Leadership in fusible circuit protection
SERIES Bussmann series
NH Gear catalogue
Eaton is the leading source of fusible circuit
protection solutions in the global marketplace.
Eaton’s Bussmann series products are
approved for use around the world and meet
agency requirements and international
standards: IEC, VDE, DIN, UL, CSA, BS and
others.
The headquarter for Eaton’s Bussmann series product line
is located in Burton-on-the-Wolds, Leicestershire (UK)
and is part of Eaton’s Industrial Control and Protection
EMEA division.
Eaton manufactures over 50,000 Bussmann series part
numbers, covering extensive fusible circuit protection
solutions for a wide range of applications: residential,
industrial, motor protection, power conversion and
distribution.
Eaton has been a leading exponent in the design,
development and manufacture of fuse links and their
associated accessories for more than 100 years and has
supplied fuse links to more than 90 countries worldwide.
Eaton's team of specialist Engineers and Field
Applications Engineers plays a leading role in
international standardisation of fuse links offering
comprehensive advice on selection and
applications.
With a continual commitment to meet our customers'
needs with innovative high quality products with ISO
9001 'approval systems', Eaton is the supplier of choice
for circuit protection solutions.
2 EATON Bussmann series NH Gear catalogue
Eaton offers a wide range of Bussmann series fuse rails and switch
disconnectors.
Their compact dimensions and enhanced safety make them
suitable for varied applications. They are available up to 1600 A in
horizontal and up to 630 A in vertical format, suitable for mounting
NH fuselinks. They comply to IEC 60947-1 & IEC 60947-3.
The vertical fuse switch disconnectors (EBV00 - EBV3) are
available in 3 pole versions, and depending on application, are
rated from 160 A to 630 A; size 4 1250 A available on request.
Versatility of the product is enhanced by having the option to
reverse - top/bottom cable terminal connection. The body of the
switch is made of V0 flame retardant materials. IP30 degree of
protection is provided against any contact from the front. The
contacts are silver plated offering low watt loss. Current transformers and ammeters are available as accessories.
The vertical fuse rails (EBF000-EBF3) are available in 3 pole
version with variations in output clamps and rated at 160, 250, 400
and 630 A.
A comprehensive range of NH fuse bases suitable for industrial
application up to 690 V a.c..
Typical Applications for the vertical fuse switch disconnectors and
rails :
• Transformer substations
• Distribution boards
• Feeder pillars
• Cable distribution cabinets
The horizontal fuse switch disconnectors offers a
comprehensive choice of ratings and sizes (EBH000 – 100 A to
630 A) with direct connection to aluminium and copper cables and
wide range of cable terminations. Installation can be via a mounting plate or directly onto a busbar system with hooked clamps.
The body of the switch is made of V0 flame retardant materials.
The contacts are silver plated offering low watt loss.
Typical Applications :
• Motor Control Centres
• Distribution Boards
• Cable Distribution cabinets
EATON Bussmann series NH Gear catalogue 3
Table of contents
EBF Vertical fuse rail 5 - 18
EBH Horizontal fuse switch disconnector 19 - 52
EBV Vertical fuse switch disconnector 53 - 73
NH DIN Fuse links overview 74 - 75
Index 76 - 77
4 EATON Bussmann series NH Gear catalogue
EBF
EBF
Vertical fuse rail
• Self extinguishing thermoplastics with flame retardant
• Touch protection IP20 with fuse links shrouds
EBF Introduction 6
EBF Technical data 7
EBF Catalogue numbers structure 7
EBF00 100 mm busbar system 8-9
EBF00 185 mm busbar system 10
EBF2 185 mm busbar system 11-12
EBF3 185 mm busbar system 11 and 13
EBF2 and 3 with lateral busbar
terminal
14
Outline drawings 15-16
Accessories 17-18
EATON Bussmann series NH Gear catalogue 5
EBF
General information
Eaton’s Bussmann series NH vertical fuse rails are specifically designed to be used with NH fuse links. All energised metal parts are
fully protected against accidental contact. They are intended for direct installation on horizontal or vertical busbar systems.
Applications
EBF Vertical fuse rails are designed for the distribution of electricity and protection against short circuits and overloads in three phase
systems with maximum operating voltage of 690 V a.c. They are intended for direct installation on horizontal or vertical busbar system.
Due to their modern and compact design installing is easy and saves space in substations and distribution boards.
The EBF vertical fuse rails are designed to suit various market requirements and comply to IEC 60269-1 and 60269-2.
Sizes
EBF vertical fuse rails are available in following sizes:
• 00 (160 A)
• 2 (400 A)
• 3 (630 A)
Construction
Plastic parts of EBF vertical fuse rails are made of fibre glass strengthened, thermoplastic polyamides.
Silver plated contacts provide low power loss.
All energised metal parts are fully protected against accidental touch.
Removal of the fuse link provides clearly noticeable, large isolating gap in the circuit.
Flexibility to terminate circular or sector-shaped busbar conductors for V or 2V terminals. Conductors with lugs can be terminated with
screw terminals.
Touch protection IP 20 with fuse link shrouds for sizes 2 and 3 fuse rails.
Mounting
Sizes 00, 2 and 3 are designed for installation on 185 mm busbar system.
EBF00/100 mm fuse rails are designed for installation on 100 mm busbar system installation. They can be installed on 185 mm busbar
system by using an adaptor.
Fuse rails width
• size 00 – 50 mm
• size 2, 3 - 100 mm,
Operating conditions
• To be installed in a room free of any dust, aggressive or explosive gases
• Altitude up to 2000 meters above sea level
• Outdoor – in cabinets with protection degree > IP 34
• Ambient temperature from -25 °C to +55 °C – but in case of use of disconnectors in temperature from +41 °C to +45 °C current
value Ith should be reduced by 5 percent and within temperature range of +46 °C to +55 °C current value Ith should be reduced by 10
percent
• Relative humidity of the air should not be higher than 50 percent at temperature of +40 °C
6 EATON Bussmann series NH Gear catalogue
EBF
Example: EBF00330S8
Ordering code information Type designation
Product type EBF
NH Fuse links size 00
Mounting type 3
Number of poles 30
Terminal clamps S8
Complete part numbers EBF 00 3 30 S8
Catalogue number EBF00330S8
represents a vertical fuse rail, suitable
for NH Fuse links size 00, for 185 mm
busbar system 3, with 3 poles 30, with
screw terminals and M8 screws S8.
Vertical fuse
switch
disconnector
NH Fuse
link size Mounting type Poles Terminal clamps details Lateral busbar terminal
EBF 00
2
3
2 = 100 mm busbar
system
3 = 185 mm busbar
system
30 = Three-pole M1 = Screw terminals with M10 Screws
S8 = Screw terminals with M8 Screws
V0 = V-terminals without V-clamps
V1 = V-terminals with V-clamps
W1 = 2-V Terminals with double V-clamps
-L = Left side
- R = Right side
Catalogue number structure
Description EBF00 / 100 mm EBF00 / 185 mm EBF2 EBF3
Size 00 00 2 3
Rated thermal current Ith=In 160 A 160 A 400 A 630 A
Rated voltage Un 690 V a.c. 690 V a.c. 690 V a.c. 690 V a.c.
Rated insulation voltage Ui 1000 V a.c. 1000 V a.c. 1000 V a.c. 1000 V a.c.
Rated frequency 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz
Rated power dissipation 12 W 12 W 45 W 60 W
Rated short-circuit withstand current 100 kA 100 kA 100 kA 100 kA
Mechanical durability (number of cycles) 100 100 100 100
Weight (without terminals) 0,75 kg 2 kg 4,50 kg 5 kg
IP degree of protection (IP) 00 00 20* 20*
Compatible NH Fuse link body size 00 00 1, 2 3
Technical data
* with fuse link shrouds
EATON Bussmann series NH Gear catalogue 7
EBF
1 - Main base
2 - protective contact cover
3 - Terminal shroud
4 - Busbar terminals access covers
5 - S-bridge clamp
6 - M8 screw
7 - V-shape clamp for sector-shaped conductor
8 - Hooked clamp
EBF00 Vertical fuse rails, 100 mm busbar system
Description Terminal shroud label
7
4
3
5
6
8
1
2
Clip-on label
Insulating busbar barrier
location
EBF00/100 mm
EBF00/100 mm-V
For 100 mm busbar system
8 EATON Bussmann series NH Gear catalogue
EBF
EBF00 / 100 mm
EBF00 Vertical fuse rail, size 00, 160 A, 690 V a.c., 100 mm busbar system
EBF00/100 mm
Size 00
Rated thermal current Ith=In 160 A
Rated voltage Un 690 V a.c.
