52 MINI VRF
High efficiency full DC inverter and twin rotary compressor
High efficiency DC fan motor Electrical control box refrigerant cooling technology
Strong Power, Stable Operation
Energy Saving And Environmental Friendly
TCL Mini VRF use full DC inverter twin rotary compressor, which has highefficiency both for full load condition and partial load condition, also leads to
low noise, stable and reliable operation.
The stepless regulation of the fan motor
can meet the actual requirement of the
capacity output, efficiency of motor is
increased up to be 45%, higher efficiency
in low speed operation.
The refrigerant cooling technology can cool the PCBs in high
ambient temperature condition, which improves the reliability,
effciency and lifespan of the MINI VRF units.
80° C
60° C
Temperature
drop
Wide operation temperation range
The Mini VRF can operate under -20℃ to ensure the heating demand, operate up to 54° C to make sure the cooling capcity output
with high effi ciency and stability.
MINI VRF
R410A High-efficiency and environmentally friendly refrigerant
RoHS Certification
R410A is an HFC refrigerant which does not damage the ozone layer. It is an
energy efficient and environmentally friendly refrigerant.
The TCL mini VRF unit meets the RoHS enviromental
certifi cation, which is environmental friendly.
R410A is non-toxic and is a \"non-flammable refrigerant\". The composition
structure of R410A is not easy to change and very stable.
7.1
7.2
53
Authoritative attestation
The TMV6+ series full inverter VRF units, through
the compressor core frequency conversion
technology upgrade, the overall optimization of
the refrigeration system and the control system,
makes the unit energy-saving performance even
better, and has passed the Eurovent and CE
standard certification.
7.3
Beautiful Appearance, Upgraded Structure Design
The top panel
Right front side plate
Grille
Right back plate
Footing
Seal plate
The front panel Lifting handle
No screw design to get high-quality structure
and improve the strength, more beautiful
Mold forming and integrated design
to make sure the strength of the panel
Grille adopts DOE simulation design, air
volume increased more than 7%
The mold is integrally formed and
the new designed diff user improves
the heat exchange effi ciency.
High strength foundation with rust - proof,
corrosion - proof, more stable and reliable. Ensure simple pipe connection.
Double 528mm wind wheel, larger air volume
and lower noise.
Upgraded handle design, easy to carry
Simple and elegant appearance
The front, side and back of the unit are
designed with knock-out holes, coper
pipes can be connected from various
directions, which is more convenient to
do the installation.
Sealing plate is combined with knock-out plate
Three side pipe connection design
Diff erent installation options
Three side direction pipe connection
7.4
54 Mini VRF Parameters
MINI VRF parameters
8-10kW 12-16kW
7.5
Items Unit
80 100 120 140 160
Model: TMV-Vd(**)W/N1-D(EU)
Power Supply V~,Hz,Ph 220-240V, 50Hz, 1N
Cooling
Capacity W 8,000 9,000 12,100 14,000 15,500
Input W 2,700 2,900 3,900 5,250 5,930
Current A 12.1 13 17.31 23.34 26.06
SEER W/W 5.4 5.4 7 6.9 6.8
ηs,c % / / 277 273 269
Heating
Capacity W 8,000 9,000 12,100 14,000 16,000
Input W 2,100 2,900 3,100 3,800 4,520
Current A 9.41 13 13.9 16.6 19.86
SCOP W/W 3.8 3.8 4.3 4.2 4.2
ηs,h % / / 169 165 165
Max. Input Consumption W 6,200 6,200 7,260 7,260 7,260
Max. Current A 28.2 28.2 33.0 33.0 33.0
Circuit Breaker A 40 40 40 40 40
Air Flow Volume m3
/h 4300 4300 5700 5700 5700
Sound Pressure Level dB(A) 54 55 56 56 57
Sound Power Level dB(A) 69/71 69/72 70/72 70/73 71/74
Dimension
(W×D×H)
Net mm 910×359×803 1010×410×850
Packing mm 1022×480×835 1145×535×970
Weight
Net kg 52 52 75 75 78
Gross kg 55 55 87 87 90
Cooling
Operating Range
Outdoor side °C -15~55
Indoor side °C 16~32
Heating
Operating Range
Outdoor side °C -20~24
Indoor side °C 15~31
1. Specifications are based on the following conditions:
2. Cooling: Indoor temperature 27°C DB/19°C WB,and outdoor temperature 35°C DB/24°C WB.
3. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB.
4. Equivalent piping length:5m; Level difference:0m; Voltage:230V.
5. Sound Level: Indoor unit sound pressure level,measured at a point 1.5m downward from the unit center.
6. Outdoor unit sound pressure level,measured at a point 1.0m in front of the unit.
7. Optional simple wired controller; Universal remote controller; auto-restart(optional); Timer:only one circle.
8. Due to ongoing product development, specifications are subject to change without notice.
Notes:
55
18-28 KW
Items Unit
180 224 252 280
Model: TMV-Vd(**)W/N1-D(EU)
Power Supply V~,Hz,Ph 380-415V, 50Hz, 3N
Cooling
Capacity W 18,000 22,400 25,200 28,000
Input W 6,900 9,220 8,600 11,280
Current A 10.75 14.2 13.23 16.62
SEER W/W 7 6.8 6.6 6.4
ηs,c % 277 269 261 253
Heating
Capacity W 18,000 22,400 25,200 28,000
Input W 4,900 6,220 7,030 8,070
Current A 7.63 9.34 10.9 12.46
SCOP W/W 4.4 4.2 4.3 4.3
ηs,h % 173 165 169 169
Max. Input Consumption W 11,000 11,000 12,000 12,000
Max. Current A 17.6 17.6 19.2 19.2
Circuit Breaker A 25 25 25 25
Air Flow Volume m3
/h 10500 10500 10500 10500
Sound Pressure Level dB(A) 59 59 61 61
Sound Power Level dB(A) 78/79 78/79 80/82 80/82
Dimension
(W×D×H)
Net mm 1120×400×1560
Packing mm 1250×560×1721
Weight
Net kg 130 130 140 140
Gross kg 145 145 163 163
Cooling
Operating Range
Outdoor side °C -15~55
Indoor side °C 16~32
Heating
Operating Range
Outdoor side °C -20~24
Indoor side °C 15~31
1. Specifications are based on the following conditions:
2. Cooling: Indoor temperature 27°C DB/19°C WB,and outdoor temperature 35°C DB/24°C WB.
3. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB.
