TAILI ELECTRIC CO.,LTD.
Best service of the
power transmission system
www.talpw.com
More than 30 years experience in design and manufacture HV and MV electric
products in relation to invironmental , safety, energy efficiency! We take 100%
responsible for our products quality and improve ourselves during close and
sincerely cooperation with our customers!
Enterprise profile
Total Solution is how we define “TAILI”. From design & customization,
engineering, manufacturing installation, and after sale service. TAILI
provides a Total Solution to our customers helping and supporting to give
them a competitive advantage in their market.
TAILI founded in 1992,is one of the largest and most respected
manufactures of MV power distribution products in WENZHOU of China, the
“Electric Industry Center” of China.We have factories for manufacturing,
research &development, and distribution of products: Transformers,
Outdoor switch, MV-LV Metal switchgears Power substations, Components
and Accessories for transformer and Switchgears.From design &
customization, engineering, manufacturing installation, and after sale
service ,we aim to at to provide the highest quality products at the most
reasonable price. And by doing so, to provide and unmatched customer
experience and actively to establish long-term cooperative relationship with
our new and old customers.
PRODUCT
APPLICATIONS
CONTENTS
High voltage load switch series
ZN63A(VS1)-12 Indoor high voltage vacuum circuit breaker
ZN63A(VS1)-12C Indoor high voltage vacuum circuit breaker side mounted
ZN85-40.5 Indoor high voltage vacuum circuit breaker(modular)
ZW32-40.5F(M) Outdoor high voltage intelligent (permanent magnet) vacuum circuit breaker
ZW7-40.5F(M) Outdoor high voltage intelligent (permanent magnet) vacuum circuit breaker
ZW20-12F Outdoor high voltage intelligent column demarcation vacuum circuit breaker
FZW28-12F Outdoor demarcation vacuum load switch
ZW32-12F Outdoor high voltage intelligent demarcation vacuum circuit breaker
FZN21-12RD Indoor isolation vacuum load switch
FKN12-12/FKRN12-12 Indoor high voltage gas insulated load switch
FZN25-12/FZRN25-12 Indoor high voltage vacuum load switch
FLN36-12 SF6 Insulated high voltage load break switch
FLN36-24 SF6 Insulated high voltage load break switch
FLN48-12 SF6 Insulated high voltage load break switch
Instrument transformer series
JDZX11-35R Single phase voltage transformer with fuse
JDZX11-20R Single phase voltage transformer with fuse
JSZV12-10R Three phase combined voltage transformer with fuse
JSZV1(2、3)-10R Three phase combined voltage transformer with fuse
LMZC(1、2、3)-10 Bushing current transformers
LSY107-10 Three phase combined bushing current transformer
LXKΦ80-Φ240 Zero sequence current transformer
LZZBJ9-10 Current transformer 10KV
LZJC-10 Current transformer 10KV
LZZBJ-10 Current transformer 10KV
JDZ(F)10-10 Voltage transformer 10KV
JDZ(J)-10 Voltage transformer 10KV
JSZW3-10 Three phase combined voltage transformer 10KV
LZZBJ9-35 Current transformer 35KV
LZZB7-35 Current transformer 35KV
LZZBJ4-35/35 Current transformer 35KV
LZZBJ9-24/220b/2 Current transformer 24KV
JDZ(F)9-35 Voltage transformer 35KV
JDZX(F)9-35 Voltage transformer 35KV
JDZX(F)11-20 Voltage transformer 20KV
High voltage vacuum circuit breaker series
02-03
04-05
06-07
08-09
10-11
12-13
14-15
16-17
19-20
21-22
23-24
25-26
27
28-29
31-32
33
34
35
36-37
38
39-40
41-42
43
44
45-46
47-48
49
50
51
52-53
54
55
56
57
Isolating switch series
GW4 Outdoor isolating switch
GW5 Outdoor isolating switch
GW8 Outdoor isolating switch
GW9 Outdoor isolating switch
GN19-12 Indoor isolating switch
GN30-12 Indoor isolating switch
JN15-12 Isolation earthing switch
JN17-12 Isolation earthing switch
JN22-40.5 Isolation earthing switch
59-60
61-62
63-64
65
66
67
68-69
70
71
High voltage vacuum circuit breaker series
TAILI 01
TAILI 05 High voltage vacuum circuit breaker series TAILI 02 High voltage vacuum circuit breaker series project
Rated voltage
Rated insulation
level
Rated short-circuit breaking current
Rated current
Rated thermally stable current (RMS)
Rated dynamic stabilization current (peak)
Rated short-circuit closing current (peak)
Rated number ofshort circuit breaking current breaks
Secondary circuit power frequency withstand voltage (lmin)s
Rated sequence of operations
Rated thermal settling time
Rated single/back-to-back capacitor bank breaking current
Mechanicallife
Rated lightning impulse withstand voltage peak
Imin power frequency withstand voltage
unit
KV
KV
KA
A
KA
times
V
S
A
times
parameter
12
75
31.5
42
20/25 40
630、1250、1600、
2000、2500、3150
630、1250
1250、1600、2000
2500、3150
31.5 40
63 80 100
50
2000
0-0.3-C0-180s-CO
0-180s-CO-180s-cO
4
630/400 800/400(40kA)
10000
20/25
63 80 100
Main technical parameters
Normal conditions of use
Model meaning
overview
Ambient temperature: not higher than +45 ℃ , not less than -45 ℃ (storage and transportation
at-30 ℃ is not allowed);
Altitude: not more than 1000m;
Relative humidity: daily average is not more than 95%, monthly average is not more than 90%,
saturated vapor pressure average is not more than 2.2 X10-3MPa;
The monthly average is not more than 1.8x 10-3MPa;
Seismic intensity: not more than 8 degrees;
No fire, explosion, serious pollution, chemical corrosion and severe vibration of the place.
ZN63A(VS1)-12 indoor high voltage vacuum circuit breaker, is a three-phase AC 50Hz or 60Hz rated
voltage of 12KV power system indoor switchgear, as a power grid equipment, industrial and mining
enterprise power equipment protection and control unit. lt is suitable for places that require frequent
The circuit breaker adopts the integrated design of the operating mechanism and the circuit breaker
body, which can be used as a fixed installation unit, or it can be equipped with a special propulsion
mechanism to form the function of the handcart unit.