Rated insulation voltage Ui 1000 V a.c.
Rated frequency 50-60 Hz
Rated power dissipation 12 W
Rated short-circuit withstand current 100 kA
Mechanical durability (number of cycles) 100
IP degree of protection (IP) 00
Compatible NH Fuse link body size 00
Accessories see page 17
EBF00 Technical data
100 mm Busbar system Weight
EBF00230S8 Cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2
, screw terminals with M8 screws 1,0 kg
EBF00230V1 Cable terminals: V-terminals with V-clamps 25-120SW 1,1 kg
EBF00230V0 Cable terminals: V-terminals, without V-clamps 1,0 kg
EBF00 - Terminal clamps details
Description
Clamp S-bridge clamp 2 x M5 x 25 M8 screw* V- clamp 25-120 SW HM 10-120
Outline drawing
Cross–section
of conductors 4 - 70 mm2
Conductor with
lug terminal
max 185 mm2
re 16 mm2
- 95 mm2
se 25 mm2
- 120 mm2
re 10 mm2
- 70 mm2
se 25 mm2
- 120 mm2
rm 16 mm2
- 95 mm2
sm 25 mm2
- 120 mm2
rm 10 mm2
- 70 mm2
sm 25 mm2
- 95 mm2
Tightening torque 3 Nm** 12 Nm** 20 Nm** 15 Nm**
For stranded conductors using cable ferrules is recommended
*) Busbar of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M-type screw terminals.
**) Using torque wrench is recommended
***) Fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request
Recommend using Eaton V-terminals only. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system –12 Nm,
recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
***
EBF00 - Catalogue numbers
EATON Bussmann series NH Gear catalogue 9
EBF
EBF00 Vertical fuse rail, size 00, 160 A, 690 V a.c., 185 mm busbar system
Description EBF00
Size 00
Rated thermal current Ith=In 160 A
Rated voltage Un 690 V a.c.
Rated insulation voltage Ui 1000 V a.c.
Rated frequency 50-60 Hz
Rated power dissipation 12 W
Rated short-circuit withstand current 100 kA
Mechanical durability (number of cycles) 100
IP degree of protection (IP) 00
Compatible NH fuse link body size 00
Accessories see page 17
185 mm busbar system Weight
EBF00330S8 Cable terminals: bridge terminals with bridge clamps (S) 4-70 mm2
, screw terminals with M8 screws 2 kg
EBF00330V1 Cable terminals: V-terminals with V-clamps 25-120SW 2.1 kg
EBF00330V0 Cable terminals: V-terminals, without V-clamps 2 kg
EBF00 - Technical data
EBF00 - Terminal clamps details
Description EBF00
Clamp S-bridge clamp 2 x M5 x 25 M8 screw* V- clamp 25-120 SW HM 10-120
Outline drawing
Cross-section
of conductors 4 - 70 mm2
Conductor
with lug terminal
max 185 mm2
re 16 mm2
- 95 mm2
se 25 mm2
- 120 mm2
re 10 mm2
- 70 mm2
se 25 mm2
- 120 mm2
rm 16 mm2
- 95 mm2
sm 25 mm2
- 120 mm2
rm 10 mm2
- 70 mm2
sm 25 mm2
- 95 mm2
Tightening torque 3 Nm** 12 Nm** 20 Nm** 15 Nm**
For stranded conductors using cable ferrules is recommended
*) Busbar of maximum width of 20 mm and maximum thickness of 5 mm can be fixed to M-type screw terminals.
**) Using torque wrench is recommended
***) Fuse switch disconnectors with V-terminals are equipped with steel V-clamp HM 10-120 on request
Recommend using Eaton V-terminals only. Minimum tightening torque (M8 screw) for screws fixing fuse switch disconnector to busbar system
–12 Nm, recommended tightening torque for screws and nuts with property class 8.8 – 21 Nm
***
EBF00 - Catalogue numbers
EBF00 / 185 mm
10 EATON Bussmann series NH Gear catalogue
EBF
EBF2
EBF3
Option of fuse link state indication
by neon indicator tube
Terminal shroud label
7
4
3
5
6
9
8
1
2
Labels on busbar
terminals access covers
Clip-on label
1 - Main base
2 - Hooked clamp – for installation on busbar system
3 - Terminal shroud for fuse switch disconnector with
double V-clamps (2 x 240 mm2
)
4 - Terminal shroud (long)
5 - Terminal shroud (short)
6 - Bottom adjusting shroud
7 - Cable terminal protective cover
8 - Protective busbar barrier
Description
Vertical fuse rail, EBF2 size 2, 400 A and EBF3 size 3, 630 A, 690 V a.c., 185 mm busbar
system
EATON Bussmann series NH Gear catalogue 11
EBF
Parameters EBF2
Size 2
Rated thermal current Ith=In 400 A
Rated voltage Un 690 V a.c.
Rated insulation voltage Ui 1000 V a.c.
Rated frequency 50-60 Hz
Rated power dissipation 45 W
Rated short-circuit withstand current 100 kA
Mechanical durability (number of cycles) 100
IP degree of protection (IP) 20*
Compatible NH Fuse link body size 1,2
Accessories see page 18
EBF2 - Technical data
185 mm busbar system Weight
EBF2330V1 Cable terminals: V-terminals with V-clamps (35-240 mm2
) 3,2 kg
EBF2330M1 Cable terminals: screw terminals with pressed nuts M10 (M10 screw) 3,1 kg
EBF2330W1 Cable terminals: 2V-terminals with double V-clamps (2 x 50- 240 mm2
) 3,8 kg
EBF2 - Catalogue numbers
EBF2 Vertical fuse rail, size 2, 400 A, 690 V a.c., 185 mm busbar system
* With fuse link shrouds
EBF2 - Terminal clamps details
Description EBF2 V-clamps EBF2 Double V-clamps EBF2 M10 screw
Clamp V-clamp 35-300SW-B V-clamp HS 2/35-240-C M10 screw (pressed nut)*
Outline drawing
Cross-section of
conductors
V-clamp for direct fixing of conductor with busbar end with cross-section of:
35 - 185 mm2 35 - 240 mm2 35 - 185 mm2 35 - 240 mm2
35 - 240 mm2 35 - 300 mm2 35 - 240 mm2 35 - 300 mm2
Tightening torque 30 Nm 40 Nm 32 Nm
*For stranded conductors using cable ferrules is recommended
Busbar of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M-type screw terminals when protective busbar barrier between
phases is installed.
Recommend using Eaton V-terminals only. Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32
Nm, recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
EBF2
with fuse link shrouds
EBF2
Fuse rail designed for operation with NH1 and NH2 fuse links
12 EATON Bussmann series NH Gear catalogue
EBF
Parameters EBF3
Size 3
Rated thermal current Ith=In 630 A
Rated voltage Un 690 V a.c.
Rated insulation voltage Ui 1000 V a.c.
Rated frequency 50-60 Hz
Rated power dissipation 60 W
Rated short-circuit withstand current 100 kA
Mechanical durability (number of cycles) 100
IP degree of protection (IP) 20*
Compatible NH Fuse link body size 3
Accessories see page 18
EBF3 - Technical data
185 mm busbar system Weight
EBF3330V1 Cable terminals: V-terminals with V-clamps (70-300 SW) 4,0 kg
EBF3330M1 Cable terminals: screw terminals with pressed nuts M10 (M10 screw) 4,1 kg
EBF3330W1 Cable terminals: 2V-terminals with double V-clamps (2 x 50- 240 mm2
) 4,8 kg
EBF3
with fuse link shrouds
EBF3
EBF3 Vertical fuse rail, size 3, 630 A, 690 V a.c., 185 mm Busbar system
EBF3 - Terminal clamps details
*With fuse link shrouds
Description EBF3 V-clamps EBF3 Double V-clamps EBF3 M10 screw
Clamp V-clamp 35-300SW-B V-clamp HS 2/35-240-C M10 screw (pressed nut)*
Outline drawing
Cross-section of
conductors
V-clamp for direct fixing of conductor with busbar end with cross-section of:
35 - 185 mm2 35 - 240 mm2 35 - 185 mm2 35 - 240 mm2
35 - 240 mm2 35 - 300 mm2 35 - 240 mm2 35 - 300 mm2
Tightening torque 30 Nm 40 Nm 56 Nm
*For stranded conductors using cable ferrules is recommended
Busbar of maximum width of 40 mm and maximum thickness of 8 mm can be fixed to M-type screw terminals when protective busbar barrier between
phases is installed.
