VL36-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In=63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In =63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
Generalintroduction
Function
VL37-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent ingrid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL37-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In=63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In =63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL38-63RCCB
Generalintroduction
Function
VL38-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL38-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In=63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
General introduction
Function
VL39-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL39-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In=63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In =63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL40-63RCCB
General introduction
Function
VL40-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL40-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL41-63RCCB
General introduction
Function
VL41-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL41-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL42-63RCCB
General introduction
Function
VL42-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL42-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VH12-125 Switch Disconnection
Generalintroduction
Function
VH12-125seriesswitchdisconnection (hereinafterreferredtoasswitch) appliestopowerdistributionandcontrol circuitswithAC5oHz,rated current upto125A,ratedvoltageup to 415V.It’smainlyusedasa general switch ofterminal combinedapparatus,also functionsascontrollerof un frequently switched small power apparatusand lighting.
Application
Industrialandminingenterprises,high-risebuildingsandresidentialhouses, etc.
Conformtostandard IEC/EN60947-3
| Types | Values |
| Ratedcurrent(le) | 32A,63A,80A,100A,125A |
| Poles | 1P、2P、3P、4P |
| Rated voltage(Ue) | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Ratedinsulationvoltage(Ui) | 400V |
| Rated working current (le) | 32A,63A,80A,100A,125A |
| Rated impulsewithstand voltageUimp | 4Kv(2000m) |
| Rated short timewithstand current(lcw) | 12le,1s |
| Ratedshortcircuitmakingcapacity(lcm) | 20le,0.1s |
| Ratedmakingand breakingcapacity | 3le,1.05Ue,cosΦ=0.65 |
| Mechanical and electrical life | Mechanicallife850oTimes |
| Electrical life300oTimes | |
| Connection wire | See Form1 |
| Operatedambient temperature℃ | -5~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Ratedcurrent In(A) | NominalsectionareaofcopperwireS(mm²) |
| 32 | 6 |
| 63 | 16 |
| 80 | 25 |
| 100 | 35 |
| 125 | 50 |
Overall and mounting sizes(mm)
General introduction
Conformstostandard EN/IEC60947-2
Main functions
Overload,shortcircuitand isolationprotection
Mainparameters
| Types | Values |
| Ratedcurrent (In) | 80A,100A,125A |
| Ratedvoltage(Ue) | 230V~(1P),400V~(2P,3P,4P) |
| Ramted insulation voltage (Ui) | 500V |
| Workfrequency | 50Hz |
| Typesofelectro-releases | li=8ln(Ctype),li=12In(Dtype) |
| Poles | 1P,2P,3P,4P |
| Mechanical life | 20000times |
| Electrical life | 4000timti(mie254) |
| Ratedultimateshortcircuit breakingcapacity(Icu) | 6000A |
| Ratedmakingshort-circuit breakingcapacity (Ics) | 6000A |
| Rated impulse withstand voltage | 4kV |
Overall and mounting sizes(mm)
| Size | 1P | 2P | 3P | 4P |
| L(mm) | 17.8 0.2 | 35.6 0.4 | 53.4 6 | 71.2 0.8 |
VB12-63/VB12-63Z/VB12-63SMCB
Generalintroduction
Function
VB12-63 series MCB,used as overload and short circuit protection,applies toacircuitofAC 50Hz,rated voltage230/40oV,rated currentup to 63A. Usually it functionsasun frequentlyswitching.Inaddition,it can be also usedasanisolatortocutoff the circuitformaintenanceof circuitand equipment.
Application
Industryandcommercial buildings,high-risebuildingsand residential houses,etc.