(1) High voltage vacuum circuit breaker
(2) Indoors
(3) Product design serial number
(4) Rated voltage(KV)
(5) Rated current (A)
(6) Rated short-circuit breaking current (KA)
ZN63A(VS1)-12 Indoor
high voltage vacuum circuit breaker
operation under rated operating current, or multi-switchshort-circuitcurrent.
TAILI 06
High voltage vacuum circuit breaker series
TAILI 03
High voltage vacuum circuit breaker series
Appearance and installation size(mm)
TAILI 05 High voltage vacuum circuit breaker series TAILI 04 High voltage vacuum circuit breaker series Normal conditions of use
Model meaning
overview
Main technical parameters
ZN63A (VS1)-12C side-mounted vacuum circuit breaker is an indoor high-voltage switchgear, suitable
for rated voltage area 12 KV, frequency 50Hz or 60Hz three-phase power system, as a protection and
controel ectrical appliances, due to the special superiority of vacuum circuit breaker, especially suitable
for frequent operation under rated current, or multiple short circuit current cut.
ZN63A(VS1)-12C side-mounted vacuum circuit breaker adopts fixed installation, mainly used for fixed
switchgear, the circuit breaker can be used alone, but also can be used for ring network power supply,
box type transformation or various non-standard power supply systems.
(1) High voltage vacuum circuit breaker
(2)Indoors
(3) Product design serial number
(4) Rated voltage(KV)
(5)Side-mounted type
(6) Rated current (A)
(7) Rated short-circuit breaking current (KA)
Ambient temperature: not higher than +45℃,not lower than -45℃;
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%.
The altitude does not exceed 1000 meters;
The intensity of the earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements they can be put forward when ordering,
and our company will givethe greatest satisfaction.
ZN85-40.5 Indoor high voltage
vacuum circuit breaker(modular)
unit
KV
A
project parameter
Rated voltage
Rated current
Rated short-circuit closing current
Maximum operating voltage
Rated short-circuit breaking current
Rated peak withstand current
4S rated short-circuit withstand current
Rated insulation
level
Rated sequence of operations
Power frequency withstand voltage (before and after rated breaking)
Impact withstand voltage (before and after rated breaking)
KA
KA
KA
KA
KV
42(Break 48)
75(break 85)
0-0.3s-C0-180s-CO
12
12
630 1250
20
50
50
20
1600
31.5
80
80
31.5
25
63
25
63
KV
Appearance and installation size(mm)
Main technical parameters
unit
times
times
V
project parameter
Mechanical life
Operating mechanism rated closing voltage (DC)
Contact spacing
Rated numberof short circuit breaking current breaks
Operating mechanism rated opening voltage (DC)
Overtravel (contact spring compression length)
Three-phase division, closing bounce time
V
mm
mm
ms
10000
50
110,220
110,220
11±1
≤2
3.5±0.5
Contact closure bounce time
Average opening speed
Opening time
m/s
m/s
S
0.9±1.2
≤0.05
0.4±0.8
S
ms ≤2
0.1
≤0.08
Closing time
The main loop resistance of each phase
At the highest operating voltage
At the lowest operating voltage
60 50
Average opening speed
μΩ
TAILI 06
High voltage vacuum circuit breaker series
TAILI 05
High voltage vacuum circuit breaker series
Model meaning
overview
Main technical parameters
ZN85-40.5 indoor high voltage vacuum circuit breaker is suitable for three-phase AC 50Hz or 60Hz, 40.5KV
system, which can be used by industrial and mining enterprises, power plants and substations as divided
load current, overload current fault current, and suitable for frequent operation occasions. This circuit
breaker adopts an upper and lower arrangement structure to effectively reduce the depth of the circuit
breaker. And the use of composite insulation structure, three-phase arc extinguishing chamber and
connected charged body by three independent epoxy resin insulating shell isolation, after the use of
composite insulation structure, circuit breaker to meet the normal operating conditions of air distance
and climbing distance requirements, and effectively reduce the volume of circuit breaker, the leading
electric circuit vacuum arc extinguishing chamber and dvnamic and static conductive connection
installed in the insulating cylinder, so that the phase between the phase is only 300mm. The main circuit
electrical connections are all fixed connections, which has high reliability.
(1) High voltage vacuum circuit breaker
(2)Indoors
(3) Product design serial number
(4) Rated voltage(KV)
(5) Rated current (A)
(6) Rated short-circuit breaking current (kA)
ZN85-40.5 Indoor high voltage vacuum
circuit breaker(modular)
unit
KV
A
KA
project parameter
Rated voltage
Rated short-circuit breaking current
Rated short-circuit closing current (peak)
Rated current
4S thermally stable current
Rated number of short-circuit current breaks
Rated insulation
level
KA
KA
times
40.5
1600
25
63
25
63
Mechanica llife
Rated voltage of energy storage motor
times
A
V
S
V
KV
Energy storage motor energy storage time
The rated voltage of the closing and opening coil
Rated back-to-back capacitor bank current
KA
A
W
A
mm
ms
mm
ms
Main loop resistance (excluding contact walls)
Contact closure bounce time
The three-phase synthesis is divided into different periods
Contact contact travel
Contact spacing
Closing and opening coil rated current
Energy storage motor rated power
Rated single capacitor bank opening and current
Rated sequence ofoperations
Dynamically stabilized current (peak)
1min power frequency withstand voltage
Lightning impulse withstand voltage (peak)
1250
31.5
80
31.5
80
25
63
25
63
31.5
80
31.5
80
2000、2500
20
O-0.3S-CO-180s-CO
10000
630
AC、DC: 110;220
≤15
Dc: 110;220
185
400
≤230
5±1
≤2
1.05(110V)0.96(220V)
18±1
≤3
≤60
95
μΩ
TAILI 05 High voltage vacuum circuit breaker series TAILI 06 High voltage vacuum circuit breaker series
TAILI 06
High voltage vacuum circuit breaker series
TAILI 07
High voltage vacuum circuit breaker series
Appearance and installation size(mm)
Model meaning
overview
Normal conditions of use
ZW32-40.5F(M) Outdoor high voltage intelligent
(permanent magnet) vacuum circuit breaker
controller
Voltage transformer
ZW32-40.5F(M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker is mainly
composed of integrated solid-sealed pole, current transformer, operating mechanism and box.
Disconnectors can be added, this model of circuit breaker is miniaturized design, the housing is made of
high-qual ity steel box. Current transformers can be selected according to user needs.
The device is mainly used in medium voltage overhead line power grid, as a division and combined load
current, overload current, short circuit current.
