EBV333TW1 | Cable terminals: 2V-terminals with double V-clamps 240 mm² | 7.2kg |
| EBV333TV0 | Cable terminals: V-terminals without V-clamps | 6.3kg |
| EBV333TW0 | Cable terminals: 2V-terminals without double V-clamps | 6.7kg |
| Description EBV3V-clamps | EBV3Double V-Clamps EBV3M12Screws | |||
| Clamp | V-clamp35-300SW-B | V-clampHS2/35240-C | M12screw(pressednut) | |
| Outline drawing | 国 | 品 | 中 | |
| Cross section of conductors Tightening torque | V-clamp for direct fixing of conductor with busbar end with cross section of: | |||
| 35-185mm² 8 | 35- 240 mm² 35-185 mm² | 8 35-240 mm² | ||
| 35-240mm² | 35-300 mm² 35-240mm² | 35-300 mm² | ||
| 30Nm | 40Nm | 56Nm | ||
EBV2and EBV3 Fuse switch disconnectorwith lateral busbar terminal\*
| Description | EBV2 | EBV3 |
| Rated thermal current lt=l | 400A | 630A |
| Rated voltage Un | 690Va.c. | 690Va.c. |
| Utilisation category | AC-22B | AC-22B |
| Rated switching voltage Ue | 690Va.c. | 500Va.c. |
| Rated switching current le | 400A | 630A |
| Rated short circuit making current | 100kA | 100 kA |
| Rated short circuit withstand current | 100 kA | 100 kA |
| Rated insulation voltage Ui | 1000Va.c. | 1000Va.c. |
| Rated impulse withstand voltage Uimp. | 12 kV | 12 kV |
| Rated frequency | 50-60 Hz | 50-60 Hz |
| Mechanical durability (numberof cycles | 1000 | 1000 |
| Electrical durability (number of cycles) | 200 | 200 |
| IP degree of protection (IP) | 30 | 30 |
| Compatible NH Fuse link body size | 2 | 3 |
| 185mmbusbarsystem Weight | |
| Fuse switch disconnectors EBV2 -400A | |
| Three-poleswitching-each phase independently | |
| EBV233SM2-L Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side | 5.1kg |
| EBV233SM2-R Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side | 5.1kg |
| Three-pole switching -all phases simultaneously | |
| EBV233TM2-L Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side | 5,1kg |
| EBV233TM2-R Cable terminals:screw terminals with pressed nuts M12, lateral busbar terminal - right side 5,1kg | |
| Fuse switch disconnectors EBV3-630A | |
| Three-poleswitching-each phase independently | |
| EBV333SM2-L Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side | |
| EBV333SM2-R | 5.9kg Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side 5.9kg |
| Threepole switching-allphases simultaneously | |
| EBV333TM2-L Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side | |
| EBV333TM2-R Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side | 5.9kg 5.9kg |
| Fuseswitchdisconnectors EBV3-1250A | |
| Threepoleswitching-all phasessimultaneously | |
| EBV3-1250-3-2M-L | Switch-disconnector 1250 A,equipped with solid-links 1250 A 7kg |
| EBV3-1250-3-3M-R Switch-disconnector 1250 A,equipped with solid-links 1250 A | Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - left side 7kg Cable terminals: screw terminals with pressed nuts M12, lateral busbar terminal - right side |
| Description | EBV2-x-NL (400 A) | EBV2-x-NR (400 A) | EBV3-x-NL (630 A) | EBV3-x-NR (630A) |
| Clamp | M12 screw | M12 screw | M12 screw | M12 screw |
| Outline drawing | 粤 | 粤 | ||
| Lateral busbar terminal | Left side | Right side | Left side | Right side |
| Tightening torque | 56Nm | 56Nm | 56Nm | 56Nm |
EBVwith electronic fuse monitoring module
Electronic fuse monitoring module
Fuse switch disconnector can be equipped with electronic fuse monitoringmodule.Fuse link status (operational,operated,loss of voltage) is indicatedby light-emittng diodesand status of relay contacts.