Conformstostandard IEC/EN60898-1
Form1
| Types | Values |
| Rated voltage Un | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Rated current In | 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Poles | 1P、2P、3P、4P |
| Instant tripping type | B,C,D |
| Ratedshort circuit breaking capacity(lcn) | 6000A(VB12-63) 4500A(VB12-63Z) 3000A(VB12-63S) |
| Overcurrent protection properties | See Form2,Diagram1,2and3 |
| Mechanicalandelectrical life | See Form3 |
| Connection wire | See Form4 |
| Tightening torque | 2.0N.m |
| Nominal temperature℃ | 30 |
| Operatedambienttemperature℃ | -5~+55 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overcurrentprotectionproperties(Nominal temperature30℃)
| Item | Type | Test curren | Initial status | Trippingor non tripping time limit | Expectedresult | Remarks |
| a | BCD | 1.13ln | Cold | t≤1h | Nontripping | |
| b | 1.45ln | Test following the previousprocedure; Processaftertest | t | Trip | Current increases tostipulated valuewithin 5s | |
| C | 2.55ln | Cold | 1s| Trip | | ||
| d | B C D | 3ln 5ln 10ln | Cold | (for In >32A) ts0.1s | Non tripping | Connection of current by opening auxiliaryswitch |
| e | B CD | 5ln 10n | Cold | t≤0.1s | Trip | Conectinoffcurentbypening |
Mechanicalandelectricallife
| Type | Time |
| Electrical life | 10000 |
| Mechanical life | 20000 |
Connectionwire
| RatedcurrentIn(A) | Copper wirenominal cross-sectional area S(mm²) |
| 1~6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40,50 | 10 |
| 63 | 16 |
Generalintroduction
Function
VB12-63H seriesMCB,used asoverloadand short circuit protection,applies toacircuitofAC 50Hz,ratedvoltage230/40oV,ratedcurrentupto63A. Usually it functions as un frequently switching.In addition,it can be also used asanisolatortocut offthecircuitformaintenanceofcircuitand equipment.
Application
Industryand commercial buildings,high-rise buildingsand residential houses, etc.
Conformstostandard IEC/EN60898-1
Form1
| Types | Values |
| Rated voltage Un | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Rated current In | 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Poles | 1P、2P、3P、4P |
| Instant tripping type | B,C,D |
| Rated short circuit breaking capacity(lcn) | 10000A |
| Overcurrent protection properties | See Form2,Diagram1,2and3 |
| Mechanical and electrical life | See Form3 |
| Connection wire | See Form4 |
| Tightening torque | 2.0N.m |
| Nominal temperature℃ | 30 |
| Operatedambient temperature℃ | -5~+55 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Form2
| Item | Type | Test curren | Initial status | Trippingor non trippingtime limit | Expectedresult | Remarks |
| a | BCD | 1.13ln | Cold | t≤1h | Nontripping | |
| b | 1.45ln | pret usloaigedue: Processaftertest | t | Trip | Current increases to stipulated valuewithin 5s | |
| C | 2.55ln | Cold | 1s | Trip | ||
| d | B C D | 3ln 5ln 10ln | Cold | ts0.1s | Non tripping | Connection of current by opening auxiliaryswitch |
| e | B CD | 5ln 10In | Cold | t≤0.1s | Trip | Conectonoffcurentbypening |
VB12-63HMCB
Mechanicalandelectrical life
| Type | Time |
| Electrical life | 10000 |
| Mechanical life | 20000 |
Connection wire
| Ratedcurrent In(A) | Copperwirenominal cross-sectional area S(mm²) |
| 1~6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40,50 | 10 |
| 63 | 16 |
VL18-63RCCB
Generalintroduction
Function
VL40-63seriesRCCB(withoutovercurrentprotection)appliestoAC50Hz,rated voltage240V2poles,415V4poles,ratedcurrentupto63A.Whenelectric shockoccurstohumanorleakagecurrentingridexceedsstipulatedvalues, RCCBcutsoff the fault powerinaveryshort time to protectthesafetyof humanandelectricalequipments.Itcanalso functionasnonfrequently switching of circuits.
Application
Industryand commercial buildings,high-rise buildingsand residential houses, etc.
Conformstostandard IEC/EN61008-1
VL18-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Rated limitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuitcurrentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VB10LE-32RCBO
Generalintroduction
Function
VB10LE-32 series RCBO mainlyapplies to thecircuitofAC 50Hz,rated voltage240V,ratedcurrentupto32A.Whenelectricshockoccurstohuman, leakagecurrent orvoltage in grid exceedsstipulated values,RCBOcuts offthefault power inaveryshort time toprotect thesafetyof humanand electrical equipments,italsoownsthe functionsof overloadandshortcircuit protection.Inaddition,itcanswitchonandoff non frequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lightingand distributionsystem for industryand commerce system.