(1) Vacuum circuit breaker
(2) Outdoor
(3) Product design serial number
(4) Rated voltage(KV)
(5) Demarcation switch
(6) Permanent magnet switch
(7) Disconnector
(8) Rated current (A)
(9) Rated short-circuit breaking current (KA)
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%;
Ambient temperature: not higher than +45℃, not lower than -45℃;
The altitude does not exceed 1000 meters;
The intensity of the earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements, they can be put forward when ordering, and our
company will give the greatest satisfaction.
TAILI 05 High voltage vacuum circuit breaker series TAILI 08 High voltage vacuum circuit breaker series
TAILI 06
High voltage vacuum circuit breaker series
TAILI 09
High voltage vacuum circuit breaker series
Appearance and installation size(mm)
Main technical parameters
unit
KV
A
HZ
project parameter
Rated voltage
Rated frequency
Rated short-circuit breaking current
Rated current
Lightning impulse withstand current (peak) phase to phase, to ground/break
Rated short-circuit closing current (peak)
4S short-term withstand current
KV
KV
KA
40.5
Rated operating cycle
The mechanism controls the voltage
times
KV
mm
KA
Contact spacing
Conductive loop resistance of each phase
Mechanical life times
V
mm
m/s
ms
m/s
mm
Three-phase split and close with different periodicity
Contact closure bounce time
The distance between the centers
Closing speed
Opening speed
Contact overtravel
The secondary circuit is 1min power frequency withstand voltage
Rated number of short-circuit current breaks
Rated short-circuit breaking current
Power frequency withstand pressure 1min (wet)(dry) phase, ground/fracture
630/1250
50 or 60
80 95/95
185
20/25/31.5
63/80
Cent-0.1s-combined-3s-combined-6s-combined-60s restored
30
AC/DC220
≤50
25/31.5
10000
2
0.4-0.8
≤5
1.4-0.8
≤2
≤100
63/80
KA
KA
ms
ms
ms
weight KG
Opening time
Closing time
<80
560±2
Without isolation 300 With isolation 380
18±1
4±0.5
μΩ
Model meaning
overview
Normal conditions of use
Main technical parameters
Voltage transformer
controller
unit
KV
A
HZ
project parameter
Rated voltage
Rated frequency
Rated short-circuit breaking current
Rated current
Lightning impulse withstand current (peak) phase to phase, to ground/break
Rated short-circuit closing current (peak)
4S short-term withstand current
KV
KA
KA
40.5
Rated peak withstand current KA
Power frequency withstand pressure 1min (wet)(dry) phase, ground/fracture
1250/1600
50 or 60
81
185
25/31.5
63/80
25/31.5
63/80
KA
KA
ZW7-40.5F(M) Outdoor high voltageintelligent
(permanent magnet) vacuum circuit breaker
ZW7-40.5F(M) outdoor high voltage intelligent (permanent magnet) vacuum circuit breaker adopts
auniquely designed split pole and high reliability spring operating mechanism or permanent magnet
operating mechanism. The device is mainly used in medium voltage overhead line power grid, as a
division and combined load current, overload current, short circuit current.
(1) Vacuum circuit breaker
(2) Outdoor type
(3) Design serial number
(4) Demarcation switch
(5) Permanent magnet switch
(6) Rated voltage(KV)
(7) Rated current(A)
(8) Rated short-circuit breaking current (KA)
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%;
Ambient temperature: not higher than +45℃,not lower than -45℃ ;
The altitude does not exceed 1000 meters;
The intensity of the earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements, they can be put forward when ordering, and our
company will give the greatest satisfaction.
TAILI 05 High voltage vacuum circuit breaker series TAILI 10 High voltage vacuum circuit breaker series
TAILI 06
High voltage vacuum circuit breaker series
TAILI 11
High voltage vacuum circuit breaker series
Appearance and installation size(mm)
Main technical parameters
unit
ms
project parameter
Rated operating cycle
Mechanical life
Contact spacing
Rated number of short-circuit current breaks
The secondary circuit is 1min power frequency withstand voltage
Contact overtravel
Closing speed
V
KV
mm
Cent-0.1s-combined-3s-combined-6s-combined-60s restored
Contact closure bounce time
Conductive loop resistance of each phase
mm
ms
ms
m/s
Opening time
Three-phase split and close with different periodicity ms
weight KG
Closing time
The distance between the centers
Opening speed
The mechanism controls the voltage
30
10000
AC/DC220
2
0.4-0.8
1.4-1.8
mm
m/s
800
times
times
μΩ
18±1
4±0.5
≤5
710±2
≤2
<80
≤100
≤50
TAILI 05 High voltage vacuum circuit breaker series TAILI 12 High voltage vacuum circuit breaker series Model meaning
overview
Normal conditions of use
Main technical parameters
ZW20-12F Outdoor high voltage
intelligent column demarcation
vacuum circuit breaker
controller
Voltage transformer
ZW20-12F outdoor high voltage intelligent demarcation vacuum circuit breaker is an outdoor high
voltage switchgear with rated voltage of 12KV and three-phase AC 50Hz or 60Hz. lt is mainly used to
open and close the load current, overload current and short circuit current of the power system.
lt is suitable for protection and control of substations, industrial and mining enterprises and urban
and rural distribution networks, especially suitable for places with frequent operations and urban grid
automatic distribution networks, This product is paired with a controller to meet the requirements of
the distribution automation system and can reliably and efficiently complete the traditional recloser
function. lt adopts mature box-type sealing structure, filled with SF6 gas inside, has good sealing
performance, so that it is not affected by the external environment, and is a maintenance-free product.
Its spring operating mechanism adopts direct-acting chain main drive and multi-stage trip system, which
has high action reliability and is a product for circuit breakers on columns.