Principleofoperation
·L1,L2, L3 diodes are on -all three phases are supplied,all fuse links are operational.Relay contacts: [21.22]-closed; [13..14] -opened
·L1,L2,L3 diodesare flashing-all three phases are supplied, fuse links operated Relay contacts: [21.22]-opened; [13..14] -closed
·L1,L2,L3 diodes are off - two or more phases are not supplied orfuse links are removed.Relay contacts:[21..22]-opened; [13..14]-closed
Nominal parameters
·Operating voltage AC-400 - 690V, 40-60 Hz; ·Relay parameters 5A,250 V\~
EBVwith electronic fuse monitoring module
| Cataloguenumber Description | Weight | |
| Fuseswitch disconnectors EBV2 -400A | ||
| For installationon 185 mm busbar system,one pole switching -each phase independently | ||
| EBV233SV1-E | Cable terminals: V-terminals with V-clamps 240 mm² | 5.9 kg |
| EBV233SM1-E | Cable terminals: screw terminals with pressed nuts M10 | 5.8kg |
| EBV233SW1-E | Cable terminals: 2V-terminals with double V-clamps 240 mm² | 6.5kg |
| EBV233SV0-E | Cable terminals: V-terminals without V-clamps | 5.6kg |
| EBV233SW0-E | Cable terminals: 2V-terminals without double V-clamps | 6.0kg |
| Forinstallationon185mmbusbarsystem,three poleswitching-all phasessimultaneously | ||
| EBV233TV1-E | Cable terminals: V-terminals with V-clamps 240 mm² | 5.9kg |
| EBV233TM1-E | Cable terminals: screw terminals with pressed nuts M10 | 5.8kg |
| EBV233TW1-E | Cable terminals: 2V-terminals with double V-clamps 240 mm² | 6.5kg |
| EBV233TV0-E | Cable terminals: V-terminals without V-clamps | 5.6kg |
| EBV233TW0-E | Cable terminals: 2V-terminals without double V-clamps | 6,0kg |
| Fuseswitch disconnectors EBV3-630A | ||
| Forinstallationon185mm busbarsystem,onepole switching-each phase independently | ||
| EBV333SV1-E | Cable terminals: V-terminals with V-clamps 240 mm² | 6.7kg |
| EBV333SM2-E | Cable terminals: screw terminals with pressed nuts M12 | 6,6kg |
| EBV333SW1-E | Cable terminals: 2V-terminals with double V-clamps 240 mm² | 7.3kg |
| EBV333SV0-E | Cable terminals: V-terminals without V-clamps | 6,4 kg |
| EBV333SW0-E | Cable terminals: 2V-terminals without double V-clamps | 6.8kg |
| Forinstallationon185mm busbarsystem,three pole switching-allphases simultaneously | ||
| EBV333TV1-E | Cable terminals: V-terminals with V-clamps 240 mm² | 6.7kg |
| EBV333TM2-E | Cable terminals: screw terminals with pressed nuts M12 | 6.6kg |
| EBV333TW1-E | Cable terminals: 2V-terminals with double V-clamps 240 mm² | 7.3kg |
| EBV333TV0-E | Cable terminals: V-terminals without V-clamps | 6.4kg |
| EBV333TW0-E | Cable terminals: 2V-terminals without double V-clamps | 6.8kg |
EBVVertical fuse switch disconnectors - Outline drawings (mm)
EBV00/100mm,EBV00-1,EBV00-3
CLOSED
EBVVertical fuse switch disconnectors - Outline drawings (mm)
EBV00/100 mm,EBV00-1,EBV00-3 Closed3-phase
EBVVertical fuse switch disconnectors - Outline drawings (mm)
EBVVertical fuse switch disconnectors - Outline drawings (mm)
EBVVertical fuse switch disconnectors - Outline drawings (mm)
EBV2,EBV3withlateralbusbarterminal
EBVO0,EBV00/100m EBV00/100mm
EBFVA1-M8Terminal screw EBFVA35-Labelling area
Mteminasifa (set -3 pcs.) 号 Labelling area □ EBFVA2- Busbar shroud EBFVA10-Terminalshroud/adjusting shroud
Busbar shroud (polycarbonate) Terminal shroud/adjusting shroud. When
forbusbarsystem185mm,Width 50 mm, ft 一 length 562 mm, thickness 3 mm 2,3 enclosure
EBFVA4-Isolating pin EBFVA36-Extendedterminalshroud/adjusting shroud
shroud,M8 setps.) lsolating pin for fixing the 50 mm busbar Extended terminal shroud/adjusting shrod.