Form2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,2A |
| Ratedresidual operatedcurrent(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non tripping current(l△no) | 0.51△n |
| DC component | AC type,A type |
| Poles | 1P+N |
| Instant tipping type | B type, C type |
| Rated short circuit breaking capacity(lcn) | 6000A |
| Rated residual making and breaking capacity(l△m) | 500A |
| Breaking timeofresidual operatedcurrent | See Form2and3 |
| Overcurrentprotectionproperties | SeeForm4,Diagram1and2 |
| Mechanicalandelectrical life | See Form5 |
| Connection wire | See Form 6 |
| Tightening torque | 1.5N.m |
| Nominal temperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Type | In(A) | 1△n(A) | ei | |||
| 1△n | ||||||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeofAtype
Overcurrent protection properties(nominal temperature 3 0 { { c } } )
| Type | In(A) | 1△n(A) | e | ||||
| 1.41△n | 350A | ||||||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
Form4
| Item | Type | Test curren | Initial status | Tripping or nontripping time limit Expected resul | Remarks | |
| a | B,C | 1.13ln | Cold | ts1h | Non tripping | |
| b | 1.45ln | Testfollowingthe previousprocedure; Processafter test | t | Trip | stipuren inauewitht s | |
| C | 2.55ln | Cold | 1 | Trip | ||
| d | BC | 3n | Cold | t≤0.1s | Non tripping | Connentionxfiauyrentchy |
| e | BC | 50n | Cold | t≤0.1s | Trip | Contionxif urentch |
Mechanicalandelectrical life
| Category | Time | OperationTime(time/hour) |
| Mechanical life | 10000 | 240 |
| Electricallife | 2000 | 120 |
Connectionwire
Form6
| RatedcurrentIn(A) | SectionareaofcopperwireS(mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
Overall and mounting sizes(mm)
VB12L-40RCBO(Magnetic type)
Generalintroduction
Function
VB12L-40 series RCBO mainlyapplies to thecircuit of AC 5 0 H z rated voltage240V,ratedcurrentupto40A.Whenelectricshockoccursto human,leakagecurrent orvoltage in grid exceedsstipulatedvalues,RCBO cutsoffthefault powerinaveryshorttimetoprotectthesafetyof human andelectrical equipments,italso owns the functions of overload and short circuit protection.Inaddition,itcanswitchonandoff non frequently the electrical facilitiesand lightingcircuitwhilethecircuit workswell.
Application
Lightingand distributionsystem for industryand commercesystem.
Conformsto
IEC/EN61009-1&61009-2-1
VB12L-40RCBO(Magnetic type)
Mainparameters
Form2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,32A,4A |
| Rated residual operatedcurrent(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non tripping current(I△no) | 0.5l△n |
| DCcomponent | AC type,Atype |
| Poles | 1P+N |
| Instant tipping type | B type,C type |
| Rated short circuit breaking capacity(lcn) | 6000A |
| Rated residual making and breaking capacity(l△m) | 500A |
| Breaking timeof residual operatedcurrent | See Form2and 3 |
| Overcurrentprotectionproperties | SeeForm4,Diagram1and2 |
| Mechanical and electrical life | See Form5 |
| Connection wire | See Form 6 |
| Tightening torque | 1.5N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Breaking timeof AC type
| Type | In(A) | 1△n(A) | Breaking time(s) whenl△equalstothebelowvalues | |||
| I△n | 21△n | 51△n | 0.25A,5A~200A,500A | |||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeofA type
Overcurrent protection properties(nominal temperature 3 0 ^ { \circ } { C } )
| Type | In(A) | 1△n(A) | Be | ||||
| 1.41△n | 350A | ||||||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
| Item | Type | Test curren | Initial status | Trippingornontrippingtime limit | Expectedresul | Remarks |
| a | B,C | 1.13ln | Cold Test following the | t≤1h | Nontripping | |
| b | 1.45ln | previousprocedure; | t | Trip | stipuren inareawthtn s | |
| C | 2.55ln | Cold | 132AA) | Trip | ||
| d | B C | 3ln 5ln | Cold | t≤0.1s | Non tripping | Connection of current by openingauxiliaryswitch |
| e | BC | 50n | Cold | t≤0.1s | Trip | Connection xfcurenth |
VB12L-40RCBO(Magnetic type)
Diagram1and 2
Mechanicalandelectrical life
| Category | Time | OperationTime(time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connection wire
| Ratedcurrent In(A) | Sectionarea of copper wireS(mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40 | 10 |
Overall and mounting sizes(mm)
VB10L-40RCBO
Generalintroduction
Function
VB10L-40 seriesRCBO mainlyappliesto thecircuit of AC 5 0 H z rated voltage240V,ratedcurrentupto40A.Whenelectricshockoccursto human, leakagecurrent orvoltage in gridexceedsstipulatedvalues,RCBOcuts offthefault power inaveryshort time toprotect thesafetyof humanand electrical equipments,italso owns the functionsof overload and shortcircuit protection.Inaddition,itcanswitchonandoff non frequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lightingand distributionsystem for industryand commerce system.
