PRODUCT SELECTION MANUAL
COMPANYPRESENTATION
Zhejiang VekONTechnologyCo.,Ltd.originated from Shahu Industrial Zone,and then moved to Economic Development Zone.Yueqing isa famous center cityof China’s low voltage apparatus.Lots of electrical giants originatedhere,suchasCHNT,DELIXI,TENGEN,CNC,etc.VEKONhasbeengrowingupwiththesegiants,asella China’s lowvoltage industries.
Foundedin2002,thecompanyhasaregisteredcapitalof20.4milionyuan,Zhejiang High-tech Enterpriseand New Third Edition listed company (stockcode:836164).Ithasmore than 200employees,including10 professonal design anddevelopment engineersand8 professional qualitymanagement personnel.
Ourcompany specializes in the research,development and production of various of RCCB relayand RCCB,MCB, RCBO,isolatingswitch,MCCB,etc.ThemonthlyutputofCCBis6000pcs,whilethemonthlyutputofCCBrelay is800,00o-9oopcs.Ourrelayownsstablequaityandreliableperformance.Ithasnadvanceddust-freeproduction lineandaprofessionalproductdebuggingand testing center,which iswell known both at home andabroad.
We have established long-term cooperative relationships with some domestic and foreign enterprises such as Chint,Delixianghiderinndhneider.urusinessoversurope,Americaoutheastsadrica. Reliable product performance,qualityassurance,andafter-salesservice systemarewellrecognized by customers.
We havestrong technical strength,excellent testingequipmentand perfectquality management system.Al theseriesof products haveobtained CCCcertfication from China QualityCertfication Center,national newproduct patentcertificateand CE,SEMKOandotherforeigncertifications,and passed ISO9001qualitymanagementsystem Certification.Sinceitsestablishment,thecompanyhasalwaysadheredtothemanagementpolicyof"survivebyquality developmentbyinnovation",andpursuesthebusinessphilosophyof"customerfirst"and "practicalandtrustworthy"to createfirstclass management.Toprovideuserswithhighqualityandcompetivepriceproductsandsatisfactoryservice are ourconsistentpursuit.We sincerely welcome customersfromallover theworld tojoin usand create greaterglories!
PRODUCT CATALOG
Professional Circuit Breaker Manufacturer
PRODUCT CATALOG
Professional CircuitBreakerManufacturer
WanxiangSeries
VL10-63RCCB
General introduction
Function
VL10-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL10-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL11-63RCCB
General introduction
Function
VL11-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL11-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshort circuitcurrent Inc | 6000A |
| Ratedlimited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In =63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL12-63RCCB
General introduction
Function
VL12-63seriesRCCB(withoutovercurrentprotection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL12-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL13-63RCCB
General introduction
Function
VL13-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL13-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL15-63RCCB
General introduction
Function
VL15-63seriesRCCB(withoutovercurrentprotection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanorleakagecurrentingridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL15-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000 Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
PROFESSIONALCIRCUIT BREAKERMANUFACTURER
VL16-63RCCB
General introduction
Function
VL16-63seriesRCCB(withoutovercurrentprotection)applies toAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL16-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In =63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL17-63RCCB
Generalintroduction
Function
VL17-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL17-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentl△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000 Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL20-63 Thermosetting RCCB
General introduction
Function
VL20-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent ingrid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryand commercial buildings,high-risebuildingsand residential houses, etc.
Conformstostandard IEC/EN61008-1
VL20-63ThermosettingRCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residualshortcircuitcurrentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operatedcurrentI△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulsewithstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL20-100RCCB
General introduction
Function
VL20-100seriesRCCB(withoutovercurrentprotection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto100A.When electricshock occursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A,80A,100A |
| Rated residual operated current I△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual shortcircuit currentl△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In= 63A),1000A(In=80A、100A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In = 63A),1000A(In=80A、100A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL21-63 Thermosetting RCCB
Generalintroduction
Function
VL21-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL21-63ThermosettingRCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL22-63 Thermosetting RCCB
General introduction
Function
VL22-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakage current in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL22-63ThermosettingRCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL22-100 Thermosetting RCCB
Generalintroduction
Function
VL22-100 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto100A.When electric shock occurs to human or leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL22-100 Thermosetting RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A,80A,100A |
| Rated residual operated current I△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In= 63A),1000A(In=80A、100A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In = 63A),1000A(In=80A、100A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL23-63RCCB
Generalintroduction
Function
VL23-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL23-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL24-63 Thermosetting RCCB
General introduction
Function
VL24-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanorleakagecurrentingridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL24-63ThermosettingRCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL24-100RCCB
General introduction
Function
VL24-100 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto100A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL24-100RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A,80A,100A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas per DC component | AC |
| Ratedlimited short circuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentl△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In= 63A),1000A(In=80A、100A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A),1000A(In=80A、100A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
General introduction
Function
VL25-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time toprotect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL25-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In =63A) |
| Rated residualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
General introduction
Function
VL26-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanorleakagecurrentingridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL26-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In =63A) |
| Rated residualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
Generalintroduction
Function
VL27-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshockoccursto humanor leakagecurrent ingrid exceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL27-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentl△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
Generalintroduction
Function
VL28-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL28-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In =63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
PROFESSIONALCIRCUIT BREAKERMANUFACTURER
VL33-63RCCB
General introduction
Function
VL33-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL33-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas perDC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In=63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In =63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL34-63RCCB
Generalintroduction
Function
VL34-63 series RCCB(without overcurrent protection)applies to AC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalsofunctionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL34-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytypeas perDC component | AC,A |
| Rated limitedshortcircuit current Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In=63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In =63A) |
| Rated residual non-operated current I△no | 0.51△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
General introduction
Function
VL35-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL35-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N.415V~3P+N |
| Rated current In | 16A,20A,25A,32A,40A,50A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Ratedlimitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuit current I△c | 6000A |
| Ratedmakingandbreakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residualmakingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 2000Times |
| Mechanical life | 3000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL36-63RCCB
General introduction
Function
VL36-63seriesRCCB(withoutovercurrent protection)appliestoAC 5 0 H z ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electricshock occursto humanor leakagecurrent in gridexceedsstipulated values,RCCBcutsoff the fault power inaveryshort time to protect the safetyof humanandelectricalequipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1