Description
This product is a three-phase AC 50Hz, rated voltage 40.5 kV indoor complete set of power distribution device. It is used for receiving and distributing electric energy in power plants, substations and industrial and mining enterprises. It also has the functions of controlling, protecting and detecting circuits
| No. | Name | Unit | Parameter | |
| 1 | Rated voltage | kV | 40.5 | |
| 2 | Rated frequency | Hz | 50 | |
| 3 | Rated current | A | ≤3150 | |
| 4 | Temperature-rise testing | 1.1lr | ||
| 5 | Rated power frequency withstand voltage (1min) | kV | 95 | |
| 6 | Rated lightning impulse withstand voltage (peak) | kV | 185 | |
| 7 | Rated short-circuit breaking current | kA | 31.5 | |
| 8 | Rated short-circuit closing current | kA | 80 | |
| 9 | Rated short-time withstand current and continuous time | kA/s | 31.5/4 | |
| 10 | Rated peak withstand current | KA | 80 | |
| 11 | Short-time power frequency withstand voltage of theAuxiliary and control circuit | kV | 2 | |
| 12 | Partialdischarge | Testing voltageSingle insulating parts | kV | 1.1x40.5≤3 |
| pC | ||||
| 13 | Protectiongrade | CasingCompartments | IP4XIP2X | |
| 14 | Creepagedistance | Porcelain material (to ground)Organic material (tò ground) | mm | ≥729≥810 |
| 15 | Interphase and pdistance (air insu | hase to ground clearlation) | mm | ≥300 |
| 16 | Loss of continuity of operation category | LSC2 | ||
| 17 | Minimum clear distance of SMC baffle plate(if any) to live conductor | mm | ≥60 | |
| 18 | Thickness of SMC baffle plate | mm | ≥5 | |
| 19 | Cooling mode | Self cooling1) | ||
| 20 | Allowable duration of internal arc | LSC2 | ||
KYN61C-40.5
High voltage Switchgear case
Structure characteristics
On the basis of keeping the original size of 1200x2400x2600 unchanged, the internal layout is reasonably adjusted, and the clear distance of copper bars in bus chamber is more than 300mm except phase-to-phase
On the basis of keeping the original size of 1200x2400x2600 unchanged, the internal layout is reasonably adjusted, and the clear distance of copper bars in bus chamber is more than 300mm except phase-to-phase
The valve of the cabinet body adopts a lever-type steel mechanism, which realizes that the valve can be driven normally only by unilateral force, without jamming, and is stable and reliable.
KYN61C-40.5 High voltage Switchgear case
Structure characteristics
The new grounding interlocking mechanism has the advantages of small operation force, long service life, strong stability, convenient assembly, commisioning and maintenance, etc.
The handcart base adopts track structure and uses special welding fixture to tamp and stabilize.
The secondary line is laid in the secondary line groove with full metal protection, which can effectively protect the burning of the secondary line by the electric strength when the cabinet is in trouble, and the signal can be accurately transmitted to the comprehensive protection control system through the secondary line, so that the fault can be quickly removed, the damage degree of the electrical equipment caused by the fault can be reduced, and the stability of the power system can be improved.
KYN28A-24
High voltage Switchgear case
Description
This product is a three-phase AC 50Hz, rated voltage 24kV indoor complete set of power distribution device. It is used for receiving and distributing electric energy in power plants, substations and industrial and mining enterprises. It also has the functions of controlling, protecting and detecting circuits.
| No. | Name | Unit | Parameter | |
| 1 | Rated voltage | kV | 24 | |
| 2 | Rated frequency | Hz | 50 | |
| 3 | Rated current | A | ≤3150 | |
| 4 | Temperature-rise testing | 1.1lr | ||
| 5 | Rated power frequency withstand voltage (1min) | kV | 65 | |
| 6 | Rated lightning impulse withstand voltage (peak) | kV | 125 | |
| 7 | Rated short-circuit breaking current | kA | 31.5 | |
| 8 | Rated short-circuit closing current | kA | 80 | |
| 9 | Rated short-time withstand current and continuous time | kA/s | 31.5/4 | |
| 10 | Rated peak withstand current | kA | 80 | |
| 11 | Short-time power frequency withstand voltage of theAuxiliary and control circuit | kV | 2 | |
| 12 | Partialdischarge | Testing voltageSingle insulating parts | kV | 1.1x40.5≤3 |
| pC | ||||
| 13 | Protectiongrade | CasingCompartments | IP4XIP2X | |
| 14 | Creepagedistance | Porcelain material (to ground)Organic material (tò ground) | mm | ≥432≥480 |
| 15 | Interphase and pdistance (air insu | hase to ground clearlation) | mm | ≥180 |
| 16 | Loss of continuity of operation category | LSC2 | ||
| 17 | Minimum clear distance of SMC baffle plate(if any) to live conductor | mm | ≥45 | |
| 18 | Thickness of SMC baffle plate | mm | ≥5 | |
| 19 | Cooling mode | 自冷1) | ||
| 20 | Allowable duration of internal arc | S | 1 | |
KYN28A-24 High voltage Switchgear case
Structure characteristics
The structure of grounding interlock is simpler, the action is more flexible and reliable, and the interlocking function can be switched freely regardless of whether it is equipped with a grounding switch operated manually or electrically, without changing any parts.
A set of interlocking device is used to realize the interlock between the rear upper and lower doors, so as to ensure that the rear door cannot be opened when the rear lower door is not opened; On the contrary, the rear lower door cannot be closed when the rear door is not closed.
The side plate adopts internal folding double bending technology, the skeleton is connected with nested steel nails, and there are no protruding screws and abdication holes on the side, which can realize single replacement after failure and shorten the time for restoring power supply.
KYN28A-24
High voltage Switchgear case
Structure characteristics
The valve mechanism adopts an integrated base, which has higher stability.
The valve guide rail adopts aluminum alloy guide rail, which has higher matching accuracy, makes the valve slide more flexible, and increases the air distance between the valve guide rail and the handcart, which improves the overall safety of the valve mechanism.
The secondary line is laid in the secondary line groove with full metal protection, which can effectively protect the burning of the secondary line by the arc when the cabinet is in trouble, and the signal can be accurately transmitted to the comprehensive protection control system through the secondary line, so that the fault can be quickly removed, the damage degree of the fault to the electrical equipment can be reduced, and the stability of the power system can be improved.
The instrument door is equipped with self-leading device to prevent drooping, opening limit device and adjustable wire binding frame. The instrument box is equipped with flippable terminal mounting beam to facilitate secondary wiring.