4. Equivalent piping length:5m; Level difference:0m; Voltage:230V.
5. Sound Level: Indoor unit sound pressure level,measured at a point 1.5m downward from the unit center.
6. Outdoor unit sound pressure level,measured at a point 1.0m in front of the unit.
7. Optional simple wired controller; Universal remote controller; auto-restart(optional); Timer:only one circle.
8. Due to ongoing product development, specifications are subject to change without notice.
Notes:
56 VRF systems, Various combinations
In response to the different needs of building types for air-conditioning equipment, TCL provides four basic
outdoor unit modules, which can be freely combined in 2HP increments, and the maximum combination can reach
128HP, which can meet the high level design capacity differentiation, installation and transportation requirements of
large and medium-sized air-conditioning projects .
Recommended combination table
HP Combination Connected
indoor unit qty HP Combination1
(Space saving)
Connected indoor
unit qty.
8 8 13 66 22+22+22 80
10 10 16 68 22+22+24 80
12 12 19 70 22+24+24 80
14 14 23 72 24+24+24 80
16 16 26 74 22+24+28 80
18 18 29 76 24+24+28 80
20 20 33 78 22+28+28 80
22 22 36 80 24+28+28 80
24 24 39 82 26+28+28 80
26 26 43 84 28+28+28 80
28 28 46 86 26+28+32 80
30 30 50 88 28+28+32 80
32 32 53 90 26+32+32 80
34 16+18 56 92 28+32+32 80
36 18+18 59 94 30+32+32 80
38 16+22 63 96 32+32+32 80
40 18+22 66 98 24+24+24+26 80
42 20+22 69 100 24+24+26+26 80
44 22+22 72 102 24+26+26+26 80
46 22+24 75 104 24+26+26+28 80
48 24+24 78 106 26+26+26+28 80
50 22+28 80 108 26+26+28+28 80
52 24+28 80 110 26+28+28+28 80
54 26+28 80 112 28+28+28+28 80
56 28+28 80 114 26+28+28+32 80
58 26+32 80 116 28+28+28+32 80
60 28+32 80 118 26+28+32+32 80
62 30+32 80 120 28+28+32+32 80
64 32+32 80 122 26+32+32+32 80
124 28+32+32+32 80
126 30+32+32+32 80
128 32+32+32+32 80
MINI VRF parameters
57
IDU lineup
Series Type Fan
motor Model
Capacity range(x100w)
18 22 25 28 32 36 40 45 50 56 63 71 80 90 100 112 125 140 160 220 280 450 560
360° Q8
cassette
Cooling
&Heating DC TMV-V(**)
Q8/NIDY(E) ● ● ● ● ● ● ● ● ● ● ● ● ● ●
compact
cassette
Cooling
&Heating DC TMV-V(**)
Q4R/NIDY (E) ● ● ● ● ● ● ● ● ● ●
Slim duct
Cooling
&Heating DC TMV-V(**)
F5/N1DY(E) ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Free static
pressure duct
Cooling
&Heating DC TMV-V(**)
F2/N1DY(E) ● ● ● ● ● ● ● ● ● ● ●
Wall-mounted
(External EXV)
Cooling
&Heating DC TMV-V(**)G/
N1DY-B(E) ● ● ● ● ● ● ● ● ● ●
Wall-mounted
(Built-in EXV)
Cooling
&Heating
AC TMV-V(**)G/
N1Y-B(E) ● ● ● ● ● ● ● ●
Wall-mounted
(Built-in EXV)
Cooling
&Heating
AC
(60Hz)
TMV-V(**)G/
N1Y-B(E) ● ● ● ● ● ● ● ● ●
High static
pressure duct
Cooling
&Heating AC TMV-V(**)
F1/N1Y(E) ● ● ● ●
Fresh air
duct
Cooling
&Heating AC TMV-V(**)
F1/XFN1Y(E) ● ● ● ●
Celilling
& Floor
Cooling
&Heating AC TMV-V(**)
ZD/N1Y(E) ● ● ● ● ● ● ● ● ● ● ●
One-way
cassette
Cooling
&Heating AC TMV-V(**)
Q1/N1Y(E) ● ● ● ● ● ● ●
Two-way
cassette
Cooling
&Heating AC TMV-V(**)
Q2/N1Y€ ● ● ● ● ● ● ● ●
Free static
58 IDU lineup & parameters
360° Q8 cassette
Technical characteristics
New panel design
Large Air Outlet Volume
DC inverter fan motor technology
Ultra low noise
360° wide-angle air supply
50Pa Static Pressure Adjustment
Adopt the new design of \"porcelain white\" color,
beautiful and generous, so that the indoor machine
panel and the ceiling color more easily integrated, more
noble, surround type air supply panel, air supply more
comfortable.
Through the new DC inverter fan motor, achieve 2100m³/h
air outlet volume, and improve the air Exchange efficiency
by 30%
Adoption DC inverter motor
technology, to improve the
running efficiency by 15% and
reduce the operation
noise (min 31dB)
Using the advanced technology of
three-dimensional spiral blade design,
can reduce the air resistance, realize
the machine low noise operation,
\"quiet\" enjoy a comfortable life.
Comfortable air supply does not leave dead corner, every
corner can enjoy cool; Uniform air supply, reduce the
temperature difference, keep the indoor temperature
comfortable; Air supply is no longer directed single, keep
air circulation, air more fresh and healthy.
Build-in 4 gear static
pressure, 0~50Pa can
be adjusted,to achieve
the 4m long air outlet
distance
Recommended places
Office, restaurant, supermarket, shopping mall, lobby, etc
4
2100m3
/h
Clean sterilization, healthy life
Standard health filter screen, effectively remove large
particles in the air, optional silver ion purification module,
adsorption of formaldehyde and odor, eliminate germs.
7-level Fan Speed Volume
Thin fuselage, the installation
space required is small, the unit
can be easily installed in a fairly
narrow ceiling.
Standard condensate pump, easy to install
Equipped with advanced high-lift condensate
drainage pump, the maximum head up to 1200mm,
easy to install drainpipes.
Standard float switch, timely warning
Standard float switch, when the condensate pump
is faulty or the drainpipe is blocked, timely warning,
prevent the water tray inside the machine overflow.