Recommend using Eaton V-terminals only. Minimum tightening torque (M12 screw) for screws fixing fuse switch disconnector to busbar system – 32 Nm,
recommended tightening torque for screws and nuts with property class 8.8 – 56 Nm
EBF3 - Catalogue numbers
EATON Bussmann series NH Gear catalogue 13
EBF
EBF Fuse rail with lateral busbar terminal technical data
Parameters EBF2 EBF3
Size 2 3
Rated thermal current Ith=In 400 A 630 A
Rated voltage Un 690 V a.c. 690 V a.c
Rated insulation voltage Ui 1000 V a.c. 1000 V a.c.
Rated frequency 50-60 Hz 50-60 Hz
Rated power dissipation 45 W 60 W
Rated short-circuit
withstand current 100 kA 100 kA
Mechanical durability (Number of cycles) 100 100
IP degree of protection (IP) 20* 20*
Compatible NH Fuse link body size 2 3
Accessories see page 18
*With fuse link covers
185 mm busbar system Weight
EBF2330-L Size 2 Lateral busbar terminal - left side 2,2 kg
EBF2330-R Size 2 Lateral busbar terminal - right side 2,2 kg
EBF3330-L Size 3 Lateral busbar terminal - left side 3 kg
EBF3330-R Size 3 Lateral busbar terminal - right side 3 kg
EBF2 and EBF3 Fuse rail, 185 mm busbar system, with lateral busbar terminal*
EBF3 with lateral
busbar terminal
- Left
EBF2 with lateral
busbar terminal
- Right
Description Outline drawing EBF2 Left side EBF2 Right side EBF3 Left side EBF3 Right side
Clamp M12 screw M12 screw M12 screw M12 screw
Cable terminal Left side Right side Left side Right side
Tightening torque 56 Nm 56 Nm 56 Nm 56 Nm
EBF (with lateral busbar terminal) - Terminal clamps details
EBF2 and 3 - Catalogue numbers
*Available upon request. Please contact Eaton’s application engineering department for further details: buletechnical@eaton.com
14 EATON Bussmann series NH Gear catalogue
EBF
EBF Vertical fuse rails - Outline drawings (mm)
EBF00 / 100 mm busbar system
M8 Screws V-Terminals M8 Screws
side view
V-Terminals
side view
EBF00 / 185 mm busbar system
M8 Screws V-Terminals
EATON Bussmann series NH Gear catalogue 15
EBF
EBF Vertical fuse rails - Outline drawings (mm)
EBF2 and 3 With terminals 2V (2 x 240 mm2
)
EBF2 and 3
EBF2 and 3
16 EATON Bussmann series NH Gear catalogue
EBF
EBF00 / 100 mm
EBFVA10 - Terminal shroud/adjusting shroud
Terminal shroud/adjusting shroud
EBFVA11 - Single adaptor
Single adaptor 100/185 enabling to
install EBF 00/100 mm on busbar system
185 mm
EBFVA12 - Double adaptor
Double adaptor 100/185 enabling to
install two EBF 00/100mm units
on busbar system 185 mm
EBFVA13 - Insulating busbar barrier
Insulating busbar barrier for EBF 00/100
mm
EBF00
EBFVA14 - Double distance adaptor
Double distance adaptor 185/185.
Designed for two EBF 00 units.
It adjusts front line of EBV 00
to that of EBV 1, 2, 3
(set – 3 pcs.)
EBFVA15 - Single distance adaptor
Single distance adaptor 185/185.
It adjusts front line of EBF 00
to that of EBV 1, 2, 3
(set – 3 pcs.)
EBFVA16 - Terminal shroud
Terminal shroud
EBF00, EBF00 / 100 mm
EBFVA1 - M8 Terminal screw
M8 terminal screw, for connection of
conductors with lug terminal (set - 3pcs)
EBFVA2 - Busbar shroud
Busbar shroud (polycarbonate) for busbar
system 185 mm, Width 50 mm, length 562
mm, thickness 3 mm
EBFVA3 - Hooked clamps
Hooked clamps for installation
of EBF on busbar system
without drilled holes.
(set - 3 pcs.)
EBFVA4 - Isolating pin
Isolating pin for fixing the 50 mm busbar
shroud, M8 (set – 2 pcs.)
EBFVA6 - S-Bridge clamp
S-Bridge clamp – fixed with 2 x M5 screw
- for connection of conductors with crosssection 4 mm2
up to 70 mm2
(set – 3 pcs.)
EBFVA7 - V-shape clamp
V-shape clamp – S-bridge clamp + V-shape
saddle - for connection of sector-shaped
conductors with cross-section 1.5 up to 70
mm2
(stranded) or 95 mm2
(solid)
(1 set - 3 pcs.)
EBFVA8 - Universal earthing device
Universal earthing device for EBF00, 2, 3
EBFVA9 - V-clamp
V- clamp HM-10-120. For connection of
conductor with cross-section:
10 - 70 mm2 10 - 70 mm2
25 - 120 mm2 25 - 95 mm2
EBF Vertical fuse rail - Accessories
EATON Bussmann series NH Gear catalogue 17
EBF
EBF2, EBF3
EBFVA25 - Busbar shroud
Busbar shroud (polycarbonate) for
busbar system 185 mm, Width 100 mm,
length 707 mm, thickness 2 mm
EBFVA26 - Isolating pin
Isolating pin for fixing the 100mm
busbar shroud, M12 (set – 2 pcs.)
EBFVA27 - Terminal shroud
Terminal shroud
EBFVA28 - Extended terminal shroud
Extended terminal shroud. For use with
terminal shroud EBFVA27
EBFVA29 - Terminal protective cover
Terminal protective cover
EBFVA31 - Fuse link shroud
Fuse link shroud
EBFVA8 - Universal earthing device
Universal earthing device
for EBV 00, 2, 3
EBF2, EBF3
Terminal screw
For connection of conductors
with lug terminal (1 set - 3pcs)
EBFVA17 - M10 terminal screw for EBF2
EBFVA18 - M12 terminal screw for EBF3
EBFVA19 - V-clamp
V-clamp. For connection of conductor
with cross-section:
35 - 120 mm2 35 - 150 mm2
35 - 240 mm2 35 - 300 mm2
EBFVA20 - V-clamp
V-clamp. For connection of conductor
with cross-section:
35 - 185 mm2 35 - 240mm2
35 - 240 mm2 35 - 300 mm2
EBFVA21 - Double V-clamp
Double V-clamp. For connection of two
conductors with cross-section:
35 - 185 mm2 35 - 240 mm2
35 - 240 mm2 35 - 300 mm2
EBFVA22 - V-terminal lug
V-terminal lug for V-clamp for
connection of conductors with crosssection 35 mm2
up to 240 mm2
EBFVA23 - V-clamp HS
V-clamp HS (steel) for connection of two
conductors with cross-section
35 - 135 mm2 35 - 240 mm2
35 - 240 mm2 35 - 300 mm2
EBFVA24 - Hooked clamps
Hooked clamps for installation
of EBF, 2, 3 on busbar
system without drilled holes
(set - 3 pcs.)
EBF Vertical fuse rail - Accessories
18 EATON Bussmann series NH Gear catalogue
EBH
EBH
Horizontal fuse switch disconnectors
Designed for distribution of electricity and protection of electrical equipment
against short-circuits and overloads with industrial fuse links.