KYN28A-12
Description
This product is a three-phase AC 50Hz, rated voltage 40.5 kV indoor complete set of power distribution device. It is used for receiving and distributing electric energy in power plants, substations and industrial and mining enterprises. It also has the functions of controlling, protecting and detecting circuits.
| No. | Name | Unit | Parameter | |
| 1 | Rated voltage | kV | 12 | |
| 2 | Rated frequency | Hz | 50 | |
| 3 | Rated current | A | ≤4000 | |
| 4 | Temperature-rise testing | 1.1lr | ||
| 5 | Rated power frequency withstand voltage (1min) | kV | 42 | |
| 6 | Rated lightning impulse withstand voltage (peak) | kV | 75 | |
| 7 | Rated short-circuit breaking current | kA | 40 | |
| 8 | Rated short-circuit closing current | kA | 100 | |
| 9 | Rated short-time withstand current andcontinuous time | kA/s | 40/4 | |
| 10 | Rated peak withstand current | kA | 100 | |
| 11 | Short-time power frequency withstandvoltage of auxiliary and control circuit | kV | 2 | |
| 12 | Partialdischarge | Testing voltageSingle insulating parts | kVpC | 1.1x 12≤3 |
| 13 | Protectiongrade | CasingCompartments | IP4XIP2X | |
| 14 | Creepagedistance | Porcelain material (to ground)Organic material (tò ground) | mm | ≥216≥240 |
| 15 | Interphase and phase to ground cleardistance (air insulation) | mm | ≥125 | |
| 16 | Loss of continuity of operation category | LSC2 | ||
| 17 | Minimum clear distance of SMC baffle plate(if any) to live conductor | mm | ≥30 | |
| 18 | Thickness of SMC baffle plate | mm | ≥5 | |
| 19 | Cooling mode | Self-cooling* | ||
| 20 | Allowable duration of internal arc | S | 1 | |
KYN28A-12
High voltage Switchgear case
Structure characteristics
The structure of grounding interlock is simpler, the action is more flexible and reliable, and the interlocking function can be switched freely regardless of whether it is equipped with a grounding switch operated manually or electrically, without changing any parts.
A set of interlocking device is used to realize the interlock between the rear upper and lower doors, so as to ensure that the rear door cannot be opened when the rear lower door is not opened; On the contrary, the rear lower door cannot be closed when the rear door is not closed.
The side plate adopts internal folding double bending technology, the skeleton is connected with nested steel nails, and there are no protruding screws and abdication
holes on the side, which can realize single replacement after failure and shorten the time for restoring power supply.
KYN28A-12
High voltage Switchgear case
Structure characteristics
The valve mechanism adopts an integrated base, which has higher stability.
The valve guide rail adopts aluminum alloy guide rail, which has higher matching accuracy, makes the valve slide more flexible, and increases the air distance between the valve guide rail and the handcart, which improves the overall safety of the valve mechanism.
The secondary line is laid in the secondary line groove with full metal protection, which can effectively protect the burning of the secondary line by the arc when the cabinet is in trouble, and the signal can be accurately transmitted to the comprehensive protection control system through the secondary line, so that the fault can be quickly removed, the damage degree of the fault to the electrical equipment can be reduced, and the stability of the power system can be improved.
The instrument door is equipped with self-leading device to prevent drooping, opening limit device and adjustable wire binding frame. The instrument box is equipped with flippable terminal mounting beam to facilitate secondary wiring.
HXGN15-12
High voltage Switchgear case
Description
HXGN15A-12(F·R) box-type fixed AC metal enclosed ring network switchgear is a new type of switchgear designed for the transformation and construction of urban power grids. The ring network cabinet is equipped with vacuum load switch and spring operating mechanism, which can be operated either manually or electrically. The grounding switch and isolating switch are equipped with manual operating mechanism.The ring network cabinet has strong complete set, small volume, no combustion and explosion danger, and has reliable five-defense functions.
Characteristics
The ring network cabinet is assembled with 8MF profile, and the modulus hole E = 20mm is installed on the whole frame. FZN21-12D type load switch or FZRN21-12D type fuse combination electrical appliance is equipped in the ring network cabinet. This type of electrical appliance has disconnecting switch, vacuum load switch, grounding half-opening, and both disconnecting switch and grounding switch have obvious fracture. Isolation switch, vacuum load switch, grounding switch and cabinet door have perfect and reliable mechanical linkage and interlocking devices, which can effectively prevent misoperation and ensure safe maintenance.
It can be operated manually and electrically.
The door of the measuring cabinet and the instrument door are provided with lead sealing pins.
| No. | Name | Unit | Parameter |
| 1 | Rated voltage | kV | 12 |
| 2 | Load switchgearRated currentCombined electrical cabinet | 630125 | |
| 3 | Rated short-circuit breaking current | kA | 31.5 |
| 4 | Rated active load breaking current | A | 630 |
| 5 | Rated short-time withstand current | kA | 20 |
| 6 | Rated peak value withstand current | kA | 50 |
| 7 | Rated power frequency withstand voltageBetween phase, to ground/fracture | kV | 42/48 |
| 8 | Lightning impulse withstand voltageBetween phase, to ground/fracture | kV | 75/85 |
| 9 | Mechanical life | cycles | 10000 |
| 10 | Rated handover current | A | 3150 |
| 11 | Operation mode | Manual or motor type | |
| 12 | Protection grade | IP2X |
HXGN15-12
High voltage Switchgear case
| No. | Name | Unit | Load switch unit | Combinedelectrical unit | Circuit breakerunit | ||||||
| 1 | Rated voltage | kV | 12 | 12 | 12 | ||||||
| 2 | Rated frequency | Hz | 50 | 50 | 50 | ||||||
| 3 | Rated current | A | 630 | 125 (dependson the fusecurrent) | 630 | ||||||
| 1min power | Between phase, to ground | 42 | 42 | 42 | |||||||
| frequencywithstand | Fracture | 48 | 48 | 48 | |||||||
| 4 | |||||||||||
| insula | |||||||||||
| insulation | voltage | Control and auxiliary circuit | kV | 2 | 2 | 2 | |||||
| level | Lightningimpulse | Between phase, to ground | 75 | 75 | 75 | ||||||
| withstandvoltage | Fracture | 85 | 85 | 85 | |||||||
| 5 | Rated short-time withstand current | kA/s | 20、25/4 | 20、25/4 | |||||||
| 6 | Rated peak value withstand current | kA | 50、63 | 50、63 | |||||||
| 7 | Rated short-circuit closing current | kA | 50.63 | Limited to theHV fuse | 50.63 | ||||||
| 8 | Rated short-circuit breaking current | kA | Limited to theHV fuse | 20.25 | |||||||
| 9 | Rated transfer current | A | 1700 | ||||||||
| 10 | Rated active load breaking current | A | 630 | ||||||||
| 11 | Rated closed loop breaking current | A | 630 | 630 | |||||||
| 12 | Mechanical | Load switch/circuit breaker | cycles | 10000 | 10000 | 20000 | |||||
| life | Disconnector/grounding switch | 3000 | 3000 | 3000 | |||||||
| 13 | Circuit resistance | μΩ | ≤150 | ≤150 | |||||||
| 14 | Rated inflation pressure (gauge pressure at 20°C) | Mpa | 0.04 | 0.04 | 0.04 | ||||||
| 15 | Gas annual relative leakage rate | Year | ≤0.01% | ≤0.01% | ≤0.01% | ||||||
| 16 | Protection | Cabinet body | IP4X | IP4X | IP4X | ||||||
| grade | Gas box | IP67 | IP67 | IP67 | |||||||
| 17 | Burning arc test | kA/s | 25/0.5 | 25/0.5 | 25/0.5 | ||||||
| Compartment (IP code) | 1 | IP2XC | |||||||||
| 18 | Gas box (IP code) | 1 | IP67 | ||||||||
| Cabinet body (IP code) | 1 | IP41 | |||||||||
| Cabinet body (IK code) | 1 | IP10 | |||||||||
| 19 | Insulation gas | 1 | Sf6 | ||||||||
GGD
| PEOPLE | 低压柜 GGD |
Description
This product is suitable for power generation and supply systems with three-phase AC frequency of 50- 60Hz, rated working voltage of 400V (690V) and below, and rated current of 6300A and below. It is used as centralized control and capacitance compensation in power, distribution and motors. Widely used in power plants, petroleum, chemical industry, metallurgy, textile, high-rise buildings and other places, this product complies with GB/T7251.1, GB/T7251.12, GB/T20641 and other standards.