4m
59
360° Q8 cassette
Specification
Items Unit 28 36 45 50 56 63 71 Indoor Model: TMV-V(**)Q8/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 10000 12000 15000 17000 19000 21000 24000
KW 2.8 3.6 4.5 5 5.6 6.3 7.1
Heating
Btu/h 11000 14000 17000 19000 21000 24000 27000
KW 3.2 4 5 5.6 6.3 7.1 8
Electric
Data
(T1)
Rated Cooling Power Input KW 0.02 0.025 0.035
Rated Heating Power Input KW 0.02 0.025 0.035
Rated Cooling Current A 0.09 0.11 0.16
Rated Heating Current A 0.09 0.11 0.16
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 800/750/700 900/800/700 1100/900/750
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 31/29/27 33/31/29 35/33/31
Net Dimension
(WxDxH) mm 840x840x245
Packing Dimension
(WxDxH) mm 920x920x270
Net Weight Kg 21.5 22
Gross Weight Kg 25 25.5
Panel
Net Dimension
(WxDxH) mm 950x950x50
Packing Dimension
(WxDxH) mm 1055x1055x90
Net weight Kg 6
Gross weight Kg 9
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Items Unit 80 90 100 112 125 140 160 Indoor Model: TMV-V(**)Q8/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 27000 30000 34000 38000 42000 48000 55000
KW 8 9 10 11.2 12.5 14 16
Heating
Btu/h 30000 34000 38000 42000 48000 55000 62000
KW 9 10 11.2 12.5 14 16 18
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.06 0.07 0.085 0.132
Rated Heating Power Input KW 0.04 0.06 0.07 0.085 0.132
Rated Cooling Current A 0.18 0.27 0.32 0.39 0.6
Rated Heating Current A 0.18 0.27 0.32 0.39 0.6
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 1300/1000/800 1500/1100/800 1600/1200/900 1800/1300/950 2100/1700/1200
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 38/35/33 39/36/33 40/37/34 43/38/35 47/42/37
Net Dimension
(WxDxH) mm 840x840x245 840x840x290
Packing Dimension
(WxDxH) mm 920x920x270 920x920x315
Net Weight Kg 22 22.5 25 27.5
Gross Weight Kg 25.5 26 28.5 31
Panel
Net Dimension
(WxDxH) mm 950×950×50
Packing Dimension
(WxDxH) mm 1055×1055×90
Net weight Kg 6
Gross weight Kg 9
Refrigerant
Pipe
Gas Side mm/in 15.88(5/8)
Liquid Side mm/in 9.52(3/8)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
60 IDU lineup & parameters
Compact cassette
Technical characteristics
Ultra low noise
Using the advanced technology of
three-dimensional spiral blade design,
can reduce the air resistance, realize
the machine low noise operation,
\"quiet\" enjoy a comfortable life.
Recommended places
Office, restaurant, supermarket, shopping mall, lobby, etc
DC inverter fan motor technology
Adoption DC inverter motor
technology, to improve the
running efficiency by 15% and
reduce the operation
noise (min 25dB)
Clean sterilization, healthy life
Standard health filter screen, effectively remove large
particles in the air, optional silver ion purification module,
adsorption of formaldehyde and odor, eliminate germs.
7-level Fan Speed Volume
Thin fuselage, the installation
space required is small, the unit
can be easily installed in a fairly
narrow ceiling.
Specification
Items Unit 18 22 25 28 32 36 40 45 50 56 Indoor Model:TMV-V(**)Q4R/N1D1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling Btu/h 6000 7500 9000 10000 11000 12000 14000 15000 17000 19000
KW 1.8 2.2 2.5 2.8 3.2 3.6 4 4.5 5 5.6
Heating Btu/h 7500 9000 10000 11000 12000 14000 15000 17000 19000 21000
KW 2.2 2.5 2.8 3.2 3.6 4 4.5 5 5.6 6.3
Electric
Data
(T1)
Rated Cooling
Power Input KW 0.014 0.016 0.022 0.044 0.05
Rated Heating
Power Input KW 0.014 0.016 0.022 0.044 0.05
Rated Cooling
Current A 0.06 0.07 0.1 0.2 0.23
Rated Heating
Current A 0.06 0.07 0.1 0.2 0.23
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 520/390/260 560/410/280 620/460/300 750/560/310 800/590/330
Indoor sound
pressure
(Hi/Mi/Lo)
dB(A) 30/28/25 31/29/25 35/30/26 43/32/26 45/34/27
Net Dimension
(WxDxH) mm 570x570x245
Packing Dimension
(WxDxH) mm 718x657x301
Net Weight Kg 14.5 15
Gross Weight Kg 17 17.5
Panel
Net Dimension
(WxDxH) mm 650x650x57
Packing Dimension
(WxDxH) mm 734x734x95
Net weight Kg 2.7
Gross weight Kg 4.25
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2)
Liquid Side mm/in 6.35 (1/4)
Operation Temperature Range °C 16~31
1. Specifications are based on the following conditions:
2. Cooling: Indoor temperature 27°C DB/19°C WB,and outdoor temperature 35°C DB/24°C WB.
3. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB.
4. Equivalent piping length:5m; Level difference:0m; Voltage:230V.
5. Sound Level: Indoor unit sound pressure level,measured at a point 1.5m downward from the unit center.
6. Outdoor unit sound pressure level,measured at a point 1.0m in front of the unit.
7. Optional simple wired controller; Universal remote controller; auto-restart(optional); Timer:only one circle.
8. Due to ongoing product development, specifications are subject to change without notice.
Note:
61
Recommended places
Office, conference room, hotel room, restaurant, living room, etc
Technical characteristics
Constant air volume
Fan motor automatically adjusts speed according to realtime wind resistance. To provide stable air volume to rooms.
Health filter (optional)
The duct can be equipped with silver ion and activated
carbon health filter.
Ultra-thin body design, fashion and beautiful
The minimum height of the body is only 200mm, saving space.
The drain pump can lift the condensing water up to 1200mm.
Standard float switch, timely warning
Standard float switch, when the condensate pump is faulty or
the drainpipe is blocked, timely warning, prevent the water tray
inside the machine overflow.
DC 7-speed wind speed Energy-saving silent operation
DC motor, 7-speed air volume, energy-saving and silent
operation. The lowest noise is 20 dB(A).
High ESP
ESP up to 80Pa supports longer air duct and fits with more
installation scenario.
Pa
MAX: 12M
Thin fuselage, the installation
space required is small, the unit
can be easily installed in a fairly
narrow ceiling.
