1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
The support type current transformer LZJC-10 with epoxy resin insulation is designed for current.
Power measurement and relay protection in 50Hz or 60Hz and rated voltage 10KV power system.
L Z J C - 10
differential protection
enhancement type
casting resin insulated
current transformer
voltage grade,KV
Normal conditions of use
TAILI 43
Instrument transformer series
The current transformer of the type LZZBJ-10 is a fully enclosed product.lt is used for metering
electric energy and current , relay protection in the electric power system up to rated frequency 50Hz
or 60Hz and rated voltage 10KV. The transformers can be executed according to the standards IEC185
and GB1208-1997
L Z Z B J - 10
Rated voltage(KV)
With protective class
Cast-resin insulated
Seat type
Norma Current transformer
l conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Extention output
TAILI 44 Instrument transformer series
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
The voltage transformers of the types JDZ(X)(F)10-10(A,B)G are single phase, casting
resin insulated and full enclosed products. They are used for metering electric energy,
voltage control and relay protection in the electric non-usefrul-ground neutral system up to
rated frequency 50Hz or 60Hz and rated voltage 10KV.
J D Z (X) (F) 10 -10 (A,B) G
with residual voltage winding
casting resin insulated
single phase
current transformer
separation of measur-ing and monitoring winding
Normal conditions of use
JDZ(F)10-10 Voltage
transformer 10KV design sequence
voltage grade,KV
Structure code
All insulation
TAILI 45
Instrument transformer series
Principle diagram
Notice details
In using, the secondary winding can not be short-circuited or operating over-load
Type Type
Fastener Fastener
G Grounding Bolt
rounding Bolt
TAILI 46 Instrument transformer series
TAILI 47
Instrument transformer series
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
This type of voltage transformer is epoxy resin vacuum casting semi-enclosed single-phase
indoor structure, mainly suitable for rated frequency of 50Hz or 60Hz, rated voltage 10KV and
below. Power system for power metering, voltage measurement.
J D Z (J) -10
with residual voltage winding
casting resin insulated
single phase
current transformer
voltage grade,KV
Normal conditions of use
TAILI 48 Instrument transformer series Principle diagram
Notice details
In using, the secondary winding can not be short-circuited or operating over-load
JDZ-10 JDZ-10
JDZ-10 JDZ-10
TAILI 49
Instrument transformer series
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
JSZW3-10 type voltage transformer is applicable to AC power system with rated frequency of
50Hz or 60Hz and rated voltage of 10kV for power metering, voltage monitoring and relay
protection.
J S Z W 3 - 10
Five-leg type
casting resin insulated
three phase
voltage transformer
design sequence
Normal conditions of use
JSZW3-10 Three phase
combined voltage
transformer 10KV
voltage grade,KV
Type
Accuracy class and
rated output(VA) rated insulation
level(KV)
JSZW3-10
JSZW3-6
JSZW3-3
Rated voltage ratio(V)
12/42/75
7.2/32/60
3.6/25/40
50 30 60 50 300
0.2 0.6 1 6P
10000/ 3/100/ 3/100/3
6000/ 3/100/ 3/100/3
3000/ 3/100/ 3/100/3
The current transformers of types LZZB9-35 are casting resins and fully enclosed. lt is used for
metering electric energy ad current ,relay protection in the electrical system up to rated frequency
50Hz or 60Hz and rated voltage 35KV.
L Z Z B J 9 - 35
DesignNo
With protective class
Casting insulatiom
Post type
Norma Current transformer
l conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Extention output
Rated voltage(KV)
Type
Rated secondary output (VA)
Raed dynamic
current(KA)
LZZBJ9-35
Rated primary
current
500lin
1s thermal
current(KA)
Accuracy class
combination
0.2 0.5 5P20
20-100
150-200
300-500
600-1250
1500-2000
2500
0.2/0.2
0.2/0.5
0.5/0.5
0.2/5P20
0.5/5P20
10 15 15
15 30 20
20 40 30
20 40 20
200lin
31.5
31.5/2
31.5/4
40/4 40/4125
80
TAILI 50 Instrument transformer series
TAILI 51
Instrument transformer series
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
The current transformers of types LZZB7-35 are casting resins and fully enclosed. lt is used for
metering electric energy ad current ,relay protection in the electrical system up to rated
frequency 50Hz or 60Hz and rated voltage 35KV.