| No. | Name | Unit | Parameter | |
| 1 | Rated voltage | ACDC | ≤1000 | |
| ≤1500 | ||||
| 2 | Rated insulation voltage | V | 690/1000 | |
| 3 | Rated frequency | Hz | 50-60 | |
| 4 | Rated withstand impulse voltage | kV | 8 | |
| 5 | Over-voltage grade | grade | Ⅲ | |
| 6 | Rated current | A | ≤6300 | |
| 7 | Rated withstand current | KA | 100 | |
| 8 | Rated peak value withstand current | KA | 220 | |
| 9 | Rated short-time withstand current | KA | 100 | |
| 10 | Protection grade CaseAnti-collision level Case | IP | IP3X | |
| IK | lk10 | |||
| 11 | Internal compartment form | NONE | NONE | |
| 12 | Type material modulus | mm | 20/25 | |
| 13 | Incoming mode | Upper busLower cableSide bus | ||
| 14 | Outgoing mode | Rear upper cableRear lower cable | ||
MNS、GCK、GCS
Description
This product is suitable for power generation and power supply systems with a three-phase AC frequency of 50-60Hz, a rated working voltage of 400V (690V) and below, and rated current of 6300A and below. It is widely used in power plants, petroleum, chemical industry, metallurgy, textiles, high-rise buildings and other places, this product complies with GB/T7251.12, GB/T20641, GB/T24274, JB/T10323, JB/T10263 standards.
| No. | Name | Unit | Parameter | |
| 1 | Rated voltage ACDC | ≤1000≤1500 | ||
| 2 | Rated insulation voltage | V | 690/1000 | |
| 3 | Rated frequency | Hz | 50-60 | |
| 4 | Rated withstand impulse voltage | kV | 8 | |
| 5 | Over-voltage grade | grade | Ⅲ | |
| 6 | Rated current | A | ≤6300 | |
| 7 | Rated withstand current | KA | 100 | |
| 8 | Rated peak value withstand current | KA | 220 | |
| 9 | Rated short-time withstand current (1s) | kA | 100 | |
| 10 | Distribution busbar | Standard type | kA | 105 |
| 11 | Peak value current | Improved type | kA | 176 |
| 12 | Protection grade | Case | IP | IP4X |
| Internal | IP | IP2X | ||
| 13 | Anti-collision level Case | IK | lk10 | |
| 14 | Internal compartment form | 3a/3b/4b | ||
| 15 | Drawer interlock mechanism | BPT dialing handle type three-station mechanismXJG-3 Hand Crank Mechanism for Door OpeningDJG-5 hand crank mechanismMLS-3/4 Size interlock MechanismJL-1/2 Hand pull mechanismJL-8 hand crank mechanism | ||
| 16 | Incoming mode | Upper busLower cableSide bus | ||
| 17 | Outgoing mode | Rear upper cableRear lower cable | ||
MNS、GCK、GCS Low voltage case
Structure characteristics
MNS、GCK、GCS Low voltage case
Structure characteristics
Double bending, steel rivet riveting, installation and positioning bayonet, primary plug-in for millions of trouble-free operation records, T-hole in the bottom plate of the drawer, which enhances the flexibility of the installation of components, the back plate of the drawer adopts rear bending, which increases the electrical gap of the leading busbar, and the interior of the drawer is equipped with secondary wire binding holes to ensure the rationality and consistency of the wiring.
Hand crank motor operation mechanism
Product characteristics
The XL-21 power distribution box is divided into two types. The box height of 1700mm and 1800mm is the ordinary type (P), which can be installed independently, and the entry and exit holes can be opened according to the requirements. The box height of 1900mm and above is the bus type with top (M type). The top of the box is equipped with a detachable cover plate, which is convenient for the installation and disassembly of the bus.
The frame of the box body is made of section steel, the door plate, side and rear sealing plate are all detachable, the installation plate and side depth can be adjusted, the installation and maintenance are flexible, convenient, the structure is tight, and the versatility is good.
Adopting precision casting adjustable door, the door opening is more than 135 ", the mounting bracket in the box body can be adjusted as a whole after the components are installed. It can be installed and inlet and outlet lines according to different use environments. It has strong versatility and can be used in combination with multiple sets.
Technical parameter
| No. | Name | Unit | Parameter |
| 1 | Rated working voltage | V | 380 |
| 2 | Rated insulation voltage | V | 690 |
| 3 | Rated working current of horizontal bus | A | ≤2000 |
| 4 | Rated short-time withstand current effectivevalue/peak value | IS/kA | 30/63 |
| 5 | Protection grade of the case | IP30 | |
| 6 | Overall dimensions(W×D×H) | mm | 400-1000x600-1000x1400-2200 |
Description
JXF distribution box is made of electrolytic steel plate bending and welding, and its surface is treated by epoxy tree gallbladder electrostatic spraying, which is beautiful and durable. According to its purpose, the distribution box is divided into lighting distribution box, power control box, metering box and other types, and according to its structure, it is divided into indoor wall-mounted control box and outdoor protective box. The outdoor protective box is divided into metal door and perspective door. General-purpose distribution boxes are flexible and diverse in style, and can be installed into control systems with different electrical performances as needed, such as lighting distribution boxes, power control boxes, metering boxes, air conditioning control boxes, water pump control boxes, fire control boxes, etc.