7-level Fan Speed Volume
MAX: 12M
Slim duct
62 Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Specification
IDU lineup & parameters
Items Unit
18 22 25 28 32 36 40 45 50 56
Indoor Model: TMV-V(**)F5/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 6000 7500 9000 10000 11000 12000 14000 15000 17000 19000
KW 1.8 2.2 2.5 2.8 3.2 3.6 4 4.5 5 5.6
Heating
Btu/h 7500 9000 10000 11000 12000 14000 15000 17000 19000 21000
KW 2.2 2.5 2.8 3.2 3.6 4 4.5 5 5.6 6.3
Electric
Data
(T1)
Rated Cooling Power Input KW 0.02 0.03 0.05
Rated Heating Power Input KW 0.02 0.03 0.05
Rated Cooling Current A 0.09 0.14 0.23
Rated Heating Current A 0.09 0.14 0.23
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 500/380/200 550/380/200 850/580/310
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 30/26/20 31/26/22 34/29/24
External Static Pressure
(Rated) Pa 20
External Static Pressure
(Range) Pa 0~50
Net Dimension (WxDxH) mm 700×450×200 920×450×200
Packing Dimension (WxDxH) mm 900×555×250 1200×555×250
Net Weight Kg 15.5 18
Gross Weight Kg 18 21
Refrigerant
Pipe
Gas Side mm/in 9.52(3/8) 12.7(1/2)
Liquid Side mm/in 6.35(1/4)
Operation Temperature Range °C 16~31
Items Unit
63 71 80 90 100 112 125 140
Indoor Model: TMV-V(**)F5/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 21000 24000 27000 30000 34000 38000 42000 48000
KW 6.3 7.1 8 9 10 11.2 12.5 14
Heating
Btu/h 24000 27000 30000 34000 38000 42000 48000 55000
KW 7.1 8 9 10 11.2 12.5 14 16
Electric
Data
(T1)
Rated Cooling Power Input KW 0.054 0.18 0.25
Rated Heating Power Input KW 0.054 0.18 0.25
Rated Cooling Current A 0.25 0.9 1.2
Rated Heating Current A 0.25 0.9 1.2
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 1100/760/480 1800/1400/760 2000/1500/1000
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 37/31/27 43/37/33 44/41/37
External Static Pressure
(Rated) Pa 20 60
External Static Pressure
(Range) Pa 0~80 30~80
Net Dimension (WxDxH) mm 1100×450×200 1400×700×250
Packing Dimension (WxDxH) mm 1290×565×245 1632×827×298
Net Weight Kg 22.5 36 38
Gross Weight Kg 26 42 44
Refrigerant
Pipe
Gas Side mm/in 15.88(5/8)
Liquid Side mm/in 9.52(3/8)
Operation Temperature Range °C 16~31
Slim duct
63
Recommended places
Office, conference room, hotel room, restaurant, living room, etc
Technical characteristics
Constant air volume
Fan motor automatically adjusts speed according to realtime wind resistance. To provide stable air volume to rooms.
Ceiling & Floor installation
Support both ceiling concealed and floor concealed installation.
Slim Body 245mm
Duct are new designed body of 245mm thickness which is
convenient for concealed installation.
Items Unit
45 50 56 63 71 80 90 100 112 125 140
Indoor Model: TMV-V(**)F2/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 15,000 17,000 19,000 21,000 24,000 27,000 30,000 34,000 38,000 42,000 48,000
KW 4.5 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0
Heating
Btu/h 17,000 19,000 21,000 24,000 27,000 30,000 34,000 38,000 42,000 48,000 55,000
KW 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0
Electric
Data
(T1)
Rated Cooling Power Input KW 0.072 0.125 0.18 0.23
Rated Heating Power Input KW 0.072 0.125 0.18 0.23
Rated Cooling Current A 0.33 0.57 0.82 1.05
Rated Heating Current A 0.33 0.57 0.82 1.05
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 1000/650/480 1350/950/700 1900/1400/1000 2100/1400/1050
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 36/30/27 40/35/30 43/39/34 44/39/34
External Static Pressure
(Rated) Pa 40 50
External Static Pressure
(Range) Pa 0~160 0~200
Net Dimension (WxDxH) mm 920×700×245 1200×700×245
Packing Dimension (WxDxH) mm 1140×830×290 1420×830×290
Net Weight Kg 28 29 37 38
Gross Weight Kg 33 34 42 43
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Fresh Air
Take in outdoor fresh air, ensure that the indoor air is fresh
and circulated. Max fresh air volume 100m2
/h.
2 Air Return Ways
There are two air return ways to be chosen for installation:
bottom air return and rear air return.
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
High ESP
ESP up to 200Pa* supports longer air duct and fits with
more installation scenario.
Pa
Recommended places
Office, conference room, hotel room, restaurant, living room, etc
Free static pressure duct
Specification
64 IDU lineup & parameters
High static pressure Duct
Recommended places
Workshop, hotel, restaurant, shopping mall, ballroom,
bar and other large space places
Technical characteristics
Specification
Ultra-high static pressure design to meet various
space requirements
Maximum static pressure 300Pa, can be long distance
multi-point air supply, fully meet the air conditioning needs
of different Spaces.
Pa
Clean sterilization, healthy life
Built-in coarse filter, PP filter screen, optional silver ion
purification module, effectively remove large particles in
the air, absorb formaldehyde and odor, eliminate germs.
The indoor unit adopts a hoiden installation mode, which
can be equipped with appropriate air outlets to perfectly
combine the air conditioning.
Various forms of air outlets,matching with decoration
Remark:The above designs and specifications are subject to change of product improvement without prior notice. Items Unit
220 280 450 560
Indoor Model:TMV-V(**)F1/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 75000 96000 154000 191000
KW 22 28 45 56
Heating
Btu/h 85300 106000 171000 208000
KW 25 31 50 61
Electric
Data
(T1)
Rated Cooling Power Input KW 1.75 2.25
Rated Heating Power Input KW 1.75 2.25
Rated Cooling Current A 8.85 11.36
Rated Heating Current A 8.85 11.36
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 4500/3440/2910 7500/5730/4860
Indoor sound pressure (Hi/Mi/Lo) dB(A) 55/53/51 61/59/57
External Static Pressure (Rated) Pa 200
External Static Pressure (Range) Pa 100~300
Net Dimension (WxDxH) mm 1366×758×520 1770×758×700
Packing Dimension (WxDxH) mm 1620×975×740 2035×975×920
Net Weight Kg 120 220
Gross Weight Kg 145 245
Refrigerant
Pipe
Gas Side mm/in 22.2(7/8) 28.6(9/8)
Liquid Side mm/in 12.7(1/2)
Operation Temperature Range °C 16~31
Fresh Air
Take in outdoor fresh air, ensure that the indoor air is fresh
and circulated. Max fresh air volume 100m2
/h.
65
Fresh air duct
Recommended places
Cinemas, hotels, lobbies, dance halls, bars and other places
Technical characteristics
Specification
Healthy Fresh Air
Through the fresh air unit, the outdoor healthy air can be
introduced into the room to keep the indoor healthy.
Simplify air exhaust system
Simplified air supply and exhaust system, stable and
reliable.
Note: The sum of the capacity of the processing unit and the
indoorsshould be 50%~100% of the ODU capacity, and the
capacity of the fresh air units does not exceed 30%.
Ultra-high static pressure design
The maximum static pressure is 300pa, which can meet longdistance air supply and different space requirements.
