ELECTRIC
POWER
RATINGS
GUIDE
2023
Eighteenth Edition
LEXE7582-18 Ratings Booklet Final.indd 1 04/04/2023 14:21:27
LEXE7582-18 Ratings Booklet Final.indd 2 04/04/2023 14:21:27
CONTENTS
Cat®
Diesel Generator Sets
50 Hz Ratings.........................................................................................................................................................................4 – 6
50 Hz Ratings – Cat GC Global.............................................................................................................................7
50 Hz Ratings – Heavy Fuel........................................................................................................................................7
60 Hz Ratings.....................................................................................................................................................................8 – 11
60 Hz Ratings – Cat GC Global........................................................................................................11 – 12
60 Hz Ratings – Cat GC North America..............................................................................12 – 13
60 Hz Ratings – Heavy Fuel ..................................................................................................................................13
50 & 60 Hz Ratings – Rental Power...........................................................................................13 – 14
Definitions.............................................................................................................................................................................................15
Cat Gas Generator Sets
50 Hz Ratings – Natural Gas.................................................................................................................18 – 19
50 Hz Ratings – Biogas..................................................................................................................................................19
60 Hz Ratings – Natural Gas.................................................................................................................20 – 21
60 Hz Ratings – Power Solutions....................................................................................................................21
60 Hz Ratings – Biogas..................................................................................................................................................22
50 & 60 Hz Ratings – Rental Power............................................................................................................22
Definitions.............................................................................................................................................................................................23
Renewable Hybrid Energy Solutions
Photovoltaic Panels (PV)..............................................................................................................................................26
PV Inverter Options CE Mark & UL Listed.........................................................................................27
Weather Stations.......................................................................................................................................................................28
Microgrid Master Controllers (MMC)...........................................................................................................29
Microgrids & Renewable Energy Systems.........................................................................................30
Power Grid Stablilization (PGS).........................................................................................................................30
Energy Time Shift (ETS)................................................................................................................................................31
Energy Capacity Expansion (ECE)................................................................................................................31
EMCP 4................................................................................................................................................................................................34 – 35