| No. | Name | Unit | Parameter |
| 1 | Rated working voltage | V | 380、220 |
| 2 | Rated insulation voltage | V | 450 |
| 3 | Rated working current of horizontal busbar | A | 630 |
| 4 | Breaking capacity | kA | 10 |
| 5 | Rated frequency | Hz | 50 |
| 6 | Protection grade of case | IP30 |
| Model No. | Code | External dimension | ||
| A | B | C | ||
| XXC1-301S | One-position three-phase meter box | 400 | 300 | 170 |
| XXC1-301S(T) | One-position three-phase meter box with transformer | 650 | 350 | 170 |
| XXC1-302S | Two-position three-phase meter box | 400 | 450 | 170 |
| XXC1-302S(T) | Two-position three-phase meter box with transformer | 650 | 550 | 170 |
| XXC1-301DIS(T) | One-position single-phase and one-position three-phasemeter box (CT) | 650 | 450 | 170 |
| XXC1-311S(T) | Type 100 meter box | 650 | 550 | 170 |
| XXC1-311DIS(T) | Type 100 one-position single-phase three-phase meter box | 650 | 650 | 170 |
| XXC1-321S(T) | Type 250 meter box | 650 | 600 | 170 |
| XXC1-321DIS(T) | Type 250 one-position single-phase three-phase meter box | 650 | 700 | 170 |
| XXC1-361S(T) | Type 600 meter box | 1000 | 700 | 250 |
| XXC1-361DIS(T) | Type 600 one-position single-phase three-phase meter box | 1000 | 850 | 250 |
COMPREHENSIVE PROTECTION DEVICE
PS-2000
Comprehensive automation system of microcomputer substation
Description
PS-2000 microcomputer substation integrated automation system is a new generation of microcomputer protection measurement and control device integrated automation system, which is launched by People Electric Shanghai Company to meet the latest requirements of substation integrated automation system, and developed by applying the latest and most advanced DSP technology at home and abroad. This system is suitable for substations, terminal stations and rural network systems below 110KV, and highlights the long-term reliable operation problems of microcomputer protection and monitoring system in harsh environments (such as low temperature, high temperature, strong electromagnetic field interference, high altitude, many lightning, etc.), and the conventional control, measurement and signal compatibility.
The PS-2000 system has formed a series of products as follows
1. Auxiliary protection
PS-2661 standby automatic switching protection measurement and control device Conventional type: incoming line, bus connector
PS-2662 standby automatic switching protection measurement and control device self-restoration type: incoming line, bus connection
PS-2663 busbar PT protection measurement and control device single busbar PT
PS-2664 Busbar PT Protection Measurement and Control Device Double Busbar PT Parallel PS-2665 Communication Management Master Control Device
2. Load protection
PS-2671 Line Protection Measurement and Control Device
PS-2672 bus coupling protection measurement and control device
PS-2673 Transformer Outlet Protection Measurement and Control Device
PS-2674 Capacitor Protection Measurement and Control Device
PS-2675 Motor Protection Measurement and Control Device
3. Backup protection
PS-2681 Transformer High Backup Protection Measurement and Control Device
PS-2682 Transformer Low Backup Protection Measurement and Control Device
PS-2683 Three-turn Variable Backup Protection Measurement and Control Device
PS-2684 main transformer backup protection operation device
PS-2685 main transformer non-electric power protection device
PS-2686 Generator Backup Protection Measurement and Control Device
PS-2687 Generator Grounding Protection Measurement and Control Device
PS-2000
Comprehensive automation system of microcomputer substation
4. Differential protection
PS-2691 Two-turn Variable Differential Protection Measurement and Control Device Without Control Loop
PS-2692 Two-turn Variable Differential Protection Measurement and Control Device with Control Loop
PS-2693 Three-turn Variable Differential Protection Measurement and Control Device
PS-2694 Motor Differential Protection Measurement and Control Device
PS-2695 Generator Differential Protection Measurement and Control Device
System characteristics
Chinese character display:
The device uses large-screen liquid crystal to directly display the required electrical quantities such as current, voltage, power, etc., and displays all kinds of information of protection actions on the screen, and records the action time and size of the recorder.
1. Easy to operate:
The protection on-off, setting value, data query, on-in signal detection, on-out test, etc. of the protection device can be directly operated on the panel of the protection device, which greatly improves the convenience of operation.
2. The instructions are obvious:
The protection device has seven photon rows under the large LCD screen, which can respectively display the working status, power supply status, monitoring status of self-test components and position monitoring of circuit breakers of the protection device.
3. Confidentiality function:
The device has a strong confidentiality function, and it is necessary to enter a password when changing the data content of the device, such as protection, switching and returning, setting the value, opening test, background communication address, etc., which greatly improves the safety of operation and operation.
4. Sampling display:
The bus voltage, measured current collected by the protection device and the calculated line voltage, active power, reactive power, power factor, frequency and other electrical quantities are all concentrated on the LCD screen and automatically displayed.
5. Sampling performance:
Each voltage loop, each protection current loop and measurement current loop are independent loops, which have good anti-saturation and anti-interference, and ensure the sampling accuracy.
6. Export independence:
Remote control opening and closing, protection trip, reclosing, accident signal, warning signal and special signal outlet all use one channel independently, which is convenient for the input and exit of protection and ensures the safety of operation.
COMPREHENSIVE PROTECTION DEVICE
PS-2000
Comprehensive automation system of microcomputer substation
7. Event records:
It can record more than 60 pieces of latest information. The displacement of the circuit breaker, displacement time, and the type, time and action value of protection actions will be recorded. At the same time, it has a poweroff holding function, and the event records in the menu can be queried.
8. Self-protection function:
The device has the protection function of circuit breaker trip-closing coil to avoid burning the circuit breaker coil due to mechanical refusal. Each circuit breaker corresponds to an operating circuit, and the switch can be directly operated in case of emergency.
9. Anti-interference performance:
The devices all adopt closed chassis with double-layer shielding inside, which effectively resists the interference of external electromagnetic waves to the internal components of the devices.
10. Seismic performance:
All the boards of the protection device are connected to the chassis in the form of plug-ins, and are fixed by multiple screws, which have very strong fixability, thus avoiding the phenomenon of loosening and falling off of the product during long-distance and bad road conditions.
11. Strong automation:
The protection device has powerful functions. It takes the perfect microcomputer protection system program as the core, reliable self-test system and hardware equipment, and powerful "four remote" functions. It replaces the protection mode of conventional relays. All data analysis and processing completely realizes the unattended mode of substation.
12. Easy to design:
According to the on-site situation, different installation modes can be selected, that is, screen installation or scattered installation on each switch cabinet.
13. Various communications:
The protection device has two independent 485 interfaces, which can expand the number of background operation stations and easily realize dual-machine hot standby. It is also equipped with a local area network LAN port to form a local area network, providing hardware support for providing various background configurations.