Pa
Control Smart and Lower Cost
The fresh air unit can be controlled independently or connected
to the same outdoor unit system with the AC indoor unit,
reducing costs and installation space.
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Items Unit
140 280 450 560
Indoor Model: TMV-V(**)F1/XFN1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 48000 95500 153000 191000
KW 15.5 28 45 56
Heating
Btu/h 34000 68000 95500 133000
KW 10 20 28 39
Electric
Data
(T1)
Rated Cooling Power Input KW 0.42 1.1 1.55 2.25
Rated Heating Power Input KW 0.42 1.1 1.55 2.25
Rated Cooling Current A 2 5.3 7.4 10.8
Rated Heating Current A 2 5.3 7.4 10.8
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 2050 3000 4000 6000
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 45 53 56 60
External Static Pressure
(Rated) Pa 196 200 300
Net Dimension (WxDxH) mm 1200×590×380 1366×758×520 1770×758×700
Packing Dimension (WxDxH) mm 1410×695×435 1620×975×740 2035×975×920
Net Weight Kg 58 120 220
Gross Weight Kg 60 145 245
Refrigerant
Pipe
Gas Side mm/in 15.88(5/8) 25.4(1) 28.69(9/8)
Liquid Side mm/in 9.52(3/8) 12.7(1/2)
Operation Temperature Range °C 16~31
66 IDU lineup & parameters
Wall mounted
Recommended places
Living room, study, reference room, negotiation room and
other places
Technical characteristics
Ultra-thin body design, smart and beautiful
The minimum thickness of the unit is only 294mm, which
makes installation more convenient.
Easy maintenance
The horizontal baffle of the unit is easy to remove for
easy cleaning and maintenance.
Ultra-low silent operation
Adopt large-diameter blade, high-quality plasticencapsulated motor, and the noise is as low as 27dB(A).
Long-lasting filter design
The long-term filter design makes the air more heathy,
reduces the difficulty of maintenance.
Wide-angle air supply, more comfortable
The upper and lower wind guide vanes make the airflow
comfortable.
Remark:The above designs and specifications are subject to change of product improvement without prior notice. Specification (External EXV)
Items Unit
22 28 36 45 50 56 71 80 90 100
Indoor Model:TMV-V(**)G/N1DY-B(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 7500 10000 12000 15000 17000 19000 24000 27000 30000 34000
KW 2.2 2.8 3.6 4.5 5 5.6 7.1 8 9 10
Heating
Btu/h 9000 11000 14000 17000 19000 21000 27000 30000 34000 41000
KW 2.5 3.2 4 5 5.6 6.3 8 9 10 12
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.045 0.055 0.09
Rated Heating Power Input KW 0.04 0.045 0.055 0.09
Rated Cooling Current A 0.19 0.2 0.25 0.4
Rated Heating Current A 0.19 0.2 0.25 0.4
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 550/450/330 650/550/360 800/700/500 1500/1200/800
Indoor sound pressure
(S/M/Mute) dB(A) 37/29/22 39/31/27 45/38/34 47/41/36
Net Dimension (WxDxH) mm 910×206×294 1010×220×315 1186×258×360
Packing Dimension (WxDxH) mm 977×276×367 1094×300×386 1260×328×430
Net Weight Kg 9.5 12 16.5
Gross Weight Kg 12 14.5 21
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
67
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Items Unit
22 28 36 45 50 56 71 80
Indoor Model:TMV-V(**)G/N1Y-B(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 7500 10000 12000 15000 17000 19000 24000 27000
KW 2.2 2.8 3.6 4.5 5 5.6 7.1 8
Heating
Btu/h 9000 11000 14000 17000 19000 21000 27000 30000
KW 2.5 3.2 4 5 5.6 6.3 8 9
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.045 0.07
Rated Heating Power Input KW 0.04 0.045 0.07
Rated Cooling Current A 0.19 0.2 0.32
Rated Heating Current A 0.19 0.2 0.32
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 550/450/350 650/580/400 800/700/550
Indoor sound pressure
(S/M/Mute) dB(A) 38/30/27 42/38/29 44/38/35
Net Dimension (WxDxH) mm 910×206×294 1010×220×315
Packing Dimension (WxDxH) mm 977×276×367 1094×300×386
Net Weight Kg 10 13
Gross Weight Kg 12.5 16
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Wall mounted
Specification (60Hz Built-in EXV)
Items Unit
22 28 36 45 50 56 63 71 80
Indoor Model: TMV-V(**)G/N1Y-B(E)
IDU Power Supply V~,Hz,Ph 208-230V, 60Hz, 1Ph
Capacity
Cooling
Btu/h 7500 10000 12000 15000 17000 19000 21000 24000 27000
KW 2.2 2.8 3.6 4.5 5 5.6 6.3 7.1 8
Heating
Btu/h 9000 11000 14000 17000 19000 21000 24000 27000 30000
KW 2.5 3.2 4 5 5.6 6.3 7.1 8 9
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.045 0.07
Rated Heating Power Input KW 0.04 0.045 0.07
Rated Cooling Current A 0.19 0.2 0.32
Rated Heating Current A 0.19 0.2 0.32
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 550/450/350 650/580/400 800/700/550
Indoor sound pressure
(S/M/Mute) dB(A) 38/30/27 42/38/29 44/38/35
Net Dimension (WxDxH) mm 910×206×294 1010×220×315
Packing Dimension (WxDxH) mm 977×276×367 1094×300×386
Net Weight Kg 10 13
Gross Weight Kg 12.5 16
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Specification (50Hz Built-in EXV)
68 Ceiling & floor
Recommended places
Living room, study, reference room, negotiation
room and other places
Technical characteristics
Specification
Ultra-thin Design
Wide Range of Air Flow
Dual Direction of Drainage
Compact design which fits for various room styles.
Condensing water can be drained both from left and right side.
Detachable Plastic Blowers
Wire Control (optional)
Flexible Installation
Universal desig ned parts and assemblies applied,
which is easy for maintenance.
Wire control is available,especially for hotel rooms,
offices,etc.
Two ways of installation available, ceiling suspended
and floor standing.
The air supply angle is from 0 to 110°, making the indoor
temperature more uniform and more comfortable.