EBH Introduction 20
EBH Technical data 21
EBH Catalogue numbers structure 22
EBH000 23-24
EBC000 Compact size 000 25-27
EBH00 Mounting plate installation 28-29
EBH00 60 mm busbar system 30-32
EBH00 Features and benefits 33-34
EBH1 35-37
EBH2 38-39
EBH3 40
Fuse switch disconnector electronic fuse
monitoring module
41
Outline drawings 42-51
Accessories 52
EATON Bussmann series NH Gear catalogue 19
EBH
Applications
EBH Horizontal fuse switch disconnectors are designed for distribution of electricity and protection of electrical equipment against shortcircuits and overloads with industrial fuse links. They are conforming to IEC 60947-1 and IEC 60947-3 standards. They are intended for
installation in low voltage distribution boards, cable and metering cabinets.
Sizes
EBH Horizontal fuse switch disconnectors are available in the following sizes:
• 000 (160 A)
• 00 (160 A)
• 1 (250 A)
• 2 (400 A)
• 3 (630 A)
Construction
Thermoplastic parts of EBH Horizontal fuse switch disconnectors are made of fibre glass strengthened polyamide with halogen free
flame retardant added and have the highest possible flammability class – V0.
EBH Horizontal fuse switch disconnectors consist of following parts:
• Three pole main base with spring-loaded contacts designed for connection of circular or sector-shaped conductors; conductors with
lug terminals or busbar
• Removable cover with fuse links,
Arc chutes with steel deionization plates over top contacts,
Silver plated contacts providing low power loss.
The making and breaking operations has to be done with adequate force since these are manually operated switches
Flexibility to terminate circular or sector-shaped busbar conductors for V-clamps or double V-clamps terminals. Conductors with lugs can
be terminated with screw terminals
Voltage test can be performed through test holes in fuse link cover
Monitoring of the fuse link status possible with electronic module
Mounting
On mounting plate
• EBH00 , EBH1 , EBH2 , EBH3
On double DIN-Rail
• EBH00
On busbar systems:
• 60 mm busbar system
• EBH00, EBH1, EBH2 – installation on busbar system with hooked clamps
• 100 mm busbar system
• EBH2, EBH1 – installation on busbar system with hooked clamps
Operating conditions
• To be installed in a room free of any dust, aggressive or explosive gases
• Altitude up to 2000 meters above sea level
• Outdoor – in cabinets with protection degree > IP 34
• Ambient temperature from -25 °C to +55 °C
• Relative humidity of the air should not be higher than 50 percent at temperature of +40°
20 EATON Bussmann series NH Gear catalogue
EBH
Technical data
EBH2 switch disconnector with solid links can be used for 400 A
• Rated short-time withstand current 1s Icw = 13 kA
• Rated short-circuit making capacity Icm = 8 kA
1) Ith - thermal current of fuse switch disconnector without external enclosure, installed outdoors (In case of the installation of fuse switch
disconnectors in enclosures then load factor should be considered)
2) for 60 mm busbar system
EBH000 EBH00 EBH1 EBH1 Busbar
system installation EBH2 EBH3
Rated thermal
current Ith
1) 160 A 160 A 250 A 250 A 400 A 630 A
Rated
voltage Un
690 V a.c. 690 V a.c. 690 V a.c. 690 V a.c. 690 V a.c. 690 V a.c.
Utilisation
category AC-23B AC-22B AC-22B AC-21B DC-21B AC-23B DC-21B DC-22B AC-23B DC-22B AC-23B AC-22B DC-22B2) AC-23B DC-21B DC-22B AC-22B DC-21B
Rated switching
current Ie
100 A 100 A 160 A 160 A 160 A 160 A 160 A 160 A 250 A 250 A 250 A 250 A 250 A 400 A 400 A 400 A 630 A 630 A
Rated switching
voltage Ue
400
V a.c.
690
V a.c.
400
V a.c.
690
V a.c.
250
V a.c.
690
V a.c.
440
V a.c.
250
V a.c.
690
V a.c.
250
V a.c.
400
V a.c.
690
V a.c.
250
V a.c.
690
V a.c.
440
V a.c.
220
V a.c.
690
V a.c.
250
V a.c.
Rated short circuit
making current 100 kA (400 and 690 V a.c.)
15 kA
(400 &
690 V a.c.)
80 kA
(690 V a.c.) 20 kA
(400 & 690 V a.c.)
80 kA
(690 V a.c.) 25 kA
(400 V &
690 V a.c.)
80 kA (690 V a.c.) 25 kA
(400 &
690 V a.c.)
80 kA
(690 V a.c.) 15 kA
(400 &
690 V a.c.)
20 kA
(400 .&
690 V a.c.)
100 kA
(400 & 690 V a.c.) 100 kA
(400 V a.c.)
100 kA
(400 V a.c.) 100 kA (400 V a.c.) 100 kA
(400 V a.c.)
Rated short circuit
withstand current 25 kA (400 and 690 V a.c.)
15 kA
(400 &
690 V a.c.)
80 kA
(690 V a.c.) 20 kA
(400 & 690 V a.c.)
80 kA
(690 V a.c.) 25 kA
(400 &
690 V a.c.)
80 kA (690 V a.c.) 25 kA
(400 &
690 V a.c.)
80 kA (690 V a.c.)
25 kA
(400 & 690 V a.c.) 100 kA
(400 V a.c.)
100 kA
(400 V a.c.)
100 kA
(400 V a.c.) 100 kA (400 V a.c.)
Rated insulation
voltage Ui
1000 V 1000 V 1000 V 1000 V 1000 V 1000 V
Rated power
dissipation 12 W 12 W 32 W 32 W 34 W 60 W
Rated impulse
withstand
voltage Uimp.
8 kV 8 kV 8 kV 8 kV 8 kV 12 kV 12 kV
Rated
frequency 50-60 Hz - 50-60
Hz - 50-60
Hz - 50-60 Hz - 50-60
Hz - 50-60
Hz -
Mechanical durability
(number of cycles) 2000 1600 1600 1600 1000 1000
Electrical durability (number
of cycles) 300 200 200 200 200 200
IP degree of
protection (IP) 20 20 30 30 20 20
Weight ~0.6 / ~0.9 kg ~0.7 / ~0.9 kg ~2 kg ~2,5 kg ~3 / ~4.5 kg ~5 / ~5.9 kg
Compatible NH Fuse
link body size 000 00 1 1 2 3
EATON Bussmann series NH Gear catalogue 21
EBH
Example: EBH00O3TS5
Ordering code information Type designation
Product type EBH
NH Fuse link size 00
Mounting type 0
Number of poles 3
Simultaneous or separate switching T
Terminal clamps S5
Complete part numbers EBH 00 O 3 T S5
Catalogue number EBH00O3TS5
represents a horizontal fuse switch
disconnector, suitable for NH Fuse link
size 00, mounting plate installation
O, 3-pole 3, simultaneous 3 phase
switching T, with S-bridge clamps, M5
screws S5.
Horizontal
fuse switch
disconnector
NH Fuse
link size Mounting type Poles Switching type Connection type Terminal clamps details Installation
EBH 000
00
1
2
3
O = Mounting
plate installation
1 = 60 mm
busbar system
2 = 100 mm
busbar system
3 =
3-pole
S = Each phase
switching
separately
T = Simultaneous 3
phase switching
B = Bottom cable
terminal connection
with lug terminals
T = Top cable terminal
connection with lug
terminals
F = Busbar ends
M2 = Screw terminals with M12 screws
M8 = Screw terminals with M8 scews
M1 = Conductors with lug terminals with
M10 screws
MV = Screw terminals / V-clamps
S5 = S-Bridge clamps with M5 screws
S8 = Screw terminals with M8 Screws
SV = S-bridge clamps / V-clamps
V1 = V-shape clamps
VS= V clamps / S-bridge clamps
VM = V clamps / Screw terminals
W1 = Double V-Clamps
-D = installation on
DIN-Rail
L = Lengthened terminal
shrouds
- E, -TE, -BE Electronic
fuse monitoring module,
see details page 41
Miscellaneous parts: EBC000: Compact fuse switch disconnector size 000 see details pages 25-27
Catalogue number structure
22 EATON Bussmann series NH Gear catalogue
EBH
EBH000
for installation on mounting plate
Installation on mounting plate Cable terminal
EBH000O3TS5 For connection of round conductors S-bridge clamps
EBH000O3TS5-D For connection of round conductors, possible installation on DIN-Rail S-bridge clamps
EBH000O3TM8 For connection of round conductors with lug terminals M8 screws
EBH000O3TM8-D For connection of round conductors with lug terminals, possible installation on DIN-Rail M8 screws
EBH000O3TS5L For connection of round conductors,lengthened terminal shrouds S-bridge clamps
EBH000O3TM8L For connection of round conductors with lug terminals, lengthened terminal shrouds M8 screws
60 mm busbar system Cable terminal
EBH00013TBS5 Cable terminal – bottom, for connection of round conductors S-bridge clamps
EBH00013TTS5 Cable terminal – top, for connection of round conductors S-bridge clamps
EBH00013TBM8 Cable terminal – bottom, for connection of conductors with lug terminals M8 screws
EBH00013TTM8 Cable terminal – top, for connection of conductors with lug terminals M8 screws