Together with two shrouds it adjusts the
EBFVA6-S-Bridge clamp length and height of EBVO0/100 mm to that
of EBV1,2,3 with terminal shroud
S-Bridge clamp-fixed with 2x M5 screw-for connection H EBFVA37-Extendedteinalsrodadustingrod
of conductors with cross-section Extended terminal shroud/adjusting shroud.
4 mm² up to 70 mm² (set-3 pcs.) When fixed to shroud it adjusts the length
EBFVA7-V-shape clamp 2
e M EBFVA11-Singleadaptor
conductors with cross-section 1,5 up to Singleadaptor100/185enabling
70 mm² (stranded) or 95 mm² to install EBV00/100mmonbusbar 9 (solid)(set- 3 pcs.) system 185 mm
EBFVA8-Universalarthingdevice EBFVA12-Doubleadaptor
Unievyoiei D Double adaptor100/185 enabling to install two EBV00/100 mm units on
busbar system 185 mm
EBVOO
EBFVA32-V-Clamp25-120SW EBFVA15-Singledistanceadaptor
V 16torm 9 Single distance adaptor 185/185. It adjusts frontlineof EBVOO to thatof EBV 111 2,3 (set-3 pcs.)
25-120mm² ? 25-120mm²
EBFVA14-Doubledistanceadaptor
EBFVA9-V-clampHM-10-120
V-clamp HM-10-120.Forconnectionof for two EBV OO units.It adjusts front line of Double distance adaptor 185/185. Designed 1 conductor with cross-section: D EBV OO to that of EBV 2,3 (set-3 pcs.)
10-70 mm² O 10 - 70 mm² ?
25-120mm² ? 25-95mm² 国 1 EBFVA3-Hooked clamps EBFVA16-Terminal shroud
Houssr (set-3 pcs.) 包 Terminal shroud 園 EBV00/100mm EBFVA38-Hookedclamps
EBFVA33-Micro switch Hookedclamps for installation
Micro switch for fuse link cover position 1 of EBV with heightened rails
monitoring (0-1)of EBV00/100mm n bsesrysersithotae C EBFVA34-Supportangle
Supportangle for installationof busbar 气
shroud
EBVVertical fuse switch disconnectors-Accessories
| EBV2,EV3,EV630KVA,E25 | EBV2,EBV3,EBV630VA,EV5 | ||
| Terminal screw | EBFVA25- Busbar shroud | ||
| Forconnectionofconductors with lug terminal (1 set- 3pcs) | Busbar shroud (polycarbonate) for busbar system 185 mm,width 100 mm,length | ||
| EBFVA17- M10 terminal screw for EBV1and EBV2 | 562 mm, thickness 3 mm EBFVA26- Isolating pin | ||
| EBFVA18 - M12 terminal screw for EBV3 | Isolating pin for fixing | ||
| EBFVA19-V-clamp | the5- m busbar shroudM12 | ||
| V-clamp.For connection of conductor with cross-section: | EBFVA27-Terminal shroud Terminal shroud | ||
| 35-120mm² 35-150 mm² | |||
| 35-240mm² 35-300mm² EBFVA20-V-clamp | |||
| V-clamp.For connection of conductor | EBFVA28-Extended terminal shroud Extended terminal shroud,foruse with | ||
| with cross-section: 35-185mm²35-240mm² | terminal shroud below | ||
| 35-240mm²35-300mm² | |||
| EBFVA21- Double V-clamp | EBFVA29-Terminal protective cover | ||
| Double V-clamp.For connection of two conductors with cross-section: | Terminal protective cover | ||
| 35-185mm²35-240mm² | |||
| 35-240mm²35-300mm² | EBFVA8-Universalearthingdevice Universal earthing device | ||
| EBFVA23-V-clamp HS V-clamp HS (steel) for connection of two | for EBV 00,2,3 | ||
| conductors with cross-section | |||
| 35-185mm²35-240mm² | EBFVA39-Label holder | ||
| 35-240mm²35-300mm² EBFVA24-Hooked clamps | Label holder | ||
| Hooked clamps forinstallation | |||
| of EBV2,3on busbar system without drilled holes (1 set-3 pcs.) | |||
NHDINFuselinksoverview
A square bodied range of NH DIN industrial fuse links for awidevarietyofapplications.