(1) Vacuum circuit breaker
(2) Outdoor
(3) Design serial number
(4) Rated voltage
(5) Intelligent
(6) Rated current (A)
(7) Rated short-circuit breaking current (KA)
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%;
Ambient temperature: not higher than +45℃,not lower than -45℃ ;
The altitude does not exceed 1000 meters;
The intensity of the earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements, they can be put forward when ordering, and our
company will give the greatest satisfaction.
unit
KV
project parameter
Rated voltage
Rated current
Rated short-time withstand current (4s)
Rated frequency
Rated peak withstand current (peak)
Rated short-circuit closing current (peak)
The number of times the rated current is cut
KA
KA
KA
Rated number of times the short-circuit arbitrary current is arbitrary
net weight
KV
The secondary circuit is 1min power frequency withstand voltage KV
Power frequency withstand voltage (1min): phase between, ground / fracture
Mechanical life
Rated short-circuit breaking current
50 or 60
630、1000、1250
20、25
50、63
30
10000
A
50、63
10000
42\\48
75\\85
2
140 (with isolation≤170)
KV
KA
KG
12
20、25
Lightning impulse withstand voltage (peak) phase to phase, to ground/break
times
times
times
HZ
Appearance and installation size(mm)
Main technical parameters
unit
mm
mm
m\\s
project parameter
Contact spacing
Opening speed
The distance between the centers
Contact overtravel
Contact closure bounce time
External live air insulation distance
Three-phase opening has different periodicity
m\\s
ms
mm
9±0.5
Closing time
The rigid position of the tentacle is deviated
ms
mm
W
cm\\KV
Energy storage motor rated power
SF6 gas pressure rating (gauge)
Lsolation break spacing
ms
mm
V
V
V
V
V
Max/min motor voltage
Maximum/minimum open operating voltage
Rated closing operating voltage
Rated voltage of energy storage motor
Manual closing torque operation
Opening time
External creepage ratio
Closing speed
3±0.5
1.2±0.2
0.6±0.2
≤2
135±1.5
240±2
≤45
≤45
≤2
≤2
≥190
≤150
AC264/143
AC220
AC220
AC242/187
3.8
mm
ms
V
‘‘0’’
AC264/143
MPa
≯40
AC220
N.m
Conductive loop resistance of each phase 150(with isolation ≤200)
Maximum/minimum closing operating voltage
Rated opening operating voltage
μΩ
TAILI 06
High voltage vacuum circuit breaker series
TAILI 13
High voltage vacuum circuit breaker series
Model meaning
overview
Normal conditions of use
Main technical parameters
FZW28-12F Outdoor demarcation
vacuum load switch
controller
Voltage transformer
(1) Vacuum load switch
(2) Outdoor
(3) Design serial number
(4) Rated voltage(kv)
(5) Demarcation switch
(6) Rated current (A)
(7) Rated short-circuit breaking current (KA)
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%;
Ambient temperature: not higher than +45℃,not lower than -45℃ ;
The altitude does not exceed 1000 meters;
The intensity of the earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements, they can be put forward when ordering, and our
company will give the greatest satisfaction.
unit
KV
project parameter
Rated current
Rated frequency
Rated voltage
Rated closing short-circuit current (peak)
Operating voltage
HZ
rating
KV
KV
Rated short-time withstand current (4S)
12
630
12.5 16 20
31.5 40 50
48
42
KV
A
AC220V(80%~110%)
42
2
75
75
84
Manual or automatic (electromagnetic)
50 or 60
Power frequency
withstand voltage
(1min)
lmpact pressure
(Peak)
interphase
To the ground
To the ground
Secondary to ground
interphase
fracture
fracture
KV
KV
KV
KV
Requirements for High Voltage Switchgear and Control Equipment Standards\".
FZW28-12F outdoor demarcation vacuum load switch (referred to as demarcation switch) is used in
outdoor column installation occasions, with manual and electric operation function. The switch body
adopts the VSP5-12 technology introduced from Toshiba of Japan, and this switch is a maintenance-free
load switch. Vacuum arc extinguishing and SF6 gas are used as ground and interphase insulation media.
This product complies with: GB3804 \"High Voltage AC Load Switch\" and GBT11022 \"Common Technical
FZW28-12F outdoor demarcation vacuum load switch has fault detection function, protection control
function and communication function, installed on 10KV overhead line, can realize automatic cutting of
single-phase ground fault and automatic isolation of short-circuit fault between phases. The installation
point is suitable for the dividing point of responsibility for the incoming line of the 10KV distribution line
user, and can also be applied to the branch line connection that meets the requirements.
TAILI 05 High voltage vacuum circuit breaker series TAILI 14 High voltage vacuum circuit breaker series
TAILI 06
High voltage vacuum circuit breaker series
TAILI 15
High voltage vacuum circuit breaker series
Appearance and installation size(mm)
Main technical parameters
project unit parameter
net weignt
Determination of manual force of the operating handle
SF6 gas pressure rating
Open gate operation
V
Closing operation
Main loop resistance
0 gauge pressure concentration is more than 93%.
100~400
≤500
120-160
N
3. Pull-in current (peak) below 17A 4 Holding current is not more
than 0.45A
1. Opening time 1.5s or less /2. Different period time less than
30ms
6~13
65~85V
KG
ms
185
1.Closing time 120~180ms(220V)/2. Bounce time is not more
than 10ms
V
μΩ
mm
mm
mm
mm
10±2
0.2 Mpa gauge pressure without air leakage
7~9
3~3.5
25~30
184~220V
Minimum closing voltage
184~220V
Minimum holding voltage
Air tightness test (leak detection)
Vacuum interrupter contacts are overrange
Vacuum interrupter contact opening distance
Isolation break spacing
lsolation break overrange
The difference in operation time between the isolation break and the
vacuum arc chamber
Opening and closing
unit
KV
A
HZ
project parameter
Rated voltage
Rated frequency
Rated short-circuit breaking current
Rated current
Lightning impulse withstand current (peak) phase to phase, to ground/break
Rated short-circuit closing current (peak)
4S short-term withstand current
KV
KA
KA
12
Rated bee value withstand current KA
630.1250
42/48
75/85
20
50
20
50
KA
KA
25
63
25
63
34
Power frequency withstand
voltage(1min)
Dry (interphase, ground/fracture)
Wet test (ground and external insulation)
50 or 60
Model meaning
overview
Normal conditions of use
Main technical parameters
ZW32-12F Outdoor high voltage
intelligent demarcation vacuum
circuit breaker
controller
When the 12KV overhead distribution line T branch line or the end user fails, when the protection action
time limit of the inlet switch and the protection time limit of the substation outlet switch cannot be
reasonably adjusted, it will cause the substation outlet switch to trip.lf the fault is permanent in nature
and the substation coincidence will be unsuccessful,a local disturbance within the medium-voltage
user boundary will outage the entire 12KV distribution line. lf an outdoor demarcation circuit breaker is
installed at the T junction or the user end (responsibility demarcation point),and the fault (overcurrent,
short circuit, single-phase ground, etc.) is confirmed within the user boundary after judgment, the fault is
automatically isolated, which can ensure the normal power consumption of users in non-fault areas.The
application of ZW32-12F outdoor high-voltage intelligent demarcation vacuum circuit breaker (watchdog)
on 12KV feed overhead line can avoid the cascade power outage oftrouble-free lines,reduce the scope of
faulty power outages, shorten the power outage time of users, and protect the safe operation of the main
network. And with fault detection function, protection control function and communication function, it
can realize automatic cutting of single-phase ground fault and automatic isolation of short-circuit fault
between phases. The installation point is suitable for the dividing point of responsibility for the incoming
line of the 12KV distribution line user, and can also be applied to the branch line connection that
meets the requirements.