EBH000 - Technical data
Parameters EBH000
Rated thermal current Ith=ln 100/160 A
Rated voltage Un
690 V a.c.
Utilisation category AC-23B AC-22B AC-21B DC-21B
Rated switching voltage Ue 400 V a.c. 400 V a.c. 690 V a.c. 250 V a.c.
Rated switching current Ie 100 A 100 A 100 A 160 A
Rated short circuit making current 25 kA
Rated short circuit withstand
current 100 kA
Rated insulation voltage Ui 1000 V
Rated impulse withstand voltage Uimp
8 kV
Rated power dissipation 12 W
Rated frequency 50-60 Hz -
Mechanical durability (number of cycles) 2000
Electrical durability (number of cycles) 300
IP degree of protection (IP) IP 20
Compatible NH Fuse link body size 000
Accessories see page 52
EBH000 - Catalogue numbers
EBH000 Horizontal fuse switch disconnectors, size 000, 160 A and 690 V a.c.
EATON Bussmann series NH Gear catalogue 23
EBH
EBH000 for installation on 60 mm busbar system
Description Clamp Drawing
of clamp
Cross-section of
conductors Cu busbar Tightening
torque
Dimensions and spacing of holes
for installation of EBH000 on
mounting plate
EBH000
S-bridge
clamp
2 x M5 x 16
Cu/Al
conductor
1,5 - 35 mm2
maximum
busbar
width
15 mm
3 Nm*
M8 x 16
screw
conductor with
lug terminal up
to 70 mm2
maximum
busbar
width
15 mm
10 Nm*
For stranded conductors using cable ferrules is recommended
*Using of torque wrench is recommended
EBH000 - Terminal clamps details
EBH000
for mounting on DIN-Rail
EBH000 for installation on mounting plate
with double terminal shrouds
EBH000
for installation on mounting plate
with single terminal shrouds
Ø6,5
50
EBH000, Horizontal fuse switch disconnectors, size 000, 160 A and 690 V a.c.
24 EATON Bussmann series NH Gear catalogue
EBH
Installation on mounting plate Cable terminal
EBC000O3TF For connection of round conductors Frame clamps
Installation on double DIN-Rail Cable terminal
EBC0003TF-D125 Double DIN-Rail with spacing of 125 mm Frame clamps
EBC0003TF-D150 Double DIN-Rail with spacing of 150 mm Frame clamps
60 mm busbar system Cable terminal
EBC00013TTF Cable terminal-top, for connection of conductors with busbar ends Frame clamps
EBC00013TBF Cable terminal-bottom, for connection of conductors with busbar ends Frame clamps
EBC000 - Technical data
EBC000 - Catalogue numbers
Compact EBC000 Horizontal fuse switch disconnectors 125 A, 690 V a.c. for mounting
on plate and on double DIN-Rail and for installation on 60 mm busbar system*
Description Cable terminal Drawing
of clamp
Cross-section of
conductors Tightening torque
EBC000 Frame clamps 2,5 - 50 mm- 6 Nm 3 Nm****
For stranded conductors using cable ferrules is recommended
****Using of torque wrench is recommended
EBC000 - Terminal clamps details
Compact dimensions - consume half the space
Protective covers provide touch protection
Built-in hooked clamps provide fast installation on busbar system
Top/bottom cable terminal
EBC000
Description EBC000
Rated thermal current Ith 125 A
Rated voltage Un 690 V a.c.
Utilisation category AC-21B** AC-22B*** AC-23B DC-22B
Rated switching voltage Ue 690 V a.c. 690 V a.c. 400 V a.c. 250 V a.c.
Rated switching current Ie 125 A 125 A 125 A 100 A
Rated short circuit making current
50*/35** kA (690 V a.c.) 20 kA
(400, 500 & 690 V a.c.) 50 kA (500 V a.c.)
80 kA (400 V a.c.)
Rated short circuit withstand current 80 kA (400, 500 & 690 V a.c.) 20 kA
(400, 500 & 690 V a.c.)
Rated insulation voltage Ui 1000 V
Rated impulse withstand voltage Uimp 6 kV
Rated power dissipation 9 W
Rated frequency 50-60 Hz -
Mechanical durability (number of cycles) 1600
Electrical durability (number of cycles) 200
IP degree of protection IP 30
Compatible NH Fuse link body size 000
*- EBH 000 , ***- EBH 000 -S
* EBC Available upon request. Please contact Eaton’s application engineering department for further details: buletechnical@eaton.com
EATON Bussmann series NH Gear catalogue 25
EBH
70 mm
Fuse switch disconnectors EBC000 are designed for installation of distribution board’s protective panels at two depths:
covering system at 70 mm depth: covering system at 32 mm and 70 mm depth
Distribution board’s
protective panel
installation depth
With cables connected
to the top cable terminal
EBC000
With cables connected to
the bottom cable terminal EBC000
Fuse switch disconnectors EBC000 are manufactured in
two versions depending on type of cable terminal
- With bottom cable terminal
- With top cable terminal
32 mm
Covering system at 32 mm depth
Distribution board’s
protective panel
installation depth
Save space in the switchboard with EBC000*
106
106
53 53 106
106
53 53
EBH00 EBC000 EBH00 EBC000
Covering system at 70 mm depth
EBC000 -S (EBC000 ) width dimensions is equal to half the width of EBH00 -S (EBH00 ), so we can install more disconnectors (keeping
a certain width of the switchboard) to protect individual circuits in the switchboard.
*EBC Available upon request. Please contact Eaton’s application engineering department for further details: buletechnical@eaton.com
26 EATON Bussmann series NH Gear catalogue
EBH
Fuse switch disconnector EBC000 suitable for busbar systems has a special cavity.
Cavity for
busbar
system’s
support
It is possible to install microswitch indicating position open/close fuse switch disconnectors.
Slot to insert wires
connected to
microswitch
Fuse switch disconnector EBC000
for mounting on double DIN-Rail
EBC000
mounting on plate
Compact EBC000 Horizontal fuse switch disconnector - Installation details*
*EBC Available upon request. Please contact Eaton’s application engineering department for further details: buletechnical@eaton.com
EATON Bussmann series NH Gear catalogue 27
EBH
Installation on mounting plate Cable terminal
EBH00O3TS5 For connection of round conductors S-bridge clamps
EBH00O3TM8 For connection of conductors with lug terminals M8 screws
EBH00O3TV1 For connection of sector-shaped conductors V-shape clamps
EBH00O3TS5L For connection of round conductors, lengthened terminal shrouds S-bridge clamps
EBH00O3TM8L For connection of conductors with lug terminals, lengthened terminal shrouds M8 screws
EBHOO03TV1L For connection of sector-shaped conductors, lengthened terminal shrouds V -shape clamps
EBH00
EBH00 - Technical data
EBH00 - Catalogue numbers
EBH00 Horizontal fuse switch disconnectors, size 00, 160 A, 690 V a.c.
Description EBH00
Rated thermal current Ith 160 A
Rated voltage Un 690 V a.c.
Utilisation category AC-23B DC-22B DC-21B
Rated switching voltage Ue 690 V a.c. 250 V a.c. 440 V a.c.