Description
Featuresandbenefits
·Comprehensive portfolio:Standard metal gripping lugs and insulated metal gripping lugs versions are available ·Reliability:Dual indication for more reliable fault finding. ·Safety:Leadandcadmium free-theyare RoHSand REACH compliant (not dangerous or hazardous for the environment). ·Energy efficient solutions: Class leading watts losshelping to improve network efficiencies.
Standards
IEC60269-1and2,VDE0636,DIN43620 and CE
| 400 Volts gG | 500VoltsgG | 690Volts gG | ||
| Catalogue numbers with conducting metal gripping lugs | (amp)NHG(size)B-400 | (amp)NHG(size)B | (amp)NHG(size)B-690 | |
| Catalogue numbers with insulated metal gripping lugs | (amp)NHG(size)Bl-400 | (amp)NHG(size)Bl | (amp)NHG(size)Bl-690 | |
| Fuse link body size | 000to3 | 000 to4 | 000 to4 | |
| Rated voltage | 400Va.c. | 500Va.c. | 690Va.c. | |
| Rated current | 2 to 630A | 2 to 1250A | 2 to 800A | |
| Operating Class | gG | gG | gG | |
| Breaking capacity | 120 kA AC | |||
| Fuse bases | Single pole SD -D DIN-Rail mounted and SD-S Screw mounting or TD-D DIN-Rail mounted (data sheet 10163) | |||
| Fuse switches | Fuse switch disconnectors vertical EBVand horizontal EBH (data sheets 10292 and 10293) | |||
| Fuse rail | Fuse rail vertical EBF (data sheet 10240) | |||
| Standards | IEC 60269-1and2,VDE 0636,DIN43620 and CE | |||
| Applications | Alternative energy, utilities,industrial and motor applications | |||
| 500/690VoltsaM | |
| Catalogue numbers with conducting metal gripping lugs | 500Volts: (amp)NHM(size)B 690 Volts: (amp)NHM(size)B-690 |
| Catalogue numbers with insulated metal gripping lugs | N/A |
| Fuse link body size | 000 to3 |
| Rated voltage Rated current | 500 and 690 Va.c. |
| 6 to 500A | |
| Operating Class Breaking capacity | aM 120 kA AC |
| Fuse bases | |
| Fuse switches | Single pole SD-D DIN-Rail mounted and SD-S Screw mounting or TD-D DIN-Rail mounted (data sheet 10163) Fuse switch disconnectors vertical EBV and horizontal EBH (data sheets 1O292 and 10293) |
| Fuse rail | Fuse rail vertical EBF (data sheet 10240) |
| Standards | IEC 60269-1and 2,VDE 0636, DIN 43620 and CE |
| Applications | Alternative energy, utilities,industrialand motor applications |
| s | Amps | |||||||||||||||
| 2 46 10 1620 25 32 3540 5063 80 100 125 160 200 224 250 300 315 355 400 425 450 500 630 | ||||||||||||||||
| 40 | 000 2 | 800 1000 1250 4 6 10 16 2025323540 50 63 80 100 125 160 | ||||||||||||||
| 00 | ||||||||||||||||
| 01 | ||||||||||||||||
| 1 | 200 | |||||||||||||||