L Z Z B 7 - 35
with protection
casting resin insulated
post phase
current transformer
design sequence
Normal conditions of use
voltage grade,KV
TAILI 52 Instrument transformer series LZZBJ4-35 type current transformer is applicable to the rated frequency 50Hz, rated voltage 35KV
power system outdoor device ZW7-40.5 type vacuum circuit breaker for electrical measurement and
protection.
L Z Z B J 4 - 35
DesignNo
With protective class
Casting insulatiom
Post type
Current transformer
Normal conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily
average temperature not more than 30℃
4.Altitude:≤1000m;
Extention output
Rated voltage(KV)
Single transformation ratio
LZZBJ4-358
LZZBJ4-358
TAILI 53
Instrument transformer series
LZZBJ9-24/220b/2 series current transformers are used in power systems with rated frequency of
50HZ or 60HZ and rated voltage of 10KV for power metering, current measurement and relay
protection and relay protection.
L Z Z B J 9 - 24 / 220b / 2
DesignNo
With protective class
Casting insulatiom
Post type
Current transformer
Reinforced type
Rated voltage(KV)
Nominal width
Sructure code
Normal conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily
average temperature not more than 30℃
4.Altitude:≤1000m;
TAILI 54 Instrument transformer series
TAILI 55
Instrument transformer series
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
The series of voltage transformers of the type JDZ(X)(F)9-35Q are full enclosed and casting resin
insulated products. They are used for metering electric energy; voltage control and relay
protection in the electric system up to rated frequency 50Hz or 60Hz and rated voltage 35KV.
J D Z (X) F 9 - 35 (G)
with residual voltage winding
casting resin insulated
single phase
current transformer
design sequence
Normal conditions of use
separation of measuring and monitoring winding
JDZ(F)9-35 Voltage
transformer 35KV
voltage grade,KV
All insulation
Principle diagram
Accuracy class
combinalion
Nameplate
The series of voltage transformers of the type JDZXF9-35 are full enclosed andcastingresin insulated
products. They are used for metering electric energy; voltage controland relay protection in the
electric system up to rated frequency 50Hz or 60Hz and ratedvoltage35KV.
J D Z X F 9 - 35
design sequence
with residual voltage winding
with residual voltage winding
single phase
Norma Current transformer
l conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
separation of measuring and monitoring winding
voltage grade kV
JDZX(F)9-35 Voltage
transformer 35KV
Nameplate
M8 Earthing bolts
TAILI 56 Instrument transformer series
Principle diagram
JDZX (F) 11-20 type voltage transformer is suitable for AC power system with rated frequency of
50H or 60Hz and rated voltage of 20KV for power metering, voltage monitoring and relay
protection.
J D Z X (F) 11 - 20
with residual voltage winding
casting resin insulated
single phase
current transformer
Normal conditions of use
JDZX(F)11-20 Voltage separation of measuring and monitoring winding
transformer 20KV
design sequence
voltage grade,KV
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
TAILI 57
Instrument transformer series
TAILI 58 Isolating switch series
TAILI 59
Isolating switch series
Rated short time withstand current (KA)
Rated current (A)
Rated voltage (KV)
Design serial number
outdoors
Isolating switch
G W 4- 40.5/ □-□
Normal conditions of use
GW4 series Outdoor High Voltage disconnectors are 3 phase AC 50Hz or 60Hz high voltage switch
gears. They are used in no-load condition to switch off the electric circuit and isolate electrical
equipment, such as high voltage bus, circuit breaker etc, and high voltage line up to 252KV power
system. The disconnecting switch can be divided into: No grounding, Single grounding and Double
Grounding, and mechanical interlock is set between the main blade and earthing switch. This product
is double pole structure, mainly consisting of frame, porcelains and conductive parts. Two porcelain
poles of each phase are mounted respectively on bearing holders of both ends of the frame, and
connected by cross links for horizontal rotation. Each of the conductive blade is divided into two parts
fixed on the two supporting porcelains, and the contact part is right in the middle. It has pollution- proof
type and plateau type.