Rated switching current Ie 160 A 160 A 160 A
Rated short circuit making
current
690 V a.c. 80 kA (690 V a.c.) 20 kA (400 & 690 V a.c.) 400 V a.c. 100 kA (400 V a.c.)
Rated short circuit withstand
current
690 V a.c. 80 kA (690 V a.c.) 20 kA (400 & 690 V a.c.) 400 V a.c. 100 kA (400 V a.c.)
Rated insulation voltage Ui 1000 V
Rated impulse withstand voltage Uimp 8 kA
Rated power dissipation 12 W
Rated frequency 50-60 Hz -
Mechanical durability (number of cycles) 1600
Electrical durability (number of cycles) 200
IP degree of protection IP 20
Compatible NH Fuse link body size 00
Accessories see page 52
Double DIN-Rail options available, please contact buletechnical@eaton.com for further details28 EATON Bussmann series NH Gear catalogue
EBH
Description Clamp Drawing
of clamps
Cross-section of
conductors
Cu
Busbar
Tightening
torque
Dimensions and spacing of holes
for installation of EBH 00
on mounting plate
EBH00
S-bridge
clamp
2 x M5 x 16
Cu/Al conductor
4 - 50 mm2
Maximum
busbar width
20 mm
3 Nm*
M8 x 16
screw
conductor with lug
terminal up to 70 mm2
Maximum
busbar width
20 mm
10 Nm*
V-shape
clamp
2 x M5 x 20
Maximum
busbar width
20 mm
3 Nm*
EBH00 - Terminal clamps details
For stranded conductors using cable ferrules is recommended
*Using of torque wrench is recommended
R
5 70
R
66 3
7
1,5 mm2
- 2,5 mm2
4 mm2
- 70 mm2
4 mm2
- 95 mm2
Fuse switch disconnector EBH00
with additional terminal shrouds
Fuse switch disconnector EBH00
for mounting on double DIN-Rail*
EBH00
EBH00 Horizontal fuse switch disconnectors, size 00, 160 A, 690 V a.c.
*please contact buletechnical@eaton.com for further details.
EATON Bussmann series NH Gear catalogue 29
EBH
EBH00 - Technical data
Description EBH0013T
Rated thermal current Ith 160 A
Rated voltage Un 690 V a.c.
Utilisation category AC-23B AC-22B DC-22B
Rated switching voltage Ue 400 V a.c. 690 V a.c. 250 V a.c.
Rated switching current I
e 160 A 160 A 160 A
Rated short circuit making current 100 kA 20 kA
Rated short circuit withstand current 100 kA 20 kA
Rated insulation voltage Ui 1000 V a.c.
Rated impulse withstand voltage Uimp 8 kV
Rated power dissipation 12 W
Rated frequency 50-60 Hz -
Mechanical durability (Number of cycles) 1600
Electrical durability (Number of cycles) 200
IP degree of protection IP 20
Compatible NH Fuse link body size 00
Accessories see page 52
EBH00 - Catalogue numbers
Description Clamp Drawing
of clamp
Cross-section of
conductors
Cu
busbar
Tightening
torque
EBH00-M8 M8 x 16
screw
Conductor with lug terminal
up to 70 mm2
Maximum busbar width
20 mm 10 Nm*
EBH00-F Frame clamps 4 - 95 mm2 - 6 Nm*
3 Nm*
For stranded conductors using cable ferrules is recommended
*Using of torque wrench is recommended
EBH00 Horizontal fuse switch disconnectors, size 00, 160 A, 690 V a.c., 60 mm busbar
system
EBH00 - Terminal clamps details
60 mm busbar system installation Cable terminal
EBH0013TBM8 Cable terminal – bottom, for connection of conductors with lug terminals M8 screws
EBH0013TTM8 Cable terminal – top, for connection of conductors with lug terminals M8 screws
EBH0013TBF Cable terminal – bottom, for connection of conductors with busbar ends Frame clamps
EBH0013TTF Cable terminal – top, for connection of conductors with busbar ends Frame clamps
System of protective covers provides touch protection
Possible installation of distribution board’s protective panel at depth of 32 mm or 70 mm
Built-in hooked clamps provide fast installation onto busbar system
Top/bottom cable terminal
EBH00
60 mm busbar system
30 EATON Bussmann series NH Gear catalogue
EBH
Fuse switch disconnector EBH00 suitable for busbar system has special cavity in its main base
Cavity
for busbar
system’s
support
Fuse switch disconnectors EBH00 busbar mount type are designed for installation of distribution board’s protective panels at two
depths: covering system at 32 mm and 70 mm depth
70 mm
distribution board
protective panel
installation depth
32 mm
With cables connected to the top cable terminal
EBH00
With cables connected to the bottom cable terminal EBH00
Fuse switch disconnectors EBH00 are manufactured in two versions depending on type of cable terminal:
• EBH00 with bottom cable terminal
• EBH00 with top cable terminal
Covering system at 32 mm depth Covering system at 70 mm depth
EBH00 Horizontal fuse switch disconnectors, Installation details
distribution board
protective panel
installation depth
EATON Bussmann series NH Gear catalogue 31
EBH
Cable terminals:
M8 screw terminal EBH00
It is possible to install microswitch indicating position of fuse switch disconnectors EBH00
Slot to insert wires
connected to
microswitch
Frame clamp EBH00
EBH00 Fuse switch disconnectors - Installation details
32 EATON Bussmann series NH Gear catalogue
EBH
New features of cable terminals
• Connection of one or two sector-shaped conductors with cross-section up to 120 mm2
• Connection of two round conductors with busbar ends and cross-section up to 70 mm2
Space saving
• Possible reduction of external width of cable distribution cabinet to width of a fuse switch disconnector
Effi cient current circuit
• No screw or riveted connection between contact and cable terminal (uniform design of current circuit ensures lower
power loss and operating temperature)
Safety
• Fuse cover and cable terminal cover sealing
• Extension of covering of conductors connected to cable terminals by installation of additional covers
Sealing of a fuse
switch disconnector
Sealing
of terminal cover
Possible connection
of two sector-shaped
conductors with
cross-section up to 120
mm2
each with double
V-clamp
Extension of covering of
conductors connected
to cable terminals
by installation
of additional covers
Flexibility to connect
two round conductors
with cross-section up
to 70 mm2
with
Prism clamp
Description label
Description label
EBH00 - Features and benefi ts
EATON Bussmann series NH Gear catalogue 33
EBH
EBH00 - Extended covering of conductors connected to cable terminal
For extension of covering of conductors connected to cable terminals, for example: to fully cover cables in cable distribution cabinet, any
required number of additional covers could be installed. Cover length - 50 mm.
EBH00 with V-clamp for connection of sector-shaped conductors with cross-section up to 120 mm2
Additional covers
34 EATON Bussmann series NH Gear catalogue
EBH
EBH1 Horizontal fuse switch disconnectors, size 1, 250 A, 690 V a.c.
EBH1 - Technical data
* For 60 mm busbar system
EBH1
for installation
on mounting plate
EBH1 - Catalogue numbers
Installation on mounting plate Cable terminals
EBH1O3TS8 For connection of round conductors S-bridge clamps
EBH1O3TM1 For connection of conductors with lug terminals Screws
EBH1O3TV1 For connection of sector-shaped conductors V-clamps
EBH1O3TVS For connection of round conductors, top terminals - V-terminals, bottom terminals - S-bridge terminals V- clamps / S-bridge clamps
EBH1O3TVM For connection of round conductors, top terminals - V-terminals, bottom terminals - screw terminals V- clamps /screws
EBH1O3TSV For connection of round conductors, top terminals - S-bridge terminals, bottom terminals - V-terminals S-bridge clamps / V- clamps
EBH1O3TMV For connection of round conductors, top terminals - screw terminals, bottom terminals - V-terminals screw terminals / V- clamps
60 mm busbar system Cable terminals
EBH113TTS8 Top cable terminals, for connection of round conductors S-bridge clamps
EBH113TBS8 Bottom cable terminals, for connection of round conductors S-bridge clamps
EBH113TBM1 Bottom cable terminals, for connection of conductors with lug terminals Screws
EBH113TTV1 Top cable terminals, for connection of sector-shaped conductors V- clamps
EBH113TBV1 Bottom cable terminals, for connection of sector-shaped conductors V- clamps
100 mm busbar system Cable terminals
EBH123TTS8 Top cable terminals, for connection of round conductors S-bridge clamps
EBH123TBS8 Bottom cable terminals, for connection of round conductors S-bridge clamps
EBH123TTM1 Top cable terminals, for connection of conductors with lug terminals Screws
EBH123TBM1 Bottom cable terminals, for connection of conductors with lug terminals Screws
EBH123TTV1 Top cable terminals, for connection of sector-shaped conductors V-clamps
EBH123TBV1 Bottom cable terminals, for connection of sector-shaped conductors V-clamps
Description EBH103
Mounting plate installation
EBH113 and EBH123
60 mm and 100 mm busbar system
Rated thermal current Ith=In 250 A 250 A
Rated voltage Un 690 V 690 V
Utilisation category AC-23B DC-22B AC-23B AC-22B DC-22B*
Rated switching voltage Ue 690 V a.c. 250 V a.c. 400 V a.c. 690 V a.c. 250* V a.c.