(1) Vacuum circuit breaker
(2) Outdoor type
(3) Design serial number
(4) Rated voltage(KV)
(5) Demarcation switch
(6) With disconnector
(7) Rated current (A)
(8) Rated short-circuit breaking current (kA)
Air relative humidity: daily average is not more than 95%, monthly average is not more than 90%;
Ambient temperature: not higher than +45℃,not lower than -45℃ ;
The altitude does not exceed 1000 meters;
The intensity of the earthquake does not exceed 8 degrees;
Places free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Note: lf customers have other special requirements, they can be put forward when ordering, and our
company will give the greatest satisfaction.
TAILI 05 High voltage vacuum circuit breaker series TAILI 16 High voltage vacuum circuit breaker series
TAILI 06
High voltage vacuum circuit breaker series
TAILI 17
High voltage vacuum circuit breaker series
Appearance and installation size(mm)
Main technical parameters
unit
m/s
project parameter
Rated operating cycle
Mechanical life
Contact spacing
Rated number of short-circuit current breaks
The secondary circuit is 1min power frequency withstand voltage
Contact overtravel
Closing speed
KV
mm
Minutes -0.3s - combined points -180s -combined points
Contact closure bounce time
Conductive loop resistance of each phase
ms
ms
mm
Three-phase split and close with different periodicity
weight KG
The distance between the centers
Opening speed
30
10000
2
mm
m/s
times
times
μΩ
9±1
2.5±1
0.6±0.2
≤2
340±2
≤2
≤80(with isolation ≤150)
1.1±0.3
Without isolation 110 Without isolation 140
High voltage load switch series TAILI 18
Model meaning
overview
Normal conditions of use
FZN21-12RD Indoor
isolation vacuum load switch
FZN21-12D/T630-20, FZN21-12DR/T125-31.5 indoor isolation vacuum load switch-fuse combination
electrical type high-voltage vacuum load switch and combination electrical appliance used in threephase AC 12KV, 50HZ or 60Hz power distribution system, with compact structure, small size, light weight,
long life, strong closing and breaking ability, safe and reliable, etc., and fuse (referred to as combination
electrical appliance), can replace the higher cost circuit breaker, its operation and maintenance is
simpleand convenient.
(1) Vacuum load switch
(2) Design serial number
(3) Rated voltage
(4) Rated current
(5) Rated short-time withstand current
(1)Indoor vacuum load switch
(2) Design serial number
(3) Rated voltage
(4) Fuses
(5) Grounding switch
(6)Maximum rated current of fuse
(7) Rated short-circuit breaking current
Ambienttemperature -45℃~+45℃:
Altitude≤1000m:
Relative humidity: daily average is not more than 95%, monthly average is not more than 90%:
Places without conductive dust, corrosive gases and water vapor:
Places where there is no risk of fire and explosion; Places without severe vibration and inclination less
than 3°.
High voltage load switch series
TAILI 19
High voltage load switch series TAILI 20 Structural features, performance and external installation size (mm)
Main technical parameters
FZN21-12indoorisolation vacuum load switch and combination electrical appliance are mainly composed of frame. disconnector or fuse as disconnector),
vacuum interrupter, grounding switch, operating mechanism, etc.
This product has compact structure. small size. ong life. strong closing and breaking abilitv. and simple operation and maintenance. The vacuum switch is
equipped with an electric operating mechanism and an energy storage spring for fast merging operation. Disconnectors, vacuum switches, and grounding
switches are interlocked with each other to prevent misoperation.
parameter
project unit
times
Rated voltage
Rated current
Rated short-circuit closing current
KA
A
A
V
Rated short-circuit breaking current(combination electrical appliance)
A
KA
KV
KA
KA
KA
KA
FZN21 FZRN21
Rated active load breaking current
4S thermally stable current
Dynamically stabilize the current
1min power frequency withstand voltage
Lightning impulse withstand voltage
Mechanical life
Rated transfer current (combiner)
The motor operates the supply voltage
630
50
-
630
75(break 85)
42(Break 48)
50
12
20
AC and DC 110,220
-
10000
125
50
31.5
630
75(break 85)
42(Break 48)
-
12
-
AC and DC 110,220
3150
10000
1. Framework
2. lsolation knife
3. Fuse
4. Insulated tie rod
5. Upper bracket
11. Opening spring
12. Insulated tie rod
13. Spindle
14. Trip mechanism
15. Pay the shaft
6. Arc extinguishing chamber
7. Grounding knife static contact
8. Insulators
9. Grounding knife
10. Grounding spring
16. Linkage tie rod
17. Operating mechanism
Load switch without fuse (item 3) and trip mechanism (item 14)
Model meaning
overview
Environmental conditions of use
FKN12-12 indoor high-voltage compressed gas load switch (hereinafter referred to as FKN12-12 load
switch) is a three-phase high-voltage switchgear with a rated voltage of 12V and a rated frequency
of 50Hz or 60Hz, which is used to separate load current, closed-loop current, no-load transformer and
current charging current, and close short-circuit current. A load switch equipped with a grounding switch can
FKRN12-12 indoor high-voltage load switch fuse combination electrical appliance (hereinafter referred
to as FKRN12-12 combination electrical appliance) is an indoor switchgear combined with FKN12-12 load
switch and SKLAJ-12 (XRNTC1-10) high-voltage current limiting fuse. lt can reliably cut off any current up
to the short-circuit current; The load switch breaks the current, the fuse breaks the short-circuit current,
and the joint interrupts any current between the working current and the full short-circuit current,
while the fuse opens the load switch through its impactor.
withstand short-circuit currents.