Product Features.......................................................................................................................................................................36
Systems Products
Advanced Control ....................................................................................................................................................40 – 41
Paralleling Switchgear and Cat Switchgear Selector.......................................42 – 43
ATS, ATC Line and TruONE & MX Line...............................................................................................44
Temporary Generator Connections...............................................................................................................45
Cat Connect and Product Support......................................................................................................48 – 52
LEXE7582-18 Ratings Booklet Final.indd 3 04/04/2023 14:21:28
4
3516E 60 Hz
LEXE7582-18 Ratings Booklet Final.indd 4 04/04/2023 14:21:28
5
DIESEL
GENERATOR SETS
LEXE7582-18 Ratings Booklet Final.indd 5 04/04/2023 14:21:29
4
DIESEL
50 Hz, 6.8 – 200 kVA RATINGS
kVA Generator Set
Standby Prime Model Engine Configuration
Single Phase Output* 1500 rpm
7.5 6.8 DE7.5E3S C1.1 R96/EU Stage IIIA Equivalent
11 10 DE11E3S C1.5 R96/EU Stage IIIA Equivalent
12 11 DE12E0S C1.5 Low BSFC
14 13 DE14E3S C2.2 R96/EU Stage IIIA Equivalent
16.5 15 DE16E3S C2.2 R96/EU Stage IIIA Equivalent
26 24 DE26E0S C3.3 Low BSFC
26 24 DE26E3S C3.3 R96/EU Stage IIIA Equivalent
40 36 DE40E0S C3.3 Low BSFC
40 36 DE40E2S C3.3 R96/EU Stage II Equivalent
50 45 DE50E0S C3.3 Low BSFC
55 50 DE55E3S C4.4 R96/EU Stage IIIA
90 82 DE90E2S C4.4 R96/EU Stage II Equivalent
90 82 DE90E3S C4.4 R96/EU Stage IIIA
Three Phase Output** 1500 rpm
9.5 8.5 DE9.5E3 C1.1 R96/EU Stage IIIA Equivalent
13.5 12.5 DE13.5E3 C1.5 R96/EU Stage IIIA Equivalent
16 14.5 DE16E0 C1.5 Low BSFC
18 16.5 DE18E3 C2.2 R96/EU Stage IIIA Equivalent
22 20 DE22E3 C2.2 R96/EU Stage IIIA Equivalent
33 30 DE33E0 C3.3 Low BSFC
33 30 DE33E3 C3.3 R96/EU Stage IIIA Equivalent
49 45 DE56AE0 C3.3 Low BSFC
50 45 DE50E0 C3.3 Low BSFC
50 45 DE50E2 C3.3 EU Stage II Equivalent
55 50 DE55E0 C3.3 Low BSFC
55 50 DE55E2 C4.4 EU Stage II Equivalent
65 60 DE65E0 C3.3 Low BSFC
65 60 DE65E3 C4.4 R96/EU Stage IIIA
88 80 DE88E0 C4.4 Low BSFC
65 60 DE75AE0 C3.3 Low BSFC
88 80 DE100AE0 C4.4 Low BSFC
88 80 DE88E3 C4.4 R96/EU Stage IIIA
110 100 DE125AE0 C4.4 Low BSFC
110 100 DE110E2 C4.4 EU Stage II Equivalent
110 100 DE110E3 C4.4 R96/EU Stage IIIA
149 135 DE169AE0 C7.1 Low BSFC
150 135 DE150E0 C7.1 Low BSFC
165 150 DE165E0 C7.1 Low BSFC
165 150 DE165E3 C7.1 R96/EU Stage IIIA Equivalent
175 160 DE175E3 C7.1 R96/EU Stage IIIA Equivalent
200 180 DE200E0 C7.1 Low BSFC
*All ratings at 1.0 pf. **All ratings at 0.8 pf.
LEXE7582-18 Ratings Booklet Final.indd 6 04/04/2023 14:21:29
5
DIESEL
50 Hz, 180 – 850 kVA RATINGS
kVA Generator Set
Standby Prime Model Engine Configuration
1500 rpm
200 180 DE218AE0 C7.1 Low BSFC
200 180 DE200E3 C7.1 R96/EU Stage IIIA Equivalent
220 200 DE220E0 C7.1 Low BSFC
250 230 DE250E0 C9 Low BSFC
275 250 DE275E0 C9 Low BSFC
275 250 DE275E3 C9 R96/EU Stage IIIA Equivalent
300 275 DE300E0 C9 Low BSFC
300 275 DE300E3 C9 R96/EU Stage IIIA Equivalent
330 300 DE330E0 C9 Low BSFC
— 350 DE350C3 C13 China Non-Road Stage III
— 400 DE400C3 C13 China Non-Road Stage III
400 350 DE400E0 C13 Low BSFC
450 400 DE450E0 C13 Low BSFC
450 400 DE450E3 C13 R96/EU Stage IIIA Equivalent
450 400 — C15 Low BSFC
— 450 DE450C3 C15 China Non-Road Stage III
— 500 DE500C3 C15 China Non-Road Stage III
500 455 DE500E0 C15 Low BSFC
550 500 DE550E0 C15 Low BSFC
550 500 DE550E3 C15 R96/EU Stage IIIA Equivalent
605 550 DE605E0 C18 Low BSFC
— 600 DE600C3 C18 China Non-Road Stage III
660 600 DE660E0 C18 Low BSFC
700 635 — C18 Low BSFC
715 650 DE715E0 C18 Low BSFC
780 706 DE780E0 C18 Low BSFC
850 770 DE850E0 C18 Low BSFC
kVA
Generator
Standby Set Model Configuration
Mission
Critical Prime
PrimeDCP Contin.
1500 rpm
750 — 680 — — 3412C Low BSFC
800 — 725 — — 3412C Low BSFC
900 — 810 — — 3412C Low BSFC
1100 1100 1000 — 910 C32 Low BSFC, Low Emissions
1250 1250 1100 — — C32 Low BSFC
50 Hz, 680 – 1250 kVA RATINGS
LEXE7582-18 Ratings Booklet Final.indd 7 04/04/2023 14:21:29
6
DIESEL
*Rating does not include package mounted radiator.
kVA
Generator
Standby Set Model Configuration
Mission
Critical Prime
PrimeDCP Contin.