Rated switching current Ie 250 A 250 A 250 A
Rated short circuit
making current 80 kA (690 V a.c.)
100 kA (400 V a.c.)
25 kA
(400 & 690 V a.c.)
80 kA (690 V a.c.)
100 kA (400 V a.c.)
25* kA
(400 & 690 V a.c.) Rated short circuit
withstand current
Rated insulation voltage Ui 1000 V 1000 V
Rated impulse withstand
voltage Uimp
8 kV 8 kV
Rated power dissipation 32 W 32W
Rated frequency 50-60 Hz - 50-60 Hz -
Mechanical durability (Number of cycles) 1600 1600
Electrical durability (Number of cycles) 200 200
IP degree of protection (IP) 30 30
Compatible NH Fuse link body size 1 1
Accessories see page 52
EATON Bussmann series NH Gear catalogue 35
EBH
Description EBH1 EBH1 M10 screw EBH 1 V-clamps
Clamp S-bridge clamp 2xM8x30 M10x25 screw V-clamp HS 35-300-C
Picture of a clamp
Drawing of a clamp
Cross-section of
conductors
Cu/Al conductor
35 - 120 mm2
Conductor with lug terminal
up to 120 mm2
V-clamp for direct fixing of conductor with
busbar end with cross-section of:
35 - 185 mm2
35 - 240 mm2
35 - 240 mm2
35 - 300 mm2
Cu busbar maximum busbar width 35 mm
Tightening torque 10 Nm* 20 Nm* 40 Nm*
Dimensions and spacing
of holes for installation
of EBH1 on mounting plate
For stranded conductors using cable ferrules is recommended
*Using of torque wrench is recommended
94
50
11
8
6
R
EBH1 - Terminal clamps details
EBH1 Horizontal fuse switch disconnectors, size 1, 250 A, 690 V a.c.
36 EATON Bussmann series NH Gear catalogue
EBH
EBH1
for installation on busbar system
EBH1
for installation on mounting plate
EBH1
for installation on mounting plate,
with double terminal shrouds
EBH1
for installation on mounting plate, picture of fuse switch
disconnector without fuse links cover and terminal
shrouds, top cable terminal - M screws, bottom cable
terminal - V-clamps, (EBH1 bottom cable terminal - M
screws, top cable terminal - V-clamps)
EBH1 Horizontal fuse switch disconnectors, size 1 installation details
EATON Bussmann series NH Gear catalogue 37
EBH
EBH2 - Technical data
EBH2
for installation on mounting plate
EBH2 Horizontal fuse switch disconnector, size 2, 400 A, 690 V a.c.
Installation on mounting plate Cable terminals
EBH2O3TS8 For connection of round condutors S-bridge clamps
EBH2O3TM1 For connection of sector-shaped condutors V-clamps
EBH2O3TV1 For connection of sector-shaped conductors Double V- clamps
EBH2O3TW1 For connection of conductors with lug terminals M10 screws
60 mm busbar system Cable terminals
EBH213TBM1 Bottom cable terminals, for connection of conductors with lug terminals M10 screws
EBH213TTM1 Top cable terminals, for connection of conductors with lug terminals M10 screws
EBH213TBV1 Bottom cable terminals, for connection of sector-shaped conductors V-clamps
EBH213TTV1 Top cable terminals, for connection of sector-shaped conductors V-clamps
EBH213TBW1 Bottom cable terminals, for connection of sector-shaped conductors Double V- clamps
EBH213TTW1 Top cable terminals, for connection of sector-shaped conductors Double V- clamps
100 mm busbar system Cable terminals
EBH223TBM1 Bottom cable terminals, for connection of conductors with lug terminals M10 screws
EBH223TTM1 Top cable terminals, for connection of conductors with lug terminals M10 screws
EBH223TBV1 Bottom cable terminals, for connection of sector-shaped conductors V-clamps
EBH223TTV1 Top cable terminals, for connection of sector-shaped conductors V-clamps
EBH223TBW1 Bottom cable terminals, for connection of sector-shaped conductors Double V-clamps
EBH223TTW1 Top cable terminals, for connection of sector-shaped conductors Double V-clamps
EBH2 - Catalogue numbers
Description EBH2
Rated thermal current Ith 400 A
Rated voltage Un 690 V a.c.
Utilisation category AC-23B DC-21B DC-22B
Rated switching voltage Ue 690 V a.c. 440 V a.c. 220 V a.c.
Rated switching current Ie 400 A 400 A 400 A
Rated short circuit making current
690 V a.c. 80 kA
15 kA 20 kA
400 V a.c. 100 kA
Rated short circuit withstand current
690 V a.c. 80 kA
15 kA 20 kA
400 V a.c. 100 kA
Rated insulation voltage Ui 1000 V a.c.
Rated impulse withstand voltage Uimp 12 kV
Rated power dissipation 45 W
Rated frequency 50-60 Hz -
Mechanical durability (Number of cycles) 100
Electrical durability (Number of cycles) 200
IP degree of protection IP20
Compatible NH Fuse link body size 2
Accessories see page 52
38 EATON Bussmann series NH Gear catalogue
EBH
For stranded conductors using cable ferrules is recommended
*using of torque wrench is recommended
EBH2 - Terminal clamps details
EBH2 (top cable terminal: V-clamp)
EBH2 (bottom cable terminal: V-clamp) for installation on
busbar systems
EBH2 (top cable terminal: double V-clamp
EBH2 (bottom cable terminal: doubleV-clamp) for
installation on busbar systems
EBH2
for installation on mounting plate,
cable terminals: double V-clamps
EBH2
for installation on mounting plate,
cable terminals: V-clamps
EBH2*
(top cable terminal: M10 screws)
EBH2 -SD* (bottom cable terminal:
M10 screws) for installation on busbar
systems
EBH2 Horizontal fuse switch disconnector, size 2, 400 A, 690 V a.c.
Description Clamp Drawing of
clamps Cross-section of conductors Cu busbar Tightening
torque
Dimensions and spacing of
holes for installation of EBH 2 on
mounting plate
EBH 2
S-bridge
clamp
2 x M8
x 30
Cu/Al conductor
50÷185 mm2
Maximum
busbar width
35 mm
10 Nm*
M10 x 30
screw
conductor with lug terminal
up to 240 mm2 20 Nm*
V- clamp
35-300SW-B
V-clamp for direct fixing
of conductor with busbar end
with cross-section:
35 - 185 mm2
35 - 240 mm2
35 - 240 mm2 35- 300 mm2
30 Nm*
Double
V- clamp
HS2/
35-240-C
V-clamp for direct fixing of conductor with
busbar end with cross-section:
35 - 185 mm2
35 - 240 mm2
35 - 240 mm2 35 - 300 mm2
40 Nm*
13
9.5
R
14
130
ø
EATON Bussmann series NH Gear catalogue 39
EBH
EBH3 - Technical data
Installation on mounting plate Cable terminal
EBH3O3TS8 For connection of round conductors S-bridge clamps
EBH3O3TM2 For connection of conductors with lug terminals M12 screws
60 mm busbar system Cable terminal
EBH313TM2 For installation on 60 mm busbar system, top/bottom cable terminal M12 screws
EBH3 - Catalogue numbers
EBH3
for installation on mounting plate
EBH3 Horizontal fuse switch disconnector, size 3, 630 A, 690 V a.c.