(1) Load switch
(2) Air medium
(3)Indoors
(4) Design serial number
(5) Rated voltage(KV)
(6) Grounding switch
(7) Spring mechanism
(8) Rated current(A)
(9) Rated short-time withstand current (KA)
(1)Load switch
(2)Air medium
(3) Fuse protection
(4)Indoors
(5) Design serial number
(6) Rated voltage(kV)
(7) Grounding switch
(8) Spring mechanism
(9) Rated current (A)
(10) Rated short-circuit breaking current (KA)
Description: The spring mechanism is divided into manual operation spring mechanism and electric
operation spring mechanism.
Sea level: not more than 1000m;
Airtemperature:-45℃~+45℃;
Relative humidity: daily average is not more than 95%, monthly average is not more than 90%:
Earthquake intensity: no more than 8 magnitude;
Installation site: no fire, explosion risk, chemical corrosion and severe vibration place;
Pollution level: Grade ll.
FKN12-12/FKRN12-12 Indoor
high voltage gas insulated
load switch
High voltage load switch series
TAILI 21
High voltage load switch series TAILI 22 Main technical parameters
Appearance and installation size(mm)
Model meaning
overview
Environmental conditions of use
FZN25-12 indoor high voltage vacuum load switch is a three-phase AC 50Hz or 60Hz, rated voltage 12KV
indoor device, used with industrial and mining enterprise power distribution stations and substations and
other occasions, as the protection and control of electrical facilities, used to divide load current,
FZRN25-12 indoor high voltage vacuum load switch fuse combination electrical appliance is a threephase AC 50Hz, rated voltage 12KV indoor device, suitable for industrial and mining enterprise power
distribution stations and substations and other occasions, for load control and short circuit protection.
Equipped with a grounding switch that can withstand short-circuit currents. The operating mechanism
can be manually closed electrically, which is convenient to realize the three remote control requirements
FZN25-12, FZRN25-12 series load switches and combination electrical appliances are suitable for
three-phase ring network or terminal power supply urban distribution stations and industrial power
equipment, for load control and short circuit protection. Because the protective effect of combined
electrical appliances on electrical equipment such as transformers is more reliable and economical than
open circuits, it is especially suitable for ring networks, dua-radiation power supply units and box-type
substations.
of the power system.
(6) Grounding switch
(7)Spring mechanism
(8) Rated current (A)
(9) Rated short-time withstand current (KA)
(10) Mode ofoperation
(1) Load switch
(2) Vacuum
(3)Indoors
(4) Design serial number(5) Rated voltage(KV)
FZN25-12/FZRN25-12 Indoor high
voltage vacuum load switch
(7)Grounding switch
(8) Spring mechanism
(9) Rated current(A)
(10) Rated short-circuit breaking current (KA)
(11) Mode ofoperation
(1) Load switch
(2) Vacuum
(3) Fuse protection
(4)Indoors
(5) Design serial number
(6) Rated voltage(KV)
Ambient temperature: maximum temperature + 45℃ ; Mnimum temperature: -45℃ ;
Altitude: not more than 2000m;
Relative humidity:< 95%;
Earthquake intensity: 8 magnitude;
Installation site: no dripping, fire, no explosion risk, serious pollution, chemical corrosion and severe vibration in the place of use
High voltage load switch series
TAILI 23
closed-loop current, no-load transformer and cable charging current.
High voltage load switch series TAILI 24 Main technical parameters
Appearance and installation size(mm)
High voltage load switch series
TAILI 25
overview
FLN36 high/medium voltage SF6 load break switch, with a rated voltage of 12kv, 24kv or 36kv,
can response and protect power system when there is an error. The switch can be either manual
operation or electrical operation, and earthing function is optional. Switch fuse combination can
protect the whole system.
Basic functions and features:
Normal conditions of use
1.Load breaker switch adapts double fracture, rotary movable contact structure, with the following three kinds of operating
states: Closing,opening,earthing.
2.Using SF6 gas as an arc extinguishing and insulating medium, the main circuit seals by the upper and lower housing
pouring epoxy resin, the conductive function is unaffected by external influences.
3.Good safety performance. If internal arcing occurs, the housing has an internal structure weak point, it will be rushed to
open, followed by the cabinet above the shutter release arc red open air overpressure stream-oriented outside the
cabinet, ensure that the switch cabinet security checks.
4.Load breaker switch sets gates, opening, earthing switch three at one, filled with SF6 gas encapsulated in epoxy resin
housing, three-position interlock,compact structure,high security and reliability.
5.Small size, light weight, maintenance-free, easy and safe to operate.
F L N 36 -12 /
Rated short-time withstand current(KA)
Rated current(A)
Rated voltage(KV)
Design number
Indoor type
Sulfur hexafluoride
Load switch
1. Altitude: ≤1000m
2. Ambient temperature at -45ºC to +45ºC, the daily average temperature should not more than 30ºC.
3. The daily average of relative humidity is less than 95%, the average monthly is less than 90%.
4. Working environment should be without steam, gas, chemical corrosive deposition, salt fog, dust, dirt and other
dangerous explosive media, which will severely impact on insulation and conductivity of products.
5. Working environment should not be regular vibration or serious bumps.
FLN36-12 SF6 Insulated
high voltage load break switch
Main technical parameters
Appearance and installation size(mm)
High voltage load switch series TAILI 26
FLN36 -24kV load break switch use SF6 gas as arc extinguishing and
insulating medium. There are three work stations: opening, closing and
grounding in the switch. It has small volume, installing easy-to-use, strong
environmental adaptability and other characteristic.
24kV 230mm distance is newly developed type.
overview
F L N 36 -24 /
Rated current(A)
Rated voltage(KV)
Design number
Indoor type
Sulfur hexafluoride
Load switch
Rated short-time withstand current(KA)
1.Altitude: ≤2000m
2.Ambient temperature: -45°C ~+45°C
3.Earthquake intensity: ≤8 degree
4.Relative humidity: Daily averages ≤95%, Monthly average≤90%
Main technical parameters
Appearance and installation size(mm)
Normal conditions of use
High voltage load switch series
TAILI 27
FLN36-24 SF6 Insulated
high voltage load break switch
TAILI 28 High voltage load switch series FLN48-12 load break switch use SF6 gas as arc extinguishing and insulating
medium. There are three work stations: opening, closing and grounding in the
switch.