1500 rpm
1250 1250 1150 1150 1000 3512 Low BSFC
1400 1400 1275 — — C32 Low BSFC
1400 1400 1275 1275 1206 3512 Low BSFC
1500 1500 1375 — — C32 Low BSFC
1500 1500 1360 1360 — 3512B Low BSFC, Low Emissions
1600 1600 1500 1500 1320 3512B Low BSFC, Low Emissions
1625 1625 — — — 3512B Low BSFC, Low Emissions
1750 1750 1600 1600 — 3512B Low BSFC, Low Emissions
1875 1875 1700 1700 1500 3512B Low BSFC, Low Emissions
2000 2000 1825 1825 1600 3516 Low BSFC
2250 2250 2045 2045 — 3516C < 2000 mg NOx, EPA Tier 2
2250 2250 2000 2000 1750 3516B Low BSFC, Low Emissions
— — 2000 — 1750 3516B DGB Low BSFC
— — 2275 — 2000 3516B DGB Low BSFC
2500 2500 2275 2275 2000 3516B Low BSFC, Low Emissions
2750 2750 2500 2500 — 3516C < 2000 mg NOx, EPA Tier 2
2750 2750 2500 2500 — 3516C Low BSFC, Low Emissions
3000 3000 2725 2725 — 3516E < 2000 mg NOx, EPA Tier 2
3000 3000 2725 2725 2500 C175-16 Low BSFC
3000 3000 — — — C175-16 Low Emissions
3000 3000 2750 2750 — 3516E Low BSFC
3250 3250 2950 2950 — 3516E < 2000 mg NOx, EPA Tier 2
3500 3500 3175 3175 — 3516E EPA Tier 2
3900 3900 3500 3500 3150 C175-20 Low BSFC
3900 3900 — — — C175-20 Low Emissions
4000* 4000* 3600* 3600* 3250* C175-20 Low BSFC
4000* 4000* — — — C175-20 Low Emissions
1000 rpm
2688 — 2425 — 2200 3606 Low BSFC
3575 — 3250 — 2938 3608 Low BSFC
— — 3250 — 2938 C280-8 IMO/U.S. EPA Tier 2
5375 — 4850 — 4400 3612 Low BSFC
— — 4850 — 4400 C280-12 IMO/EPA Tier 2
7150 — 6500 — 5875 3616 Low BSFC
— — 6500 — 5875 C280-16 IMO/EPA Tier 2
750 rpm
1963 — 1963 — — 3606 Low BSFC
2600 — 2600 — — 3608 Low BSFC
3925 — 3925 — — 3612 Low BSFC
5200 — 5200 — — 3616 Low BSFC
50 Hz, 1000 – 7150 kVA RATINGS
LEXE7582-18 Ratings Booklet Final.indd 8 04/04/2023 14:21:29
kVA Generator Set
Standby Prime Model Engine Configuration
1500 rpm
33 — DE33 GC C3.3 Low BSFC
50 — DE50 GC C3.3 Low BSFC
55 — DE55 GC C3.3 Low BSFC
65 — DE65 GC C3.3 Low BSFC
88 — DE88 GC C4.4 Low BSFC
110 — DE110 GC C4.4 Low BSFC
150 — DE150 GC C7.1 Low BSFC
163.9 — DE165 GC C7.1 Low BSFC
200 — DE200 GC C7.1 Low BSFC
217 — DE220 GC C7.1 Low BSFC
400 — DE400 GC C9.3B Low BSFC
450 — DE450 GC C13 Low BSFC
500 — DE500 GC C13 Low BSFC
550 — DE550 GC C13 Low BSFC
605 — DE605 GC C15 Low BSFC
660 — DE660 GC C15 Low BSFC
715 — DE715 GC C15 Low BSFC
1100 — DE1100 GC C32 Low BSFC
1250 — DE1250 GC C32 Low BSFC
1400 — DE1400 GC C32 Low BSFC
1500 — DE1500 GC C32 Low BSFC
7
DIESEL
50 Hz, 33 – 1500 kVA RATINGS — Cat GC GLOBAL
Continuous Generator
kVA bkW Set Model* Configuration
1000 rpm
2000 1680 3606 Low BSFC
2700 2240 3608 Low BSFC
4050 3360 3612 Low BSFC
5400 4480 3616 Low BSFC
*Special rating request required.