Form2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,32A,40A |
| Rated residual operatedcurrent(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non tripping current(I△no) | 0.5l△n |
| DCcomponent | AC type,Atype |
| Poles | 1P+N |
| Instant tipping type | B type,C type |
| Rated short circuit breaking capacity(lcn) | 6000A |
| Rated residual making and breaking capacity(l△m) | 500A |
| Breaking timeof residual operatedcurrent | See Form2and 3 |
| Overcurrentprotectionproperties | SeeForm4,Diagram1and2 |
| Mechanical and electrical life | See Form5 |
| Connection wire | See Form 6 |
| Tightening torque | 1.5N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Type | In(A) | 1△n(A) | Breaking time(s) whenl△equalstothebelowvalues | |||
| I△n | 21△n | 51△n | 0.25A,5A~200A,500A | |||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeofAtype
Overcurrent protection properties(nominal temperature 3 0 ^ { \circ } { C } )
| Type | In(A) | 1△n(A) | rei | ||||
| 1.41△n | 350A | ||||||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
Form 4
| Item | Type | Test curren | Initial status | Trippingornontrippingtime limit | Expectedresul | Remarks |
| a | B,C | 1.13ln | Cold Test following the | t≤1h | Non tripping | |
| b | 1.45ln | previousprocedure; | t | Trip | stipuren inarewthtn s | |
| C | 2.55ln | Cold | 1 | Trip | ||
| d | B C | 3ln 5ln | Cold | t≤0.1s | Non tripping | Connection of currentby openingauxiliaryswitch |
| e | BC | 50n | Cold | t≤0.1s | Trip | Connentianxifcurrenthy |
Mechanicalandelectrical life
| Category | Time | OperationTime(time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connection wire
| Ratedcurrent In(A) | Sectionareaof copperwireS(mm2) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40 | 10 |
Overall and mounting sizes(mm)
Generalintroduction
Function
VDF-63 isakind ofcircuitbreakerwith completeupdateof residual current detection,based oncurrent typeA RCCB.It can not only effectively protect ACandpulsingDC(Atype),thepossiblecompoundresidual current (Ftype),butalso smoothingDCand high frequencyresidual current(1K Hz).Inacircuitconsistingofrectifier,inverter,frequencyinverter,etc,the leakagecurrentcaused in DC loopcircuitcanbeeffectivelydetectedand protected.