It has small volume, installing easy-to-use, strong environmental adaptability and
other characterist.
overview
Normal conditions of use
1.Altitude: ≤2000m
2.Ambient temperature: -45°C ~+45°C
3.Earthquake intensity: ≤8 degree
4.Relative humidity: Daily averages ≤95%, Monthly average≤90%
F L N 48 -12 /
Rated current(A)
Rated voltage(KV)
Design number
Indoor type
Sulfur hexafluoride
Load switch
Rated short-time withstand current(KA)
Main technical parameters
FLN48-12 SF6 Insulated
high voltage load break switch
TAILI 29
High voltage load switch series
Appearance and installation size(mm)
TAILI 30 Instrument transformer series
TAILI 31
Instrument transformer series
JDZX11-35R voltage transformer is epoxy resin casted fully enclosed structure, suitable for power
system with rated frequency 50Hz or 60Hz and rated voltage 35kV, for power metering, voltage
monitoring and relay protection. This product conforms to IEC60044-2 and GB1207 \"voltage
transformer\" standard.
J D Z X 11 - 35 R
With fuse tube
voltage grade,KV
design sequence
with residual voltage winding
casting resin insulated
single phase
currenttransformer
Type Rated voltage ratio(V)
Accuracy class
combination
Rated output(VA) Max output(VA)
Rated insulation
level(kV)
JDZX11-35R
JDZXF11-35R
35000/ 3/100
/ 3/100/3
35000/ 3/100
/ 3/100/ 3/100/3
0.2/6P
0.2/0.2/6P
0.5/6P
0.2/0.5/6P
0.5/0.5/6P
30/100
20/20/100
50/100
20/30/100
30/30/100
600
2x300
40.5/95/200
JDZX11-35R Single phase
voltage transformer with fuse
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Normal conditions of use
TAILI 32 Instrument transformer series JSZV1-10R Profile
TAILI 33
Instrument transformer series
J D Z X 11 - 20 R
With fuse for protecion
Rated voltage(KV)
Deasign No.
Residual voltage winding
Casting insulation
Single-phase
Voltage transformer
JDZX11-20R series voltage transformer is epoxy resin insulated and fully enclosed structure,
resistant to dirt and humidity, also suitable for use in tropical areas. The transformer is small in
size, light in weight, with small partial discharge and strong over-voltage resistance, suitable for
installation in any position and direction.
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Normal conditions of use
JDZX11-20R Single phase
voltage transformer with fuse
Rated secondary output(VA)
Wiring
diagram
24/65/125
Figure 1
Figure 2
0.2 0.5
class
1
0.2/0.2
0.2/0.5
0.5/0.5 6P
2000 100 100
/ / 3 3 3
20000 100 100 100
/ / / 3 3 3 3
30 80 150
15/15
15/20
/ / 100 400
/ / / / 30/30 100 300 300
class
3
300
TAILI 34 Instrument transformer series J S Z V 12 - 10 R
With fuse for protecion
Rated voltage(KV)
Deasign No.
Residual voltage winding
Casting insulation
Single-phase
Voltage transformer
The combination transformer of voltage、 current is used for voltage、current and power
measurement and relay protection in three phase A、C line with rated frequency50 Hz and rated
voltage 10KV. lt applicable to be used for industry corporation small typechanging- matching
electricity-place and box type transformer substation.
Normal conditions of use
JSZV1(2、3)-10R
Three phase combined
voltage transformer with fuse
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Type
Accuracy class and rated
output(VA)
Maxoutput(VA)
rated insulation
level(KV)
class 0.2 class 0.5
500
JSZV12-10R
JSZV12-10R
JSZV12-6R
10000/100
10000/100
6000/100
Rated voltage
ratio(V)
20 60
20 60
12/42/75
12/42/75
7.2/32/60
Type
Accuracy class and
rated output(VA)
Short time Max
output power(VA)
rated insulation
level(KV)
500
JSZV12-10R
JSZV12-10R
JSZV12-6R
JSZV12-3R
JSZV12-10R
JSZV12-6R
10/0.1/0.22
10/0.1/0.1
6/0.1/0.1
3/0.1/0.1
10/0.1
6/0.1
Rated voltage
ratio(V)
60
2×400
12/42/75
12/42/75
7.2/32/60
3.6/25/40
12/42/75
7.2/32/60
0.2
0.2
0.2
0.2
30
20
20
20
form 1:technical data of voltage transformer for measuring
(form 2: technical data of voltage transformer for circuit breaker operating power)
Notes: voltage resistance should not exceed 15% for circuit breaker operating power
TAILI 35
Instrument transformer series
J S Z V 1 - 10 R
with fuse
voltage grade,KV
design sequence
“V”wiring manner
castingresininsulated
three phase
voltage transformer
The combination transformer of voltage、 current is used for voltage、current andpower
measurement and relay protection in three phase A、C line with rated frequency 50Hz or 60Hz and
voltage 10KV. lt applicable to be used for industry corporation small typechanging- matching rated
electricity-place and box type transformer substation.
Normal conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Type
Accuracy class and
rated output(VA) rated insulation
level(KV)
JSZV1-10R
JSZV2-10R
JSZV3-10B
JSZV1-6R
JSZV2-6R
JSZV3-6R
10000/100
10000/100
10000/100
6000/100
6000/100
6000/100
Rated voltage
ratio(V)
12/42/75
12/42/75
12/42/75
7.2/32/60
7.2/32/60
7.2/32/60
20
20
20
50
50
50
class 0.2 class 0.5
500
500
Maxoutput(VA)
form 2:technical data of voltage transformer for circuit breaker operating power
Notes: voltage resistance should not exceed 15% for circuit breaker operating power
Type Short time Max output power(VA)
rated insulation
level(KV)
JSZV1-10R
JSZV2-10R
JSZV3-10R
JSZV1-6R
JSZV2-6R
JSZV3-6R
10/0.1/0.22
10/0.1/0.22
10/0.1/0.22
6/0.1/0.22
6/0.1/0.22
3/0.1/0.22
Rated voltage
ratio(V)
12/42/75
12/42/75
12/42/75
7.2/32/60
7.2/32/60
7.2/32/60
500
500
500
form 1:technical data of voltage transformer for measuring
JSZV1(2、3)-10R
Three phase combined voltage
transformer with fuse
TAILI 36 Instrument transformer series LMZC-10 high precision current transformer is suitable for current and electric energy
measurement and protection of 35KV and 10KV in AC power systems.The current transformer has
the characteristics of small volume,light weight,convenient.
installation and the like.Have full insulation is widely used in compact ring switchgear in ABB-Safe
Ring/plus’ Uniswitch,Schneider RM6/SM6’ Eaton SVS ’ GA/GE Germany,FB France,SS Korea,etc.
lt also can be used in combined type transformer substations and cable distribuion boxes.The core
current transformer selection of composite alloy core permeabiity,hichsaturation maanetic induction
intensity is low as magnetic materia, with high precision and high satety factor,high quality imported
steel processed by advanced technology as the core of the protection windings,ensure the accuracy
limit factor.Ring core and two windings using high-quality epoxy resin vacuum casting in aplastic
casing,the fire retardant moisture proof,stable performance,no need cf maintenance.The current
transformer has the advantaaes of small volume, ligh weiht,small occupied space,and is fixed in the
cable room of the switch cabinet of the ring network cabinet.Based on the current ratio,accuracy and
rated load the current transformers can be divided into the following several types,parameters of
specific parameters foreach model corresponding to the.