50 Hz, 2000 – 5400 kVA RATINGS — HEAVY FUEL
LEXE7582-18 Ratings Booklet Final.indd 9 04/04/2023 14:21:30
8
DIESEL
60 Hz, 8 – 600 ekW RATINGS
ekW Generator Set
Standby Prime Model Engine Configuration
Single Phase Output* 1800 rpm
8.8 8 DE7.5E3S C1.1 R96/EU Stage IIIA Equivalent
13 12 DE11E3S C1.5 R96/EU Stage IIIA Equivalent
17 15.5 DE14E3S C2.2 R96/EU Stage IIIA Equivalent
19.4 17.6 DE16E3S C2.2 R96/EU Stage IIIA Equivalent
45 40 DE40E0S C3.3 Low BSFC
60 55 DE50E0S C3.3 Low BSFC
99.5 90 DE90E2S C4.4 EU Stage II Equivalent
Three Phase Output** 1800 rpm
8.8 8 DE9.5E3 C1.1 R96/EU Stage IIIA Equivalent
13.2 12 DE13.5E3 C1.5 R96/EU Stage IIIA Equivalent
17.6 16 DE18E3 C2.2 R96/EU Stage IIIA Equivalent
20 18 DE22E3 C2.2 R96/EU Stage IIIA Equivalent
30 27 DE33E0 C3.3 Low BSFC
45 40 DE56AE0 C3.3 Low BSFC
45 40 DE50E0 C3.3 Low BSFC
50 45 DE55E0 C3.3 Low BSFC
60 55 DE75AE0 C3.3 Low BSFC
60 55 DE65E0 C3.3 Low BSFC
80 72 DE100AE0 C4.4 Low BSFC
80 72 DE88E0 C4.4 Low BSFC
100 90 DE125AE0 C4.4 Low BSFC
100 90.4 DE110E2 C4.4 EU Stage II Equivalent
132 120 DE150E0 C7.1 Low BSFC
135 120 DE169AE0 C7.1 Low BSFC
150 135 DE165E0 C7.1 Low BSFC
174 157 DE218AE0 C7.1 Low BSFC
175 160 DE200E0 C7.1 Low BSFC
200 180 DE200SE0 C9 Low BSFC
250 225 DE250SE0 C9 Low BSFC
275 250 DE275SE0 C9 Low BSFC
300 270 DE300SE0 C9 Low BSFC
350 320 DE350SE0 C13 Low BSFC
400 350 DE400SE0 C13 Low BSFC
450 410 DE450SE0 C15 Low BSFC
500 455 DE500SE0 C15 Low BSFC
550 500 DE550SE0 C18 Low BSFC
600 545 DE600SE0 C18 Low BSFC
*All ratings at 1.0 pf. **All ratings at 0.8 pf.
LEXE7582-18 Ratings Booklet Final.indd 10 04/04/2023 14:21:30
9
DIESEL
60 Hz, 20 – 400 ekW RATINGS EPA Stationary Emergency – North America.
ekW Generator Set
Standby Prime Model Engine Configuration
Single Phase Output* 1800 rpm
20 — D20 C2.2 ESE
25 — D25 C2.2 ESE
30 — D30 C2.2 ESE
40 36 D40S C4.4 ESE
50 45 D50S C4.4 ESE
60 55 D60S C4.4 ESE
80 72 D80S C4.4 ESE
100 90 D100S C4.4 ESE
Three Phase Output** 1800 rpm
20 — D20 C2.2 ESE
25 — D25 C2.2 ESE
30 — D30 C2.2 ESE
40 36 D40 C4.4 ESE
50 45 D50 C4.4 ESE
60 55 D60 C4.4 ESE
80 72 D80 C4.4 ESE
100 90 D100 C4.4 ESE
125 114 D125 C7.1 ESE
150 136 D150 C7.1 ESE
175 158 D175 C7.1 ESE
200 — D200 C7.1 ESE
200 180 200 C9 ESE
250 225 250 C9 ESE
300 275 300 C9 ESE
350 320 350 C13 ESE
400 365 400 C13 ESE
350 320 350 C15 ESE
400 365 400 C15 ESE
ekW Generator Set
Standby Prime Model Engine Configuration
1800 rpm
650 600 DE650SE0 C18 Low BSFC
716 650 DE715SE0 C18 Low BSFC
750 680 DE750SE0 C18 Low BSFC
60 Hz, 600 – 750 ekW RATINGS
*All ratings at 1.0 pf. **All ratings at 0.8 pf. ESE = “EPA Stationary Emergency”.