- Ambient temperature: max +45°C min -45°C
- Altitude: <3000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Air contamination degree: IV degree
- Earthquake intensity: 8 degree
- No corrosive or flammable gas
TAILI 60 Isolating switch series Mounting holes
TAILI 61
Isolating switch series
Rated short time withstand current (kA)
Rated current (A)
Rated voltage (kV)
Design serial number
outdoors
Isolating switch
G W 5- 40.5/ □-□
Normal conditions of use
GW5 series Outdoor High Voltage disconnectors consists of three single phase, V type for each phase,
symmetrical angle is 50’, disconnect switch is made of pedestal, post insulator and electric part, They
are used in no-load condition to switch off the electric circuit and isolate electrical equipment, such as
high voltage bus, circuit breaker etc, and high voltage line up to 252kV power system.GW5-40.5/72.5/
126/252 outdoor high voltage disconnecting switch is used to make or break high voltage circuit in
rated voltage 40.5kV, 72.5kV,126, 252kV, AC 50/60Hz electric system. lt can open and close small
capacitance and inductive current. This disconnecting switch accords with standards: EC62271-103
High voltage switches. GB1985: AC High voltage disconnect switch and earthing switch and lEC 60694
& GB/T11022: Common technical requirements of HV switch gear and control equipment.
- Ambient temperature: max +45°C min -45°C
- Altitude: <1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Air contamination degree: IV degree
- Earthquake intensity: ≤8 degree
- No corrosive or flammable gas, no frequent violent vibration
TAILI 62 Isolating switch series base portion
(Double grounding type)
TAILI 63
Isolating switch series
Rated short time withstand current (KA)
Rated current (A)
Rated voltage (KV)
Design serial number
outdoors
Isolating switch
G W 8- 40.5/ □-□
Normal conditions of use
GW8(GW13)-40.5/72.5/126 series neutral point high voltage disconnecting switch is an outdoor
isolator of GW8-40.5, used for making and breaking transformer neutral point under no load condition.
The switch can be used CJ2 Type motor-driven operation mechanism or CS14G Type manual operation
mechanism. It consists of a single pole and operation mechanism. The single pole includes foundation,
support insulator, conducting arm and contact, etc. The operation mechanism realizes switching on or
off of disconnecting switch through connecting rod driving conducting arm. The product conforms to
IEC129, IEC694,GB1985-89.
- Ambient temperature: max +45°C min -45°C
- Altitude: ≤1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Air contamination degree: Ⅲ degree
- Earthquake intensity: ≤8 degree
- No corrosive or flammable gas, no frequent violent vibration
TAILI 64 Isolating switch series Mounting holes
Neutral Point
Mounting holes
Type disconnect switch
Mounting holes
TAILI 65
Isolating switch series
Rated short time withstand current (kA)
Rated current (A)
Rated voltage (kV)
Design serial number
outdoors
Isolating switch
G W 9- 12/ □-□
Normal conditions of use
- Ambient temperature: max +45°C min -45°C
- Altitude: ≤1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Air contamination degree: Ⅲ degree
- Earthquake intensity: ≤8 degree
- No corrosive or flammable gas, no frequent violent vibration
GW9-12(W) series outdoor high voltage disconnecting switch is used for AC 50Hz or 60Hz, rated voltage
up to10KV, 15KV, 24KV, making and breaking electric circuit under no load condition. The switch
consists of base, post insulator conducting parts, insurance hook and etc. Each phase has a
knife switch, and insulation hook rod can be used to open and close divide-shut brake. The knife switch
itself has a self-locking unit. The product conforms to IEC129, IEC694,GB1985-89.
Mounting hole size
Dimension
Series F Series igures
Figures
Rated thermal stability current (KA)
Rated current (A)
Through wall
styleRated voltage (KV)
Design serial number
indoor
G N 19 12/(C) □-□
Normal conditions of use
GN19-12 indoor HV disconnect switch applies t o power system of rated voltage below 12KV,
AC 50/60Hz. It is equipped with CS6-1 manual-operating mechanism and is used to break and
make circuit under no-load. There are additional pollution type, high-altitude type and power
indicating type.