14. Overall performance:
On the perfect software and hardware platform, the protection device has passed the detection of relevant national authoritative organizations, which well meets the quick action, accuracy and reliability of relay protection. Note: Our company also produces RPS-5000 series protection. This protection is a product of the upgraded platform of RPS-2000. In terms of functions, it not only has full-function protection, but also can be modified to meet the needs of field applications, which is convenient and flexible; The measurement and control accuracy level is required to be higher; Hardware has been comprehensive upgraded, adoption all import chip component reaction speed, accelerated, precision, reaktion, precision, high precision, adoption.
PS-2000
Background monitoring system
System introduction
PS-2000 local monitoring system is a comprehensive automation background monitoring system for substations based on current computers. It adopts international standards and is a multi-window and multi-task system. It runs in Chinese WINDOWSNT or WINDOWS98 or above operating system environment. It has stable operation, high reliability, and is easy to operate. Easy to learn.
General Hardware Configuration Requirements of PS-2000 Background Monitoring System
Selection of display (color plane right angle):
1. In a 10KV/6KV substation, when the number of protection measurement and control devices is less than 15, a 19-inch display can be selected.
2. When there are a large number of protection units in substations above 35KV and substations below
10KV, at least 21-inch monitors should be selected.
3. In addition to the models specified by the design institute, our company will follow the conventional Dell complete machine configuration.
Monitoring host selection:
1. The hard disk is above 320G;
2. The memory is not less than 1G;
3. The main frequency is not less than 3.2 G;
4. Sound card, network card, graphics card, optical drive, floppy drive, keyboard, mouse and other accessories.
Alarm speaker: adopts Edifier series;
Uninterruptible power supply: backup type and online type; Neither can be lower than 1KVA; 1 h; Printer: HP A4
Communication line: shielded twisted pair.
System performance
Because of the high-performance and high-reliability industrial control machine, the average trouble-free running time is more than 20,000 to 50,000 hours, the modular design of software and the flexible configuration of real-time database greatly improve the reliability of the system.
In addition, the system has good compatibility and reliability, WindowsNt or Windows98 or above running environment, open software working platform, and easy to upgrade and expand.
VACUUM CIRCUIT BREAKER
ZN73-12(VS1)
Indoor type high voltage AC Vacuum circuit breaker
Description
ZN73-12 Series Indoor type high voltage AC vacuum circuit breaker is the indoor equipment with three phase AC50Hz, rated voltage 12KV, it is applicable for switching various different kinds of load and the places with frequent operation, as the use of electrical equipment's protection and control for the industrial mining, enterprise, power plant equipment and substation.
Using environment
1. Ambient temperature: * 1 0 ^ { \circ } C ~ + 4 0 ^ { \circ } C ;
2. Altitude: does not exceed 1000m;
3. Humidity: relative humidity: daily average value does not exceed 95%, monthly average value does not exceed 90%, saturated vapor pressure: daily average does not exceed 2.2× 10-3MPa, monthly average does not exceed1.8×10-3MPa.
4. Earthquake intensity: does not exceed 8 degree
5. The surrounding air should not be corrosive or combustible gas, steam and other obvious pollution.
6. There is no regular violent vibration in the use place.
Remark: if the not the same with the above using condition, can be customized
ZN73-12(VS1)
Indoor type high voltage AC Vacuum circuit bre
| Table 1 | ||||||
| Rated voltage kV | 12 | |||||
| Rated frequency Hz | 50 | |||||
| Rated insulationlevel | 1min Power frequency withstandvoltageInterphase、 phase to ground/fracture kV | 42/48(Effective value) | ||||
| Lightning impulse withstand voltageInterphase、phase to ground/fracture kV | 75/85(Peak value) | |||||
| Rated operation sequency | O-t-CO-t'-CO* | |||||
| Main circuit resistance mΩ | ≤50 | |||||
| Mechanical life cycles | 10000 | |||||
| Model No. | Rated currentA | Rated short-circuit breakingcurrent kA | Rated short-circuitclosing current (peak)kA | Rated short-circuitcontinuous time (s) | Rated short-circuitbreaking currentbreaking time | |
| ZN73-12/630-20 | 630 | 20/25 | 50/63 | 50 | ||
| ZN73-12/1250-20 | 1250 | |||||
| ZN73-12/1250-31.5 | 1250 | 80 | 4 | 50 | ||
| ZN73-12/1600-31.5 | 1600 | 31.5 | ||||
| ZN73-12/2000-31.5 | 2000 | |||||
| ZN73-12/2500-31.5 | 2500 | |||||
| ZN73-12/1250-40 | 1250 | 50 | ||||
| ZN73-12/1600-40 | 1600 | |||||
| ZN73-12/2000-40 | 2000 | 40 | 100 | |||
| ZN73-12/2500-40 | 2500 | |||||
| ZN73-12/3150-40 | 3150 | |||||
ZN73-12(VS1)
Indoor type high voltage AC Vacuum circuit breaker
Table 2
| Unit | Parameter | ||||
| Contact's opening distance | mm | 11±1 | |||
| Contact's overstroke | mm | 3.5±0.5 | |||
| Three phase opening and closing synchronization | ≤2 | ||||
| Contact closing tripping time | ≤2 | ||||
| Opening time | ms | ≤50 | |||
| Closing time | ≤100 | ||||
| Average opening speed | 0.9~1.3 | ||||
| Average closing speed | 0.4~0.8 | ||||
| Closing contact's contact pressure | N | 20kA | 25kA | 31.5kA | 40kA |
| 2000±2002 | 2400±2003 | 100±2004 | 750±250 | ||
| Accumulated allowable wear thickness for the moving andfixing contact | mm | 3 | |||
ZN73-12(VS1)
Indoor type high voltage AC Vacuum circuit bre
Table 3
| Power supply for the operation | AC/DC | |
| Rated voltage | 220V/110V | |
| Opening tripping | 264W | |
| Rated power | Closing tripping | 264W |
| Energy storage motor | 40kA | |
| 70W 100W | ||
| Normal workingvoltage range | Opening tripping | 65%~120% of rated voltage |
| Closing tripping | 85%~110% of rated voltage | |
| Energy storage motor | 85%~110% of rated voltage | |
| Energy storage time | ≤10s | |
Overall and installation dimensions
ZW32-12
Outdoor type High voltage AC Vacuum circuit breaker
Description
ZW32-12 Outdoor high voltage vacuum circuit breaker is the outdoor high voltage switch equipment with three phase AC50Hz, Rated voltage of 12kV, it is suitable for breaking and closing the load current, overload current and shirt-circuit current of the urban or rural power distribution system.