IDU lineup & parameters
Items Unit
45 50 56 63 71 80 90 100 112 125 140
Indoor Model: TMV-V(**)ZD/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 15000 17000 19000 21000 24000 27000 30000 34000 38000 42000 48000
KW 4.5 5 5.6 6.3 7.1 8 9 10 11.2 12.5 14
Heating
Btu/h 17000 19000 21000 24000 27000 30000 34000 38000 42000 48000 55000
KW 5 5.6 6.3 7.1 8 9 10 11.2 12.5 14 16
Electric
Data
(T1)
Rated Cooling Power Input KW 0.102 0.149 0.158 0.235
Rated Heating Power Input KW 0.102 0.149 0.158 0.235
Rated Cooling Current A 0.46 0.68 0.72 1.07
Rated Heating Current A 0.46 0.68 0.72 1.07
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 960/870/680 1200/1100/820 1600/1440/1280 2000/1910/1590
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 44/42/38 46/44/40 50/48/44 52/50/46
Net Dimension (WxDxH) mm 1055×675×235 1055×675×235 1275×675×235 1635×675×235
Packing Dimension (WxDxH) mm 1131×753×313 1351×753×313 1711×753×313
Net Weight Kg 24 25 29 38
Gross Weight Kg 27 28 35 46
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
69
Specification
One-way Cassette
Technical characteristics
Recommended places
Living room, dining room, office, lobby, etc
Slim body
Super slim body with 235mm thickness, less installation
area required, capable to match multiple decoration styles.
Three level fan speeds
High,Mid,Low three fan speed
options, can meet the needs of
different indoor condition.
Wide-angle air flow
Adopting new type of swing motor, which largely increases
the angle of air flow.
High-lift Drain Pump
The drain pump with a 700mm lifting head which is as standard,
simplifying installation of the drain pipes.
Suitable for corner installation, comfortable air flow
Well-designed shape, suitable for corner installation,
make sure the air flow and temperature distribution well.
High ceiling design
Reserves a super high fan speed for high ceiling installation,
unit can provide powerful cooling and heating under a more
than 3 meters floor height.
3M
Standard float switch, real-time monitor water level
Equipped with float switch, which will automatically monitor
the water level and send alarm when malfunction of drain
pump or stuck of drain pipe occurs.
L
M
H
Items Unit 18 22 28 36 45 50 56 Indoor Model: TMV-V(**)Q1/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 6000 7500 10000 12000 15000 17000 19000
KW 1.8 2.2 2.8 3.6 4.5 5 5.6
Heating
Btu/h 7500 9000 11000 14000 17000 19000 21000
KW 2.2 2.5 3.2 4 5 5.6 6.3
Electric
Data
(T1)
Rated Cooling Power Input KW 0.05 0.06 0.07
Rated Heating Power Input KW 0.05 0.06 0.07
Rated Cooling Current A 0.24 0.28 0.31
Rated Heating Current A 0.24 0.28 0.31
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 510/400/340 680/600/510 800/720/620
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 39/34/31 40/34/31 42/36/33
Net Dimension (WxDxH) mm 850×480×235
Packing Dimension (WxDxH) mm 1105×645×305
Net Weight Kg 23
Gross Weight Kg 28
Panel Net Dimension (WxDxH) mm 1055×580×30
Net weight Kg 3.84
Refrigerant
Pipe
Gas Side mm/in 9.52(3/8) 12.7(1/2)
Liquid Side mm/in 6.35(1/4)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
70 Specification
Recommended places
Sitting room, study, dining room, small meeting room, etc
Technical characteristics
Quiet design, quiet and comfortable
Centrifugal wind wheel, axial air inlet, through rotation to
form a certain wind pressure, small blade area, large number,
uniform air, noise greatly reduced, for you to create a quiet
and comfortable environment.
Ultra-thin body, lightweight design
Ultra-thin body (290mm), requires less installation space,
even in the narrow low ceiling, still can be easily installed,
more flexible collocation decoration style.
Three - speed adjustment
New winding motor, with scroll fan technology, wider air
volume regulation, quieter operation, unique intimate
wind gear design. High, medium and low three speed
adjustment, strong refrigeration and heating, to create a
quiet and comfortable temperature.
High ceiling design, direct air flow to the ground
High ceiling design, suitable for ceiling height up to 3m space. 3M
High-lift Drain Pump
A drain pump with a 700mm raise height is fitted as
standard, simplifying installation of the drain piping.
Standard float switch, water level monitor
Equipped with float switch, which will automatically send
alarm when malfunction of drain pump or stuck of drain
pipe occur.
Super wide Angle air supply
Panel swing motor system adopts high-precision stepper motor,
panel up and down risk control system is more intelligent, to
achieve ultra-wide Angle and large range of air supply.
IDU lineup & parameters
Items Unit 22 28 36 45 50 56 63 71 Indoor Model: TMV-V(**)Q2/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 7500 10000 12000 15000 17000 19000 21000 24000
KW 2.2 2.8 3.6 4.5 5 5.6 6.3 7.1
Heating
Btu/h 9000 11000 14000 17000 19000 21000 24000 27000
KW 2.5 3.2 4 5 5.6 6.3 7.1 8
Electric
Data
(T1)
Rated Cooling Power Input KW 0.064 0.07 0.11
Rated Heating Power Input KW 0.064 0.07 0.11
Rated Cooling Current A 0.27 0.31 0.49
Rated Heating Current A 0.27 0.31 0.49
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 580/460/380 680/660/520 850/660/520 1360/1180/970
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 42/35/32 43/38/35 44/38/35 46/39/36
Net Dimension(WxDxH) mm 1140×575×290
Packing Dimension (WxDxH) mm 1305×755×370
Net Weight Kg 32 33 34
Gross Weight Kg 38 39 40
Panel Net Dimension (WxDxH) mm 1240×680×30
Net weight Kg 5.56
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Two-way Cassette
71
71
71
72 Front Front
Front Front
More than
More than
More than
IDU
ODU
First diverging pipe
IDU IDU
Guide plate
>
> >
>
>
The space shown in the figure needs to be reserved
for the installation of the ODU, and the power
supply equipment should be installed separately.
When a system has more than two outdoor
units, it is necessary to install the units as the
followings:
The outdoor units are arranged in descending
order(for example, in the right picture, ODU
capacity A ≥ ODU capacity B ≥ ODU capacity C)
and the ODU A should install at the brance pipe.
If there are stacks around the outdoor unit, the height
should be less than 800mm from the top of the
outdoor unit. If it is less than the size,a mechanical
exhaust device must be installed.
To ensure the heat dissipation of the outdoor unit,
there should be no obstacles above the outdoor
unit. If it cannot be avoided, a deflector should be
installed.