| 02 2 | 224250 354050 63 80 100 125 160 200 224250 | |||||||||||||||
| 03 | ||||||||||||||||
| 3 | ||||||||||||||||
| 000 2461016202532 | ||||||||||||||||
| 00 | ||||||||||||||||
| 0 6 10 01 | ||||||||||||||||
| 500 | 16 20 25 32 35 40 | |||||||||||||||
| 610 16 20 25 32 35 40 50 63 80 100 125 160 | ||||||||||||||||
| G | ||||||||||||||||
| 1 50 63 80 100 125 160 200 224 250 315355 | ||||||||||||||||
| 2 | 02 3540 50 63 80 100 125 160 200 224 250 | |||||||||||||||
| 03 | 250 300 315 355 400 425 450 500 | |||||||||||||||
| 3 4 | 250 315 355 400 | |||||||||||||||
| 00 | 315 355 400 425 450 500 630 800 | |||||||||||||||
| 1000 1250 | ||||||||||||||||
| 500 630 800 | ||||||||||||||||
| 000 24610 16 20 25 32 3540 50 63 | ||||||||||||||||
| 50 63 80 100 125 160 | ||||||||||||||||
| 80 | 12 50 63 80 100 125 160 2020 2424 2020 | |||||||||||||||
| 315 | ||||||||||||||||
| 3 250 315 355400425 500 4 630800 | ||||||||||||||||
| Page | ||||
| Catalogue number | Page | Catalogue number | Catalogue number | Page |
| EBC00013TBF | 25 | EBFVA36 | 72 EBH103TS8 | 35 |
| EBC00013TTF | 25 | EBFVA37 72 | EBH103TS8-BE | 41 |
| EBC0003TF-D125 | 25 | EBFVA38 72 | EBH103TS8-TE | 41 |
| EBC0003TF-D150 | 25 | EBFVA39 73 | EBH103TSV | 35 |
| EBC000O3TF | 25 | EBFVA4 17 and 72 | EBH103TV1 | 35 |
| EBF00230S8 | 9 | EBFVA6 17 and 72 | EBH1O3TVM | 35 |
| EBF00230V0 | 9 | EBFVA7 17 and 72 | EBH103TVS | 35 |
| EBF00230V1 | 9 | EBFVA8 17,18 and 72 | EBH213TBM1 | 38 |
| EBF00330S8 | 10 | EBFVA9 17 and 72 | EBH213TBS8-E | 41 |
| EBF00330V0 | 10 | EBH00013TBM8 23 | EBH213TBV1 | 38 |
| EBF00330V1 | 10 | EBH00013TBS5 23 | EBH213TBW1 | 38 |
| EBF2330-L | 14 | EBH00013TTM8 23 | EBH213TTM1 | 38 |
| EBF2330M1 | 12 | EBH00013TTS5 23 | EBH213TTS8-E | 41 |
| EBF2330-R | 14 | EBH00003TM8 23 | EBH213TTV1 | 38 |
| EBF2330V1 | 12 | EBH00003TM8-D 23 | EBH213TTW1 | 38 |
| EBF2330W1 | 12 | EBH000O3TM8L 23 | EBH223TBM1 | 38 |
| EBF3330-L | 14 | EBH00003TS5 23 | EBH223TBS8-E | 41 |
| EBF3330M1 | 13 | EBH00003TS5-D 23 | EBH223TBV1 | 38 |
| EBF3330-R | 14 | EBH00003TS5L 23 | EBH223TBW1 | 38 |
| EBF3330V1 | 13 | EBH0013TBF 30 | EBH223TTM1 | 38 |
| EBF3330W1 | 13 | EBH0013TBM8 30 | EBH223TTS8-E | 41 |
| EBFVA1 | 17 and 72 | EBH0013TBS5-E 41 | EBH223TTV1 | 38 |
| EBFVA10 | 17 and 72 | EBH0013TTF 30 | EBH223TTW1 | 38 |
| EBFVA11 | 17 and 72 | EBH0013TTM8 30 | EBH203TM1 | 38 |
| EBFVA12 | 17 and 72 | EBH0013TTS5-E 41 | EBH203TS8 | 38 |
| EBFVA13 | 17 | EBH00O3TM8 28 | EBH203TS8-BE | 41 |
| EBFVA14 | 17 and 72 | EBH00O3TM8L 28 | EBH203TS8-TE | 41 |