Main technical parameter
| Unit | ZW32-12/630-20 | ZW32-12/630-25 | ||
| Rated voltage | kV | 12 | ||
| Rated current | A | 6301250 | ||
| Rated short-circuit breaking current | 20 | 25 | ||
| Rated short-circuit closing current(peak) | 50 | 63 | ||
| Rated peak withstand current | 50 | 63 | ||
| Rated short-time withstand current | 20 | 25 | ||
| Rated short-circuit continuous time | S | 4 | ||
| Rated insulation | Lightning impulsewithstand voltage (peak) | kV | Interphase, to ground 75, fracture85 | |
| level | 1min power frequencywithstand voltage | Interphase, to ground 42, fracture48 | ||
| Rated operation sequency | O-0.3s-CO-180s-CO(Electric operation) | |||
| Rated short-circuit current breaking time | Cycles | 30 | ||
| Electrical life | 10000 | |||
| Rated operating voltage(Opening and closing coil) | V | DC220,110,AC220 | ||
| Moving and fixing contacts allowableaccumulated thickness | mm | 3 | ||
| Rated current of over-current tripping | A | 5 | ||
| Current ration of current transformer (regular) | 200/5 400/5 630/5 | |||
Outdoor type High voltage AC Vacuum circuit breaker
| Unit | ZW32-12/630-20 | |||
| Contact opening distance | mm | 9±1 | ||
| Contact overstroke | 2.015 | |||
| Average opening speed | m/s | 1.2±0.2 | ||
| Average closing speed | 0.6±0.2 | |||
| Opening time | 15~50 | |||
| Closing time | 25~80 | |||
| Closing tripping time | ms | ≤2 | ||
| Three phase opening and closingsynchronism | ≤2 | |||
| Each phase circuit DC resistance | mΩ | ≤80 | ||
| Energy storagemotor | Rated voltage | V | DC/AC 220 | |
| Rated power | W | 70 | ||
| Energy storage time | S | |||
| Weight | kg | 100 | ||
ZW32-12
Outdoor type High voltage AC Vacuum circuit breaker
Indoor High Voltage Vacuum circuit breaker
Description
ZN73S-24 Indoor high voltage vacuum circuit breaker is suitable for the indoor distribution equipment of 24kv, three phase AC50Hz, it is mainly used to break and close the load current, over current and shortcircuit current in the circuit, plays a control and protection role, and it's the main switch components of medium central switchgear. It is used for protection and control in power distribution systems of substations,
enterprises and industrial and mining enterprises. It is suitable for rural power grids and places with frequent operations, especially for the needs of urban and agricultural network transformation.
Main function characteristics
●The circuit breaker adopts copper-chromium contact material and a cup-shaped longitudinal magnetic field contact structure. The electrical wear rate of the contacts is small, the dielectric insulation strength is stable, the recovery after arc is rapid, the cut-off level is low, the breaking ability is strong, and the electrical life is long.
●The operating mechanism is a spring energy storage mechanism arranged in a plane, which has manual energy storage and electric energy storage functions to make the operating performance of the circuit breaker more reliable.
Model No.
| No. | Name | Unit | Parameter | ||
| 1 | Rated voltage | kV | 24 | ||
| 2 | Rated frequency | Hz | 50 | ||
| 3 | Rated current | A | 630 | 1250 | 1600,2000,2500 |
| 4 | Rated short-circuit breaking current | kA | 20 | 25 | 31.5 |
| 5 | Rated peak withstand current | kA | 50 | 63 | 80 |
| 6 | Rated short time withstand current | kA | 20 | 25 | 31.5 |
| 7 | Rated short-circuit closing current | kA | 50 | 63 | 80 |
| 8 | Rated operation sequence | O-0.3s-CO-180s-CO | |||
| 9 | Mechanical life | Cycles | 10000 | ||
VACUUM CIRCUIT BREAKER
ZN73S-24
Indoor High Voltage Vacuum circuit breaker
| No. | Name | Unit | Parameter | |
| 10 | Rated number of short circuit breaks | cycles | 20 | |
| 11 | Power frequency withstand voltage 1min | Interphase,ground/break | kV | 65/79 |
| 12 | Lightning shock withstand voltage | Interphase,ground/break | kV | 125/145 |
| 13 | Allowable wear thickness of moving and fixed contacts | mm | 3 | |
| 14 | Contact opening distance | mm | 14±1 | |
| 15 | Contacts stroke | mm | 4±1 | |
| 16 | Average opening speed (6mm just after opening) | m/s | 1.3±0.2 | |
| 17 | Average closing speed (6mm just before closing) | m/s | 1.0±0.2 | |
| 18 | Contact closing bounce time | ms | ≤2 | |
| 19 | Three-phase opening and closing synchronicity | ms | ≤2 | |
| 20 | Main loop resistance (without touch arm) | μΩ | ≤45 | |
| 21 | Closing time | ms | 35-70 | |
| 22 | Opening time | ms | 20-50 | |
| 23 | Interphase center distance | mm | 210±0.5,275±0.5 | |
ZW32-40.5
Outdoor High voltage AC Vacuum circuit breaker
Description
ZW32-40.5 F type intelligent vacuum circuit breaker is composed of an electric spring mechanism and a high-reliability intelligent controller. The device is mainly used in medium-voltage overhead line power grids as a dividing and combining load current, overload current, and short-circuit current, and has 0\~3 automatic maximum closing