- Ambient temperature: max. +45°C min. -45°C
- Altitude: ≤1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Relative humidity: daily average ≤95%, monthly average ≤90%
- Earthquake intensity: ≤8 degree
- No corrosive, explosive or flammable gas ,no voilent vibration
TAILI 66 Isolating switch series
TAILI 67
Isolating switch series
Rated short time withstand currer
Rated current
With grounding device
Rated voltage
Design serial number
Indoor type
Lsolating switch
G N 30 - 12(D) □-□
Normal conditions of use
- Ambient temperature: max. +45°C min. -45°C
- Altitude: ≤1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Relative humidity: daily average ≤95%, monthly average ≤90%
- Earthquake intensity: ≤8 degree
- No corrosive, explosive or flammable gas ,no violent vibration
GN30-12(D) series Indoor HV disconnecting switches is a new type of touch rotating knife isolator ,
which special designed for XGN2-12 HV switch gear, with rated voltage 12KV and three phase AC
50Hz or 60Hz indoor device. It’s mainly used for making and breaking circuit under with voltage and
no load.Its main structure in three-phase chassis of the upper and lower two plane, fixed two set of
insulator and contact, by rotating contactor, so as to realize switching on & off.
TAILI 68 Isolating switch series Interphase distance
Rated short time withstand current (KA)
Rated voltage (KV)
Design serial number
Indoor
Grounding switch
J N 15-12/31.5 - □
Normal conditions of use
1.Altitude: ≤1000m
2.Ambient temperature: -45°C ~+45°C
3.Earthquake intensity: ≤8 degree
4.Pollution level: II
5.Relative humidity: Daily averages95%,Monthly average≤90%
JN15-12/31.5 is suitable for use in 12Kv and below AC 50Hz or 60Hz power system, and
can be used with various types of high-voltage switchgear, and can also be used for
grounding protection when overhauling high-voltage electrical equipment. This type of
switch can be used together with the charged display device.
Product Model unit Data
KV
KA
S
KA
KA
12
31.5
4
80
80
Rated voltage
Rated short-time withstand current
Rated short-circuit duration
Rated short-circuit making current
Rated peak withstand current
KV
time
Rated
insulation level
PF withstand
voltage(1 min)
Lightning impulse
withstand voltage
Phase to earth
Phase to phase
42
75
2000
TAILI 69
Isolating switch series
TAILI 70 Isolating switch series Interphase distance
Rated short time withstand current
Rated voltage (KV)
Design serial number
Indoor devices
Grounding switch
J N 17-12/40 - □
Normal conditions of use
1.Altitude: ≤1000m
2.Ambient temperature: -45°C ~+45°C
3.Earthquake intensity: ≤8 degree
4.Pollution level: II5.Relative humidity: Daily averages95%, Monthly average≤90%
JN17-12/40 indoor AC high voltage grounding switch is an advanced level product with high-tech
parameters performance. After comprehensive evaluation, it conforms to GB1985 and IEC129,
applies to power system of 3-12kV and three-phase AC 50( 60)Hz. It owns short-circuit making
capacity to protect other electric equipment not being damaged. Can be used with various high
voltage switchgear, also play a protective role in the high-voltage electrical equipment overhaul.
Product Model unit Data
KV
KA
S
KA
KA
12
40
4
100
100
Rated voltage
Rated short-time withstand current
Rated short-circuit duration
Rated short-circuit making current
Rated peak withstand current
KV
time
Rated
insulation level
PF withstand
voltage(1 min)
Lightning impulse
withstand voltage
Phase to earth
Phase to phase
42
75
2000
TAILI 71
Isolating switch series
1.Altitude: ≤1000m
2.Ambient temperature: -45°C ~+45°C
3.Earthquake intensity: ≤8 degree
4.Relative humidity: Daily averages95%,Monthly average≤90%
Interphase distance
Rated short time withstand current (KA)
Rated voltage (KV)
Design serial number
Indoor
Grounding switch
J N 22-40.5/31.5 - □
Normal conditions of use
JN22-40.5/31.5 indoor AC high voltage earthing switch is an advanced level product with high-tech
parameters performance. After comprehensive evaluation, it conforms to GB1985 AC HV disconnect
switch and earthing switch, applies to power system of 40.5KV and AC 50Hz or 60Hz. Can be used with
KYN61 -40.5 and other types high voltage switchgear, also play a protective role in the high-voltage
electrical equipment overhaul.