| EBFVA15 | 17 | EBH00O3TS5 | EBH203TV1 | 38 |
| EBFVA16 | 17 and 72 | 28 EBH00O3TS5-BE 41 | EBH203TW1 | |
| EBFVA17 | 18 and 73 | EBH00O3TS5L 28 | EBH313TM2 | 38 40 |
| EBFVA18 | 18 and 73 | EBH0003TS5-TE 41 | EBH303TM2 | 40 |
| EBFVA19 | 18 and 73 | EBH00O3TV1 28 | EBH303TS8 | 40 |
| EBFVA2 | 17 and 72 | EBH113TBM1 35 | EBHA1 | 52 |
| EBFVA20 | 18 and 73 | EBH113TBS8 35 | EBHA10 | 52 |
| EBFVA21 | 18 and 73 | EBH113TBS8-E 41 | EBHA11 | 52 |
| EBFVA22 | 18 | EBH113TBV1 35 | EBHA12 | 52 |
| EBFVA23 | 18 and 73 | EBH113TTS8 35 | EBHA13 | 52 |
| EBFVA24 | 18 and 73 | EBH113TTS8-E | EBHA2 | 52 |
| EBFVA25 | 18 and 73 | 41 EBH113TTV1 35 | EBHA3 | 52 |
| EBFVA26 | 18 and 73 | EBH123TBM1 35 | EBHA4 | 52 |
| EBFVA27 | 18 and 73 | EBH123TBS8 35 | EBHA5 | 52 |
| EBFVA28 | 18 and 73 | EBH123TBS8-E 41 | EBHA6 | 52 |
| EBFVA29 | 18 and 73 | EBH123TBV1 35 | EBHA7 | 52 |
| EBFVA3 | 17 and 72 | EBH123TTM1 | EBHA8 | 52 |
| EBFVA31 | 18 | EBH123TTS8 | EBHA9 | 52 |
| EBFVA32 | 72 | EBH123TTS8-E | 35 41 EBHOO03TV1L | 28 |
| EBFVA33 | 72 | EBH123TTV1 | 35 EBV0011SS8 35 | 59 |
| EBFVA34 | 72 | EBH103TM1 | EBV0011SV0 | 59 |
| EBFVA35 | 72 | EBH103TMV | 35 EBV0011SV1 | 59 |
Index
| Catalogue number Page |
| EBV0011TS8 |
| EBV0011TV0 |
| EBV0011TV1 |
| 59 EBV0023TS8 58 |
| EBV0023TV0 58 |
| EBV0023TV1 58 |
| EBV0033SS8 |
| 59 EBV0033SV0 59 |
| EBV0033SV1 59 |
| EBV0033TS8 59 |
| EBV0033TV0 59 |
| EBV0033TV1 59 |
| EBV223SW0 62 |
| EBV233SM1 62 |
| EBV233SM1-E 66 |
| EBV233SM2-L 64 |
| EBV233SM2-R 64 |
| EBV233SV0 62 |
| EBV233SV0-E 66 |
| EBV233SV1 62 |
| EBV233SV1-E 66 |
| EBV233SW0-E 66 |
| EBV233SW1 62 |
| EBV233SW1-E 66 |
| EBV233TM1 62 |
| EBV233TM1-E 66 EBV233TM2-L 64 |
| EBV233TM2-R 64 |
| EBV233TV0 62 |
| EBV233TV0-E 66 |
| EBV233TV1 |
| 62 EBV233TV1-E |
| 66 EBV233TW0 62 |
| EBV233TW0-E 66 |
| EBV233TW1 62 |
| EBV233TW1-E 66 |
| EBV3-1250-3-2M-L 64 |
| EBV3-1250-3-3M-R 64 |
| EBV333SM2 63 |
| EBV333SM2-E 66 |
| EBV333SM2-L 64 |
| EBV333SM2-R 64 |
| EBV333SV0 63 |
| EBV333SV0-E 66 |
| EBV333SV1 63 |
| EBV333SV1-E 66 |
| EBV333SW0 63 |
| EBV333SW0-E 66 |
| EBV333SW1 63 |
| Catalogue number |
| Page EBV333SW1-E 66 |
| EBV333TM2 63 |
| EBV333TM2-E 66 |
| EBV333TM2-L 64 |
| EBV333TM2-R 64 |
| EBV333TV0 63 |
| EBV333TV0-E 66 |
| EBV333TV1 63 |
| EBV333TV1-E 66 |
| EBV333TW0 63 |
| EBV333TW0-E 66 |
| EBV333TW1 63 |
| EBV333TW1-E 66 |
| Notes |
Contactdetails
CustomerSatisfactionteam
Eaton's Customer Satisfaction team isavailable to answer questions regarding Bussmann series products.