• Extremely high reliability
• Completely maintenance-free throughout its life
• Has high mechanical life and electrical life
• The whole body is small in size, light in weight, and easy to install
• With standard relay protection and fast automatic reclosing function
Use environmental conditions
1. Ambient air temperature: -30°C\~+60°C;
2. Altitude: no more than 2000 meters;
3. The wind speed does not exceed 34m/s;
4. Vibration or ground movement from outside the switchgear and control equipment is negligible;
5. Pollution level: Level IV;
6. Storage temperature -40°C\~+85C.
Main technical parameter
Table 1
| No. | Name | Unit | Parameter |
| 1 | Rated voltage | kV | 40.5 |
| 2 | Rated current | A | 1250/1600 |
| 3 | Rated frequency | Hz | 50 or 60 |
| 4 | Power frequency withstand voltage (wet)(dry) | kV | 80/95 |
| 5 | Lightning impulse withstand current (peak) | kV | 185 |
| 6 | Rated short-circuit breaking current | KA | 31.5 |
| 7 | Rated short-circuit closing current (peak) | kA | 80 |
| 8 | Rated peak withstand current | KA | 80 |
| 9 | 4s short-time withstand current | KA | 31.5 |
| 10 | Rated operation sequence | O-0.1S-CO-3s-CO-6s-CO-60s recovery | |
| 11 | Rated short-circuit current breaking cycles | cycles | 30 |
| 12 | Mechanical life | cycles | 20000 |
| 13 | Intelligent mechanism control voltage | V | Dc220 |
| 14 | Secondary circuit 1min power frequency withstand voltage | kV | 2 |
ZW32-40.5
Outdoor High voltage AC Vacuum circuit breaker
Main mechanical parameter of circuit breaker
Table 2
| No. | Item | Unit | Parameter |
| 1 | Contact opening distance | mm | 16±1 |
| 2 | Contact over-range | mm | 4±0.5 |
| 3 | Opening speed | m/s | 1.4~1.8 |
| 4 | Closing speed | m/s | 0.4~0.8 |
| 5 | Contacts closing bounce time | m/s | ≤5 |
| 6 | Interphase center distance | mm | 560±2 |
| 7 | Three-phase opening and closing synchronicity | ms | ≤2 |
| 8 | Each phase conductive circuit resistance | μΩ | <120 |
| 9 | Closing time | ms | 25~45 |
| 10 | Opening time | ms | 20~45 |
| 11 | Weight | kgs | 315 |
Structure and working principal of circuit breaker
ZW32-40.5 F type intelligent circuit breaker is mainly composed of integrated solid sealing pole column, current transformer, motor operating mechanism and box. This type of circuit breaker is designed for miniaturization. At the same time, it is equipped with manual opening and closing devices. The current transformer can be selected according to user needs.
The control of ZW32-40.5 F type intelligent vacuum circuit breaker is completed by the supporting intelligent control unit. The opening and closing operation can be realized locally, or it can be operated remotely from a distance through the communication interface. Other information about the circuit breaker can also be transmitted to the control center, and the communication channels can be selected from cable, optical fiber, GPRS/CDMA, GSM, etc.
The intelligent control unit is installed close to the circuit breaker and is connected to the circuit breaker through a control cable. The power supply of the intelligent control unit is divided into the main power supply, the main power supply is AC or DC 220V, which is obtained by the high-voltage line through PT: the backup power supply is provided by the battery (installed in the intelligent control unit box).When working normally, the main power supply charges the backup power supply: when the main power supply is lost, the backup power supply can still complete the control of the circuit breaker and other operations in the control unit. The backup power supply (at full load) can maintain the whole machine for not less than 48 hours of work.
The circuit breaker operating mechanism is equipped with a manual emergency opening handle, which is used for emergency opening operation in the event of a control system or power failure.
ZW32-40.5
Outdoor High voltage AC Vacuum circuit breaker
Working principle and process of circuit breaker
1. Arc extinguishing principle: ZW32-40.5 F type vacuum intelligent circuit breaker adopts a vacuum arc extinguishing chamber, which uses vacuum as the arc extinguishing and insulating medium, and has a very high degree of vacuum. When the moving and fixed contacts are electrically charged under the action of the operating mechanism, a vacuum arc will be generated between the contacts. At the same time, due to the special structure of the contacts, an appropriate longitudinal magnetic field will also be generated in the gap between the contacts, causing the vacuum arc to remain diffuse and the arc to be evenly distributed on the contact surface to burn and maintain a low isolation voltage. When the current naturally crosses zero, the remaining ions, electrons and metal vapor can be combined or condensed on the contact surface and the shield within the order of microseconds, and the dielectric insulation strength of the arc extinguishing chamber fracture is quickly restored, so that the arc is extinguished to achieve the purpose of breaking. Due to the use of longitudinal magnetic field to control the vacuum arc, the vacuum circuit breaker has a strong and stable ability to turn off the current.
2. Energy storage: ZW32-40.5 F type can store energy manually through the energy storage handle, or it can store energy motorized.
3. Closing operation: press the closing button on the intelligent controller locally, or remote control the closing operation from a distance, or use the opening and closing handle to close manually.
4. Opening operation: press the opening button on the intelligent controller locally, or remotely control the opening operation from a distance, or use the opening and closing handle to opening manually.
Installation dimension of circuit breaker (does not include the disconnector)
ZW32-40.5
Outdoor High voltage AC Vacuum circuit breaker
Outdoor High voltage AC Vacuum circuit breaker
ZW7-40.5
Description
ZW7-40.5 outdoor high-voltage AC vacuum circuit breaker has the advantages of safe and reliable performance, easy maintenance, and long maintenance cycle. Due to the use of a new type of insulating material, the outer side of the arc extinguisher and the inner wall of the porcelain sleeve are noncondensing. The overall structure of the transformer placed in the mechanism box facilitates installation. It also avoids the oil, gas leakage and toxicity problems of other switches. Since the moving and fixed contacts of the circuit breaker are sealed in a vacuum arc extinguishing chamber, and vacuum is used as the insulating medium and arc extinguishing medium, it has a series of advantages unmatched by other types of switches. Therefore, this product is an ideal product to replace the DW multi-oil circuit breaker. The structure type of the operating mechanism box of this product in the middle of the circuit breaker is a central-mounted high-voltage vacuum circuit breaker. The shape, length and size of this type of circuit breaker are 260mm smaller than the original circuit breaker, which is suitable for installation in places with smaller spatial locations.
This product is suitable for 40.5kV, 50Hz three-phase power distribution system, as a combination of load current, overload current and short-circuit current.
Model No.
Use environmental conditions
1. The upper limit of the ambient temperature is +40°C, the lower limit is -30°C (general areas), and -40°C (high and cold areas);
2. Altitude: no more than 1000m;
3. Wind pressure: no more than 700Pa (equivalent to wind speed 34/m/s) ;
4. The degree of air pollution: extreme III.
ZW7-40.5
Outdoor High voltage AC Vacuum circuit breaker
Table 1
| No. | Item | Unit | Parameter | ||
| 1 | Rated voltage | kV | 40.5 | ||
| 2 | Rated insulation | 1min power frequency withstand voltage Dry (effective value) Lightning Wet | kV kV | 95 80 | |
| level | Impulse withstand voltage (peak) | kV | 185 | ||
| 3 | Rated current | A | 1250/1600/2000/2500 | ||
| 4 | Rated short-circuit breaking current | kA | 20/25/31.5 | ||
| 5 | Rated operating sequence | O-0.3s-CO-180s-CO | |||
| 6 | Rated capacitor bank breaking current | A | 400 | ||
| 7 | Rated short-circuit breaking current breaking cycles | cycles | 20 | ||
| 8 | Rated short-circuit closing current (peak) | kA | 50/63/80 | ||
| 9 | Rated peak withstand current | kA | 50/63/80 | ||
| 10 | Rated short-term withstand current | kA | 20/25/31.5 | ||
| 11 | Rated short circuit continuous time | S | 4 | ||
| 12 | Full breaking time | S | ≤0.08 | ||
| 13 | Mechanical life | cycles | 10000 | ||
| 14 | Rated operating voltage and rated voltage of auxiliary circuit | V | AC, DC 220, 110 | ||
| No. | Item | Unit | Parameter |
| 1 | Contact opening distance | mm | 22±2 |
| 2 | Contact over-range | mm | 4±1 |
| 3 | Average opening speed | m/s | 1.5±0.2 |
| 4 | Average closing speed | m/s | 0.7±0.2 |
| 5 | Opening time | ms | ≤3 |
| 6 | Closing time | ms | ≤2 |
| 7 | Closing bounce time | ms | ≤150 |
| 8 | Three-phase opening and closing synchronicity | ms | ≤60 |
| 9 | DC resistance per phase circuit | mΩ | ≤100 |
ZW7-40.5
Outdoor High voltage AC Vacuum circuit breaker
Overall and installation dimensions
1. Overall dimension
2. Installation dimension
a. The installation size is shown in the figure
b. Installation fracture dimension diagram
HIGH VOLTAGE DISCONNECTOR
GN19-12
Indoor High Voltage AC Disconnector
Description
GN19-12 indoor high-voltage AC disconnector is suitable for AC 50Hz, rated voltage 12kV and the following power system, equipped with manpower operating mechanism, as in the case of voltage and no load, the use of opening and closing electrical equipments.