Application
Industry,medical,EVcharger,elevatortc
Conformstostandard IEC/EN61008-1,IEC/EN62423
Detectionresidualcurrent type A C + A + smoothing DC + F + high frequency signal (1K Hz)
Mainparameters
| Types | Values |
| Ratedvoltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,25A,32A,40A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Type of residual current | Type B (AC+A+ smoothing DC+F+ high frequency signal 1K Hz) |
| RatedlimitedshortcircuitcurrentInc | 10000A |
| Rated limited residual short circuitcurrentI△c | 10000A |
| RatedmakingandbreakingcapacityIm | 1000A |
| Ratedresidualmakingandbreakingcapacityl△m | 1000A |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Electrical life | 2000 Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Tightening torque | 3N.m |
| Connection capacity | 16mm2 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
| Circuitdiagram | Loopcurrentof Normal loopcurrent earthing fault | Detectiontypeofresidualcurrent | ||||
| N | AC | A | B | |||
| PE Single phase | ||||||
| PE Phase control N | ||||||
| PE- Impulse control N | ||||||
| PE Single phase half-wave rectification N | ||||||
| Single phase full-wave rectification | ||||||
| PE Single phase half-wave rectification, | ||||||
| 华 N PE | ||||||
| PNE Single phase half-wave rectification, | IL | IF | ||||
| L5 N LI PE | L | IF www | ||||
| Threephase half-wave rectification LIL 本本 NF | IF | |||||
General info
Briefintroduction
AFDD(arc fault detectiondevice) isanew electrical anti-fire equipment. Itcouldavoidvariousoffirescausedbyshortcircuit,circuitaging,heavy load,poorcontact,fault electrical devices,etc.Automaticcontrol isrealized bybuilt-incomputerchip.Itsoperatingprinciple:thedetectedarc impulse is processed,compared and identified by electronic circuitand MCU.Once faultarc impulsewhich easilycreates firedetected,theoutputwill drive tripping unit tocut off the load powersupply,so that the fire is prevented.
Function
AFDDaimstodetect hazardousarc impulsewhicheasilycreatesfire(such asinsulationdecreasingbetween lines,loadshortcircuit,poor contact ofconnector,arc causedby house electrical apparatus fault).Thenit triggers trippingunit to cut off thepower supply to prevent electrical fire. AFDDisusedtogetherwith leakagecircuitbreaker,lowvoltagecircuit breaker(overcurrent protection)to buildamulti functionelectrical protective device.Asatrueintelligentlowvoltageelectricalapparatus,tcannotonly preventelectricalfire,electric shockto human,overloaddanger,etc,but alsobecustomizedwithdifferentfunctions.
Application
Asper IEC62606,thesedifferentratingsavailable:10A,16A,20A,32A,40A, 63A,usuallyused in residential housesasa terminal protectivedevice. Theapplicationsof AFDDarewide,in theory,itcan beused toavoid fire wherever there iselectricity,suchasinresidential house,officebuilding, hospital,shoppingmall,supermarket,fctory,vehicle(auto,train,vesel,ir plane),especially foranti-fireuse inresidential house.
Conform to
IEC61009-1IEC62606
Mainparameters
Ratedvoltage(Un):230V/50Hz;
Rated operating frequency:50/60Hz;
Max load current:10A、16A、20A、32A、40A、63A;
Min load current:3A;
Maxload power:4KVA(dependson loadcurrent);
AFDD-63
Main parameters
| Mainparameters | Values |
| Ratedvoltageoptions(Un) | AC:110V~230V~240V |
| Ratedcurrent(In) | 6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated current(l△n) | 0.03A |
| Rated residual non trippingcurrent(l△no) | 0.51△n |
| DCcomponent | AC type,A type |
| Poles | 2P |
| Instant tripping type | TypeC |
| Ratedshortcircuitbreakingcapacity(lcn) | 6000A |
| Ratedresidualmakingand breakingcapacity(l△m) | 500A(In≤50A),630A(In=63A) |
| Overcurrent protectionproperties | SeeForm5,Diagram1 |
| Mechanical and electrical life | SeeForm6 |
| Connection wire | See Form7 |
| Tighteningtorque | 2.0N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
Normal use conditions
Ambienttemperature - 5 { C } or + 4 0 { { C } } ,averagedailytemperature + 3 5 { { C } } Max.Altitudenotexceeding 2 0 0 0 \mathsf { m } ,relative humidity: 5 0 % Maxat 4 0 { { c } } ” 9 0 % at 2 0 { { c } } :
Characteristics
AFDD-63hstlongotectssaatdrentfudndoticitrppingactsicf esidual operatedcurrentshownasForm1.
Form2
| Type | In(A) | 1△n(A) | eaine | |||
| I△n | ||||||
| AFDD-63 | Any value | >0.03 | 0.3 | 0.15 | Maxbreaking time | |
| 0.03 | 0.3 | 0.15 | ||||
| 0.3 | 0.15 | 0.04 | ||||
TheprotectionunitsofFD63onsistsoftfllowigsarcfaultprotectiondetectiounitmodificatioofunitetectioandd atrippingsignalwhendistingishingthefacthtripperpushesthemechanicalstructuretotripthnthemaincontactoil beswitchedfroopeingositiotisconectiongpositionwichakesthfaultircuitisconectedndvodtlfie createdbyarcfault. Form2andform3showtheultimatelimitoftrippingjudgementofarcfaultandbreaking timeforratedvoltageof230V.