Description EBH 3
Rated thermal current Ith=ln 630 A
Rated voltage Un 690 V a.c.
Utilisation category AC-22B DC-21B
Rated switching voltage Ue 690 V a.c. 250 V a.c.
Rated switching current Ie 630 A 630 A
Rated short circuit making current 25 kA
Rated short circuit withstand current 100 kA
Rated insulation voltage Ui 1000 V a.c.
Rated impulse withstand voltage Uimp 12 kV
Rated power dissipation 60 W
Rated frequency 50-60 Hz
Mechanical durability (Number of cycles) 1000
Electrical durability (Number of cycles) 200
IP degree of protection IP 20
Compatible NH Fuse link body size 3
Accessories see page 52
Version Clamp Drawing
of clamp
Cross-section
of conductors Cu busbar Tightening
torque
Dimensions and spacing of holes
for installation of EBH 3 on mounting plate
EBH 3
S-bridge
clamp
2 x M8 x 35
Cu/Al conductor
50 - 185 mm2
Maximum
busbar
width 35
mm
10 Nm*
M12 x 30
screw
conductor with
lug terminal up
to 240 mm2
20 Nm*
50
150
9.5
8.5
R
For stranded conductors using cable ferrules is recommended
*using of torque wrench is recommended
EBH3 - Terminal clamps details
40 EATON Bussmann series NH Gear catalogue
EBH
EBH00-X
with electronic fuse monitoring module
Horizontal fuse switch disconnector electronic fuse monitoring module*
Parameters
Operating voltage AC - 400 - 690 V, 40 - 60 Hz;
Relay parameters 5 A , 250 V~
CAUTION! Use only with fuse links with non-isolated
gripping lugs!
Catalogue number Description
EBH00O3TS5-TE For installation on mounting plate, power supply connected to top cable terminals
EBH00O3TS5-BE For installation on mounting plate, power supply connected to top bottom terminals
EBH0013TTS5-E For installation on 60 mm busbar system, top cable terminals
EBH0013TBS5-E For installation on 60 mm busbar system, bottom cable terminals
EBH1O3TS8-TE For installation on mounting plate, power supply connected to top cable terminals
EBH1O3TS8-BE For installation on mounting plate, power supply connected to top bottom terminals
EBH113TTS8-E For installation on 60 mm busbar system, top cable terminals
EBH113TBS8-E For installation on 60 mm busbar system, bottom cable terminals
EBH123TTS8-E For installation on 100 mm busbar system, top cable terminals
EBH123TBS8-E For installation on 100 mm busbar system, bottom cable terminals
EBH2O3TS8-TE For installation on mounting plate, power supply connected to top cable terminals
EBH2O3TS8-BE For installation on mounting plate, power supply connected to top bottom terminals
EBH213TTS8-E For installation on 60 mm busbar system, top cable terminals
EBH213TBS8-E For installation on 60 mm busbar system, bottom cable terminals
EBH223TTS8-E For installation on 100 mm busbar system, top cable terminals
EBH223TBS8-E For installation on 100 mm busbar system, bottom cable terminals
Electronic fuse monitoring module, cable terminal - S-bridge clamps installation details
L1, L2, L3 diodes are on - all three phases are supplied, all
fuse links are operational.
Relay contacts: [21..22] - closed; [13..14] - opened
L1, L2, L3 diodes are flashing - all three phases are
supplied, fuse links operated
Relay contacts: [21..22] - opened; [13..14] - closed
L1, L2, L3 diodes are off - two or more phases are not
supplied or fuse links are removed.
Relay contacts: [21..22] - opened; [13..14] - closed
5 A 250 V AC
Fuse switch disconnector Electronic fuse monitoring
module
LEDs
disconnector contact position during normal operation
* Available upon request. Please contact Eaton’s application engineering department for further details: buletechnical@eaton.com
EATON Bussmann series NH Gear catalogue 41
EBH
EBH000 Mounting plate installation, S-Bridge clamps and M Screws
EBH000 Mounting plate installation, S-Bridge clamps and M Screws with lengthened terminal shrouds
EBH Horizontal Fuse switch disconnector - Outline drawings (mm)
42 EATON Bussmann series NH Gear catalogue
EBH
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
EBH000 - 60 mm busbar system busbar installation
EBH00 Mounting plate installation
207
18,3
81
157
106,5*
42
212
106
33 33
182
7,5
2
45
2
sealing point
*122.5 mm for M screw terminal (for busbar and
lug terminal)
70°
112
70
242
215
60 58
191
60
min. 12 mm
max. 30 mm
89
25 25
busbar thickness 3-10 mm
EATON Bussmann series NH Gear catalogue 43
EBH
EBH00 Mounting plate installation with lengthened terminal shroud 198 184207
18,3
81
106,5*
106
33 33
7,5
42
212
45
*122.5 mm for M
screw terminal
(for busbar and
lug terminal)
sealing point
EBH003T Installation on 60 mm busbar 60 60
194
8 26 5
109,5
70
32
70°
214
7,5
106
33 33 241
sealing point
5-10
19,5
3
206
12-30
33,5
M8
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
44 EATON Bussmann series NH Gear catalogue
EBH
EBH1 Mounting plate installation S Bridge and M8 Screws 269
Ø7,5
57 57
180
292
243
240
176*
41
65 3
309
111
27 4
70°
*197 mm for M type clamp
EBH1 Mounting plate installation V-clamps 269
Ø7,5
57 57
180
292
243
240
41
65 3
309
111
4
70°
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
EATON Bussmann series NH Gear catalogue 45
EBH
130
319
70°
80
266
260
216
341
31
298
Ø7,5
208
65 65
EBH2 Mounting plate installation S-Bridge clamps and M Screws
sealing point
EBH1 60 mm and 100 mm busbar installation
A
Ø7,5
57 57
180
A
C
292
243
165
4
70°
70 339
140
94
B
Thickness of the busbar from 3 to 10 mm
M,S,V types of clamps
AB C
60 mm 66 mm max. 30 mm
100 mm 27 - 66 mm max. 60 mm
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
46 EATON Bussmann series NH Gear catalogue
EBH
130
321
EBH2 Mounting plate installation , V-clamps
Ø7,5
315
208
170
120
319
300
381
70°
EBH2 Mounting plate installation, double V-clamps
sealing point
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
Ø7.5
325
208
sealing point
EATON Bussmann series NH Gear catalogue 47
EBH
Ø7,5
208
298
65
154
70°
319
266
260
366
109
EBH2 Installation on 60 mm and 100 mm busbar, M Screws
70°
366
319
154
321
266
260
109
298
Ø7,5
208
65 65
EBH2 Installation on 60 mm and 100 mm busbar, V-clamps
65
busbar thickness 5-10 mm
busbar
thickness
5-10 mm
top cable terminal
bottom cable terminal
sealing point
sealing point
* cable terminal:
screw terminal M,
S-bridge clamp
AB C
60 mm 75 mm max. 30 mm
100 mm 35 - 67 mm max. 60 mm
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
48 EATON Bussmann series NH Gear catalogue
EBH
319
300
406
194
149
Ø7,5
208
315
65 65
EBH2 Installation on 60 mm and 100 mm busbar, double V-clamps
70°
AB C
60 mm 75 mm max. 30 mm
100 mm 35 - 67 mm max. 60 mm
top cable terminal
busbar bottom cable terminal
thickness
5-10 mm
sealing point
EBH3 Mounting plate installation, S bridge and M Screws
140
70°
337
212
31-33
48
86,5
371
250
80 80
308
154
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
EATON Bussmann series NH Gear catalogue 49
EBH
EBH3 60 mm busbar installation, M Screws
EBH3 60 mm busbar installation, M Screws
EBH 00 EBH 1 EBH 2
138
156
113
EBH with electronic modules width - mm
EBH Horizontal fuse switch disconnector - Outline drawings (mm)
50 EATON Bussmann series NH Gear catalogue