The performance of this product is in accordance with GB/T1985 “AC High Voltage Disconnector and Grounding Switches"standard.
| Model No. | Rated voltage (kV) | Rated current (A) | 4s rated short-time withstand current (rms) (kA) | Rated peak withstand current (kA) |
| GN19-12/S400-12.5 | 12 | 400 | 12.5 | 31.5 |
| GN19-12/S630-20 | 12 | 630 | 20 | 50 |
| GN19-12S1000-31.5 | 12 | 1000 | 31.5 | 80 |
| GN19-12/S1250-31.5 | 12 | 1250 | 31.5 | 80 |
| GN19-12C/S400-12.5 | 12 | 400 | 12.5 | 31.5 |
| GN19-12C/S630-20 | 12 | 630 | 20 | 50 |
| GN19-12C/S1000-31.5 | 12 | 1000 | 31.5 | 80 |
| GN19-12C/S1250-31.5 | 12 | 1250 | 31.5 | 80 |
GN19-12
Indoor High Voltage AC Disconnect Switches
Overall and installation dimensions
| Model No. | A | B | C |
| GN19-12/400 | 490 | 436 | 4-14×24 |
| GN19-12/630 | 490 | 436 | 4-14×24 |
| GN19-12/1000/1250 | 510 | 530 | 4-18×28 |
| GN19-12C/400 | 460 | 625 | 4-14×24 |
| GN19-12C/630 | 460 | 625 | 4-14×24 |
| GN19-12C/1000/1250 | 505 | 745 | 4-18×28 |
GN24-12D
Idoor High Voltage AC disconnector
Description
GN24-12D (I, II), GN24-12D (I, II) C series indoor high voltage disconnector are indoor devices with a rated voltage of 12kV and a three-phase AC of 50Hz. Structure:
a.GN24-12D (I1.2; II 1.2) Q-type disconnector is in the form of moving (or fixed) contact side grounding; the main knife and the grounding knife are combined on an overall frame; Type 1 is operated on the left; type 2 is operated on the right; Type Q is a product under full working conditions, and can be equipped with a live display device according to the user's order requirements. b.GN24-12SD I, II (C1.2.3) type disconnector are the grounding form on both sides of the moving or fixed contacts, and the moving (or fixed) contact side can be changed to a wall-through sleeve; (or both sides can be changed to a wall-through sleeve); The main knife and two sets of grounding knives are combined on the same frame, one set of grounding knives can be operated separately, or one mechanism can be used to operate at the same time.
Model No.
Normal using condition
1. Altitude: 1000m.
2. The ambient temperature
3. Relative humidity of the surrounding environment: the daily average value is not greater than 95%, and the monthly average value is not greater than 90%.
4. The earthquake intensity does not exceed 8 degrees.
5. There is no danger of fire, explosion, serious pollution, chemical corrosion and severe vibration.
GN24-12D
Idoor High Voltage AC disconnector
| ParameterSpecification | 400A 630A | 1000A | 1250A | Installation | ||||||||||
| A | B | C | D | A | B | C | D | A | B | C | D | hole size | ||
| GN24-12DI | 890 | 660 | 450 | 125 | 890 | 690 | 480 | 125 | 890 | 700 | 500 | 125 | ||
| GN24-12DII | 890 | 660 | 450 | 125 | 890 | 690 | 480 | 125 | 890 | 700 | 500 | 125 | 700×300 | |
| GN24-12DI | 890 | 660 | 450 | 240 | 890 | 690 | 480 | 350 | 890 | 700 | 500 | 350 | ||
| GN24-12DIIC | 890 | 660 | 450 | 240 | 890 | 690 | 480 | 350 | 890 | 700 | 500 | 350 | ||
| GN24-12DI | 920 | 780 | 450 | 125 | 920 | 790 | 480 | 125 | 920 | 790 | 500 | 125 | ||
| GN24-12DIIC | 920 | 780 | 450 | 240 | 920 | 790 | 480 | 350 | 920 | 790 | 500 | 350 | ||
HIGH VOLTAGE DISCONNECTOR
GW4-40.5
Outdoor High Voltage AC disconnector
Description
GW4-40.5 outdoor isolation switch is suitable for power systems with outdoor AC at 50Hz and rated voltage of 40.5 kV, respectively, for the line to be used as an opening and closing circuit when there is voltage and no load.
The products meet the requirements of GB/T 1985 and other related standards.
Main technical parameter
| Model No. | Rated voltage(kV) | Rated current(A) | Peak withstandcurrent (kA) | 4 seconds short-termwithstand current (kA) | |
| GW4-40.5GW4-40.5D | 40.5 | 400 | 50 | ||
| 20 | |||||
| 630 | 50 | 20 | |||
| 1000 | 63 | 25 | |||
| 1250 | 80 | 31.5 | |||
| 1600 | 80 | 31.5 | |||
Structural Characteristics
1.The disconnector consists of a base, an insulating pillar, a conductive part, and an operating mechanism. There are two pillars at each pole, and the upper end of each pillar is equipped with a conductive knife, and the contact of the knife on both sides is in the middle of the two pillars. The lower ends of the pillars are each equipped with bearing sleeves. Driven by the operating mechanism, the knife can be rotated horizontally by 90° to meet the requirements of opening and closing.
2.The disconnector is a unipolar type, and the three poles can also be connected into a three-pole type that can be linked by a connecting rod. Equipped with CS11 type or CS8-6D type manual mechanism operation. Among them, CS17 is used for disconnector with double grounding devices. (The motor mechanism can be equipped as needed).
3.The disconnector has a reasonable structure and flexible operation; it can be used as a single pole or as a three-pole, and it is easy to install; the opening distance of the contact knife is large, and the insulation is safe and reliable. It can also be ungrounded or equipped with single-sided grounding or double grounding according to user needs.
GW4-40.5