Fluorine filing valve
Liquid-side stop valve
Gas-side stop valve
Oil balance stop valve(Used when modules
are connected in parallel)
(used to detect the pressure/add refrigerant
vacuumize at the time of maintenance)
Location of refrigerant pipes
Installation space for ODU
Arrangement sequence of ODU
Installation options
73
Dimension of ODU
Requirements for ODU installation
Model A B
TMV-VED+252(280/335)W/AS-D(E) 724 725
TMV-VED+400(450/504/560/615)W/AS-D(E) 1141 725
TMV-VED+680(730)W/AS-D(E) 1561 725
TMV-VED+785(850/900)W/AS-D(E) 1700 725
TMV-VED+680/730 W/AS-D(E)
TMV-VED+252(280/335)W/AS-D(E) TMV-VED+400(450)W/AS-D(E)
1780 17801780
1780
925
1760 1900
1340
845
845 845 845
TMV6-VED+785/850/900W/AS-D(E)
TMV-VED+504(560/615)W/AS-D(E)
A shock absorber or shock pad should be installed between the unit and the foundation.
The unit and the foundation should be released tightly, otherwise there will be a lot of noise and vibration.
The outdoor unit must be grounded reliably.
It is forbidden to open the valves of the liquid pipe, gas pipe and oil balance pipe of the unit before commission.
The installation should ensure that there is enough space for maintenance. 1780
1340
845
74 Design of refrigerant piping
Branch pipe specifications
Refrigerant pipe length and height
Admissible
value Pipes
Length of
supporting
pipe
Total length of Refrigerant pipes
(Total extended length) 1100m L1+(L2+L3+L4+L5+L6+L7+L8+L9+L10+L11
+L12)×2+a+b+c+d+e+f+g+h+i+j+k+l+m
Length of the farthest
supporting pipe(L)
True length 220m
L1+L7+L8+L9+L10+i
Equivalent length 240m
Length of the supporting pipe furthest from the
first branch pipe(L)* 120m L7+L8+L9+L10+i
Height
Height difference between
indoor and outdoor units (H)
ODU up 100m
ODU down 110m
Height between indoor units (h) 40m
Assembly Include parts Assembly Include parts
BY01 Branch pipe parts G01、L01 BY05 Branch pipe parts G04、L03
BY02 Branch pipe parts G02、L01 BY06 Branch pipe parts L01、L01
BY03 Branch pipe parts G02、L02 BY07 Branch pipe parts L01、L02
BY04 Branch pipe parts G03、L02 BY08 Branch pipe parts G05、G02
* Note: Refer to relevant technical documents or consult technical person
120m
100m
240m
40m
First branch pipe
Between IDU & ODU Height difference Between IDU & ODU Height difference
Equivalent pipe length farthest from
the first branch pipe
Equivalent length of farthest piping of IDU
Installation options
75
Branch pipe specifications
76 Piping classification
Piping classification
Pipe dimension of indoor unit(NO.:a,b,c,d,… m)
Allowable length and height difference of refrigerant piping
IDU main piping and branch pipe assembly(Number: L2,L3,L4...L12,A,B,C...L)
Name of supporting pipe Connection position of supporting pipe Assembly
Main pipe Pipe between the outdoor unit and the first branch L1
Main pipe of indoor unit Pipe behind the first indoor branch which do not connect
to indoor unit L2,L3,L4,... L12
Slave pipe of indoor unit Pipes between the branch and indoor unit a,b, c, d,... m
Indoor unit branch assembly Pipes to the master pipe and slave pipes A, B, C,D,E,F,G,H, I,J,K,L
Outdoor unit branch assembly Pipes to the outdoor unit and main pipe L,Mg
Outdoor unit connecting pipe Pipe between outdoor and outdoor branch 1,g2, g3, g4, G1, G2
Indoor Unit Model Gas side Liquid side
Capacity: 1800~2200W φ9.52(flared nut) φ6.35(flared nut)
Capacity: 2800~5600W φ12.7(flared nut) φ6.35(flared nut)
Capacity: 6300~14000W φ15.9(flared nut) φ9.52(flared nut)
Capacity of
downstream
Indoor unit
A(×100w)
Dimension of
Master pipe
(Gas/Liquid)
Applicable brance
pipe
(Gas/Liquid) A(×100w)
Dimension of master
pipe
(Gas/Liquid)
Applicable brance
pipe
(Gas/Liquid)
A < 63 φ12.7/φ6.35 BY06(L01/L01) 63 ≤ A < 168 φ15.9/φ9.52 BY07(L01/L02)
168 ≤ A < 224 φ19.1/φ9.5 BY07(L01/L02) 224 ≤ A < 330 φ22.2/φ12.7 BY01(G01/L01)
330 ≤ A < 470 φ25.4/φ12.7 BY01(G01/L01) 470 ≤ A < 710 φ28.6/φ15.9 BY03(G02/L02)
710 ≤ A < 1040 φ31.8/φ19.1 BY03(G02/L02) 1040 ≤ A < 1540 φ38.1/φ19.1 BY04(G03/L02)
1540 ≤ A < 1800 φ41.2/φ22.2 BY05(G04/L03) 1800 ≤ A < 2500 φ44.5/φ25.4 BY05(G04/L03)
2500 ≤ A φ54.0/φ28.6 BY08(G05/G02)
Installation options
77
Diameter of outer connecting pipe
ODU Main pipe and branch pipes
Remark:
1. Please select the main pipe diameter of the outdoor unitfollow the above table. If the main pipe is larger ,
choose the main pipe according to larger one.
2. If the system is more than 108HP,please consult technical personnel.
Model Gas Liquid
TMV6+
-Vd+252(280/335/400)W/AS-D(E) φ25.4(welding) φ12.7(welding)
TMV6+
-Vd+450(504/560/615/680)W/AS-D(E) φ28.6(welding) φ15.8(welding)
TMV6+
-Vd+730(785/850/900/)W/AS-D(E) φ31.8(welding) φ19.1(welding)
TMV6+
-Vd+950(1000)W/AS-D(E) φ34.9(welding) φ19.1(welding)
ODU stop valve port diameter(Number: g1,g2,g3,g4)
Capacity of Outdoor
Units(HP)
Dimensions of Master Pipe, when the equivalent
lengthof all supporting pipes is less than 90
meters
Dimensions of Master Pipe, when the equivalent lengthof all
supporting pipes is 90 meters at least
Gas/Liquid-side Indoor Branch Pipe
1(Gas/Liquid-side) Gas/Liquid-side Indoor Branch Pipe 1(Gas/Liquid-side)
8HP 19.1/9.52 Assembly BY01(G01/
L01) 22.2/12.7 Assembly BY01(G01/L01)
10HP 22.2/9.52 Assembly BY01(G01/
L01) 25.4/12.7 Assembly BY01(G01/L01)
12-14HP 25.4/12.7 Assembly BY01(G01/
L01) 28.6/15.9 Assembly BY03(G02/L02)
16HP 28.6/12.7 Assembly BY02(G02/
L01) 31.8/19.1 Assembly BY03(G02/L02)
18-22HP 28.6/15.9 Assembly BY03(G02/
L02) 31.8/19.1 Assembly BY03(G02/L02)
24-26HP 31.8/19.1 Assembly BY03(G02/
L02) 38.1/22.2 Assembly BY04(G03/L02)
28HP 34.9/19.1 Assembly BY04(G03/
L02) 38.1/22.2 Assembly BY04(G03/L02)
30-32HP 38.1/19.1 Assembly BY04(G03/
L02) 41.2/22.2 Assembly BY05(G04/L03)
34-48HP 38.1/19.1 Assembly BY04(G03/
L02) 41.2/22.2 Assembly BY05(G04/L03)
50-54HP 38.1/19.1 Assembly BY04(G03/
L02) 44.5/22.2 Assembly BY05(G04/L03)
56-66HP 41.2/22.2 Assembly BY05(G04/
L03) 44.5/22.2 Assembly BY05(G04/L03)
68-72HP 44.5/22.2 Assembly BY05(G04/
L03) 50.8/25.4 Assembly BY08(G05/G02)
74-84HP 50.8/22.2 Assembly BY05(G04/
L03) 50.8/25.4 Assembly BY08(G05/G02)
86-96HP 50.8/25.4 Assembly BY08(G05/
G02) 54.0/28.6 Assembly BY08(G05/G02)
98-108HP 54.0/28.6 Assembly BY08(G05/
G02) 63.0/28.6 Assembly BY08(G05/G02)
78 Remark :1.The wire diameter and continuous length in the table are applicable to a maximum distance of 20 meters. If the power wiring exceeds
20 meters and the voltage drop exceeds the range of 2%, please choose a wire diameter with a larger cross-sectional area.