Limitvalue of tripping judgement of 63Aand below
| Testedarccurrent(effective value) | 3A | 6A | 13A | 20A | 40A | 63A |
| Maxbreaking time | 1s | 0.5s | 0.25s | 0.15s | 0.12s | 0.12s |
Limit value of tripping judgement of above 63A
Form4
| Testedarccurrent(effectivevalue) | 75A | 100A | 150A | 200A | 300A | 500A |
| N | 12 | 10 | 8 | 8 | 8 | 8 |
| Item | Type | Test current | Initial status | Timelimitftpingingo non | Expected | Remarks |
| a | C | 1.13ln | Cold | t≤1h | Non tripping | |
| b | 1.45ln | Testfolloinsesou | t | Trip | stipurenticesthtnss | |
| C | 2.55ln | Cold | 1322A) | Trip | ||
| d | C | 3ln、5ln、10ln | Cold | t0.1s | Non tripping | Conentionxifaurenth |
| e | C | 3ln、5ln、10ln | Cold | t≤0.1s | Trip | Connectionxifcryrentch |
AFDD-63
Mechanicalandelectricallife
| Type | Time | Operationfrequency(time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connectionwire
| Ratedcurrent In(A) | NominalsectionareaofcopperwireS(mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40.50 | 10 |
| 63 | 16 |
Overall and mounting sizes(mm)
VDC-100EVRCCB
General info
Function
Residualcurrentcircuit-breakerVDC-1ooEVTypeEVspecificallydeveloped foruseinchargepointsandwall-boxes forchargingelectric vehicles(EV).It isusedwhereanupstream residual current operated protectivedevice is notknownorwhereanAC,AorFtypeRCDisinuse.TheVDC-10oEVType EVprovides therequired protection fromdangerous residual currents ateverysinglechargingpoint.Forexampleitalsoprotectsanupstream residual current operated protective device from the risk of not tripping forDC residual currentscreated by thecharging equipment.
Application
Industry,medical,EVcharger,elevator,etc.
Conform to
IEC/EN61008-1,IEC/EN62955;certifiedbyCCC,SEMKO,CE
IEC/EN61oo8-1:Residual circuit breakers without overcurrent protection for household and similar purposes
IEC/EN62955:Applies to residual direct current detecting devices (RDC-DD) of model3EVcharging
IEC/EN61008-1,IEC/EN62955.
Mechanicalandelectrical life
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,25A,32A,40A,63A,100A |
| Ratedresidual operatedcurrentI△n | AC0.03A |
| Ratedresidual operatedDCcurrentI△n | DC6mA |
| Poles | 1P+N,3P+N |
| Typeof residual current | Type EV (A+ smoothing DC) |
| Rated limitedshortcircuit current Inc | 10000A |
| Ratedlimited residual shortcircuitcurrentI△c | 10000A |
| RatedmakingandbreakingcapacityIm | 1000A |
| Rated residual making and breaking capacityl△m | 1000A |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Electrical life | 2000 Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+50 |
| Storedambienttemperature℃ | -25~+70 |
| Tightening torque | 3N.m |
| Connection capacity | 16mm2 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
PG-MSeriesResidual CurrentCircuitBreaker
Application
PG-MseriesRCCBrangesfrom5Ato60A, 1 P + N or 3 P + N withorwithout earthleakageprotection300mA,500mA).
TheproductcomfirmsloIEC60947-2
Specifications
| Type | PG-MRCCB | |
| Poles | 2P | 4P |
| Rated current(A) | 5-15A(5、10、15)A 10-30A(10、15、20、25、30)A 15-45A(15、30、45)A 30-60A(30、40、50、60)A | |
| Rated voltage(V) | 230V/400V | |
| Leakageoperating current(mA) | 300mA/500mA | |
| leakage non-operating current(mA) | 150mA/250mA | |
Overall and mounting sizes(mm)