Calls can be made between:
Monday-Thursday 7.30 a.m.-5.30 p.m.GMT Friday 7.30 a.m.-5.00 p.m.GMT
The Customer Satisfaction team can be reached via:
Phone: 00 44(0) 1509 882 600 Fax: 00 44(0) 1509 882 786 Email:bulesales@eaton.com
www.my.eaton.com
Tailored just for you.Powerful online tools and resources get you the up-to-date information you need to work smarter,make informed decisions and streamline your transactions with Eaton.
Get started today at www.my.eaton.com by clicking Request User IDand Password'.
·Easy to Navigate·Simple to Use·Real-Time Data.
Online resources
Visit www.eaton.com/bussmannseries for the following resources:
·Product cross reference
·Product profiles
·Online catalogues for the latest United States and European catalogues.
Application engineering
Application Engineeringassistance is available to all customers.The Application Engineering team is staffed by university-qualified electrical engineers who are available with technical and application support.
Calls can be made between:
Monday-Thursday 8.30 a.m.-4.30 p.m.GMT Friday 8.30 a.m.-4.00 p.m.GMT
Application Engineering can be reached via:
Phone: 00 44 (0) 1509 882 699
Fax: 00 44 (0) 1509 882 794
General technical enquiries: buletechnical@eaton.com
Highspeed technical enquiries: bulehighspeedtechnical @eaton.com
At Eaton,we're energized by the challenge of powering a world thatdemands more.With over 10o years experience in electrical powermanagement,we have the expertise to see beyond today.From groundbreaking products to turnkey design andengineeringservices,critical industriesaround the globe count on Eaton.
Wepower businesseswith reliable,efficientand safe electrical powermanagement solutions.Combined with our personal service,support and bold thinking,we are answering tomorrow'sneedstoday.Followthechargewith Eaton. Visit eaton.com/electrical.
Contact your local Eaton office
Eaton
Melton Road
Burton-on-the-Wolds
LE125TH
Leicestershire
United Kingdom
bulesales@eaton.com
www.eaton.com/bussmannseries
Eaton
Changes to the products, to the information contained in this document,and to prices are reserved; so are errors and omissions. Only order confirmations and technical documentation by Eaton is binding. Photos and pictures also do not warrant a specific layout or functionality. Their use in whatever form is subject to priorapproval byEaton.Thesame appliesto Trademarks (especially Eaton,Moeller, and Cutler-Hammer). The Terms and Conditions of Eaton apply, as referenced on Eaton Internet pages and Eaton order confirmations.
EMEA Headquarters Route de la Longeraie 7 1110 Morges,Switzerland Eaton.eu
2016 Eaton
All RightsReserved
Printed in the United Kingdom
Publication No. CA132061EN
July 2016
Eaton is a registered trademark
All other trademarks are property of their respective owners.
Follow us on social media to get the latest product and support information.