2.The selection of the power cord is based on the ambient temperature of 40°C.
3.The wire current carrying capacity in the attached table is only for the user's reference. The actual interception capacity of the wire
varies depending on the type and length of the cable, the way of pipe penetration, and the actual laying environment, and the correction
factor is different.
Distribution transformer
Outdoor power
Ground1 Ground2 Ground3
Building
Lightning
arrester Ground wire
Junction box
Leakage protector
Manual switch
Electrical system and installation
Please design the dedicated power supply for IDU and ODU separately.
In order to reduce interference, it is recommended to use two-core shielded cables for the signal cables of the IDU and
ODU. Please do not use multi-core cables without shielding.
The power supply should be equipped with a leakage protector and a manual switch.
During installation, the communication line and the power line must not be intertwined, and must be routed separately,
and the minimum distance should be greater than 20CM, otherwise the communication of the unit may be abnormal.
Power wiring must be entrusted to professional electricians.
The power supply, leakage protector and manual switch of the IDU connected to the same ODU are required to be
universal. (Please use the same circuit for the IDU power supply of the same system. And it must be turned on and off at
the same time, otherwise it will seriously affect the service life of the system, and unpredictable situations may occur. )
Please integrate the IDU and ODU connection wiring system and refrigerant piping system into the same system.
Electrical wiring precautions
ODU power wiring
ODU power connection
()a
L1
L2
L3
N
PE
Outdoor unitofModel Power Supply Minimum Wire
Diameter Current (A)
Copper Core PVC
Insulated Wire BVV(mm2)
Copper Core XLPE
Insulated Wire YJV(mm2)
Manual Switch
Capacity (A)
Electric Leakage
Protector
Capacity:25200W)
380-415V 3N
~50Hz
20.03 4.05 2.55 25
No more than 100mA
0.1sec
Capacity:28000W) 22.03 4.05 2.55 25
Capacity:33500W) 24.33 6.05 4.05 32
Capacity:40000W) 28.8 6.05 4.05 32
Capacity:45000W) 32.6 10.05 6.05 40
Capacity:50400W) 42 16.05 10.05 50
Capacity:56000W) 46.2 16.05 10.05 63
Capacity:61500W) 52.6 16.05 10.05 63
Capacity:68000W) 55.8 16.05 10.05 63
Capacity:73000W) 58.95 16.05 10.05 63
Capacity:78500W) 61.29 25.03+16.02 16.05 80
Capacity:85000W) 69.9 25.03+16.02 16.05 80
Capacity:90000W) 73.1 25.03+16.02 16.05 80
Installation options
79
Signal lines must be shielded. Using other wires may cause signal interference and cause malfunction.
The shielding nets of all shielded wires are connected to each other and finally connected to the sheet metal ground at
one point.
It is forbidden to bundle signal wires, refrigerant pipes, power wires, etc. together. When the power line and the signal
line are laid in parallel, they should be kept at a distance of more than 300mm to prevent the signal source from
being disturbed.
Please use two-core shielded wire ( ≥ 0.75mm²) for the signal cable of indoor and outdoor units, without polarity.
The signal cable of indoor and outdoor units should be connected as far as possible from the end of the outdoor unit.
Signal lines cannot form a closed loop.
The signal line has no polarity, and there is no need to distinguish it when wiring.v
Remarks: The wiring diameter and continuous length in the table indicate that the voltage drop is within 2%. When the continuous wiring
length exceeds the value in the table, please follow the relevant regulations to select the wire diameter.
Remarks:
1. Please use the refrigerant piping system, the indoor unit-indoor unit room, and the indoor unit-outdoor unit connection signal line as the
same system.
2. All the internal units in the same system must be powered in a unified manner, and some internal units cannot be cut off, otherwise the
unit will fail.
3. When the power cable and the signal cable are parallel, please put the wires into their respective wire ducts, and leave a suitable distance
between the wires. (Distance between power cables: 300mm below 10A, 500mm below 50A)
4. When multiple outdoor units are connected in parallel, the main outdoor unit must be set. (Refer to the settings of the DIP switch)
IDU power wiring
Control system and installation
IDU and ODU signal line wiring
Power Leakage Protector Manual switch Junction box IDU
Model Power supply
Minimum wire diameter(mm²) Manual switch
Leakage
protector Dimensions
(Continuous Length)
Dimensions
(Continuous Length)
Ground
wire Capacity Fuse
All IDU
Model
90-140Q8
125-140F2
125-140F5
380V ~
3N50Hz 2.5
(30m)
4.0
(50m) φ1.6mm 30 15 20A、30mA
< 0.1sec
Other model 220V ~1N
50Hz
ODU(Host) ODU(Slave1) ODU(Slave2)ODU(Slave3)
Signal line between ODU
The last one needs to be shorted with a matching resistor at the RP position on the control board.
Signal line between IDU
China
V26.04.07
GD TCL INTELLIGENT HEATING & VENTILATING EQUIPMENT CO.,LTD.
Address: No.7 Yuanlin Road, Nantou, Zhongshan, Guangdong, PR China
Web: cac.tcl.com E-mail: hvac@tcl.com