L M Z C (1、2、3)-10
Rated power
Design No
Insulating type
Casting insulation type
Bus type
Current transformer
Normal conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
LMZC(1、2、3)-10
Bushing current transformers
TAILI 37
Instrument transformer series
Type
Purpose Measuring current transformer Protection current transformer Double winding current
Ratio
Acc.class and rated
40/1
50/1
75/1
100/1
150/1
200/1
300/1
400/1
500/1
600/1
100/5
150/5
200/5
300/5
400/5
500/5
600/5
2.5
3.75
5
7.5
10
12.5
2.5
3.75
5
7.5
10
12.5
1
1
2.5
3.75
5
7.5
10
12.5
15
2.5
3.75
5
7.5
10
12.5
15
1
1
25
375
5
75
10
125
15
25
375
5
75
10
125
15
1
1
1
25
375
5
5
75
1
1
25
375
5
5
75
1
1
1
25
375
5
75
10
125
1
25
375
5
75
10
125
1
1
25
375
5
75
125
15
20
25
375
5
75
125
15
20
25
1
1
25
375
5
5
1
25
375
5
5
1
1
25
375
5
5
75
1
1
25
375
5
5
75
1
25
375
375
5
75
1
1
25
25
375
375
5
75
1
25
375
5
75
75
10
15
375
5
75
75
10
15
LMZC1、2、3-10
0.2S 0.2 0.5 10P10 10P5 02 05 10P10 10P5
Acc.class and rated Acc.class and rated
TAILI 38 Instrument transformer series LSY107-10 series current ransformer switch special transformer for outdoor column,the instalationis
fixed on the casing of the circuit breaker three-phase outdoor switch,can simultaneous achieve short
circuit protection,single groundini(zero) protection and provide power supply for the controller and
other functions.Can also be used in the ring network cabinet out of the three-phase casing,used as
a current measurement of electrical equipment,electrical energy measurement and microcomputer
protection.At present in the ZW20, ZW27, ZW28, VSP5 and other outdoor pole switch s widely used
to solve the problem of the internal space of the column switch can not install the zero sequence
The ron core and the two winding of the series transformer are made of hi quality epoxy resin vacuum
casting in the body of te fire retardant plastic casing,which can prevent moisture,stable performance
and no need of maintenance
transformer,by a large number of users.
J S Y 107 - 10
Rated power
The pitch of three-phase
Low voltage
Three phase
Current transformer
Normal conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
LSY107-10 Three phase
combined bushing
current transformer
Type
Purpose Measuring current transformer Protection current transformer Double winding current
\\PRatiol1/l2
Acc.class and rated
100/1
150/1
200/1
300/1
400/1
500/1
600/1
100/5
150/5
200/5
2.5
3.75
5
1
25
3.75
5
75
25
1
25
5
7.5
10
15
1
2.5
3.75
1
1
2.5
2.5
2.5
3.75
1
2.5
3.75
3.75
5
5
75
1
25 1
2.5
2.5
3.75
5
5
1
2.5
3.75
5
7.5
10
125
1
25
LSY107-10
0.2S 0.2 0.5 10P15 10P10 10P5 05 10P10 10P5
Acc.class and rated Acc.class and rated
25
3.75
5
7.5
10
12.5
15
2.5
3.75
5
TAILI 39
Instrument transformer series
L X K - Φ80~Φ240
inside diameter of the transformer
break-make type)
cable type zero sequence current transformer
Normal conditions of use
LXKΦ80-Φ240 Zero sequence
current transformer
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
The series of zero current transformers are used indoor. They are used for over driven
current protection in the electric non-useful-ground neutral system up to rated frequency 50Hz
or 60Hz and rated voltage 35KV. The type of the relay fitting with the transformers is DD-11/60、
DD-1/60.
The zero current transformers of LX K-Φ80~Φ240 series are casting into two half circles.
ln installation, the transformer can be clipped together.
Rated output(VA)
Bated current
ratio(A)
Accuracy class
10P10
1
1.5
2.5
3.75
5
2.5
5
7.5
10
form 1:technical data of voltage transformer for measuring
Rated current ratio, accuracy class,rated output see form1
TAILI 40 Instrument transformer series Rated current
ratio(A)
Relay type Primary zero sequence
current(A)
Connecting method
of relay windings
DD—11/60
DD—11/60
Series connection
Parallel connection
Series connection
Parallel connection
15x1~30x1
15x2~30x2
15x1~30x1
15x2~30x2
2~5
2~6
60/1
Type φd φD H h
LXK- φ80
LXK- φ100
LXK- φ120
LXK- φ140
LXK- φ80
LXK- φ160
LXK- φ180
LXK- φ200
LXK- φ240
80
100
120
140
150
160
180
200
240
160
180
200
220
230
240
260
280
320
175
195
215
235
245
255
275
295
335
82.5
92.5
102.5
112.5
123.5
122.5
132.5
142.5
162.5
TAILI 41
Instrument transformer series
Normal conditions of use
1.Rated frequency: 50 or 60Hz;
2.Anti-Pollution grade: Class II;
3.Ambient temperature: -45℃+45℃ , daily average temperature not more than 30℃
4.Altitude:≤1000m;
Current Transformer LZZBJ9-10 is made indoor cast-resin insulated, totally- enclosedstructure.
lt ’s designed for current, power measurement and relay protection in AC powersystem with
rated frequency 50Hz or 60Hz, rated voltage 10KV and below.
L Z Z B J 9 - 10 (AC)
the construction code
voltage grade,KV
enhancement type
with protection
casting resin insulated
post type
current transformer
design sequence
LZZBJ9-10 Current
transformer 10KV
combination
1000
1200
1250
1500
2000
TAILI 42 Instrument transformer series LZZBJ9-10A
LZZBJ9-10C
M8 Earthing bolts