LEXE7582-18 Ratings Booklet Final.indd 11 04/04/2023 14:21:30
10
60 Hz, 635 – 2750 ekW RATINGS
ekW
Generator
Standby Set Model Configuration
Mission
Critical Prime
PrimeDCP Contin.
1800 rpm
700 — 635 — — 3412C Low BSFC
750 — 680 — — C27 ESE, Low BSFC
750 — 680 — — 3412C Low BSFC
800 800 725 — — C27 ESE, Low BSFC
800 — 725 — — 3412C Low BSFC
1000 1000 910 — 830 C32 ESE, Low BSFC
1100 1100 1000 1000 890 3512 Low BSFC
1100 1100 1000 — — C32 ESE, Low BSFC
1250 1250 1136 — — C32 ESE, Low BSFC
1250 1250 1135 1135 1010 3512 Low BSFC
1400 1400 1275 1275 — 3512B Low BSFC, Low Emissions
1500 1500 1360 1360 1230 3512B Low BSFC, Low Emissions
1500 1500 1360 1360 1230 3512C ESE
1750 1750 1600 1600 — 3512C ESE
1750 1750 1600 1600 1450 3516 Low BSFC
2000 2000 1825 1825 1640 3516B Low BSFC, Low Emissions
— — 1825 — 1640 3516B DGB Low BSFC
2000 2000 1825 1825 1650 3516C ESE
2000 2000 1825 1825 1650 3516C EPA Tier 4 Final
2250 2250 2000 2000 — 3516B Low BSFC
2250 2250 2045 2045 — 3516C ESE
2500 2500 2250 2250 2050 3516C ESE
2500 2500 2250 2250 — 3516C EPA Tier 4 Final
2750 2750 2500 2500 — 3516E ESE
DIESEL
ekW Generator Set
Standby Prime Model Engine Configuration
1800 rpm
450 410 450 C15 ESE
500 455 500 C15 ESE
500 455 500 C18 EPA Tier 4 Final
550 500 550 C18 ESE
600 545 600 C18 ESE
650 600 650 C18 ESE
700 635 700 C18 ESE
750 680 750 C18 ESE
ESE = “EPA Stationary Emergency”.
60 Hz, 410 – 750 ekW RATINGS EPA Stationary Emergency – North America.
ESE = “EPA Stationary Emergency”.
LEXE7582-18 Ratings Booklet Final.indd 12 04/04/2023 14:21:30
11
DIESEL
60 Hz, 1525 – 5320 ekW RATINGS
ekW Generator Set
Standby Prime Continuous Model Configuration
900 rpm
2000 1820 1650 3606 Low BSFC
2660 2420 2200 3608 Low BSFC
— 2420 2200 C280-8* EPA Tier 4 Final
4000 3640 3300 3612 Low BSFC
— 3640 3300 C280-12* EPA Tier 4 Final
5320 4840 4400 3616 Low BSFC
— 4840 4400 C280-16* EPA Tier 4 Final
720 rpm
— 1525 — 3606 Low BSFC
— 2020 — 3608 Low BSFC
— 3050 — 3612 Low BSFC
— 4040 — 3616 Low BSFC
*Tier 4 Final is met using AVERAGE, BANKING, and TRADING PROGRAM.
60 Hz, 30 – 100 ekW RATINGS — Cat GC GLOBAL
ekW Generator Set
Standby Prime Model Engine Configuration
1800 rpm
30 — DE33 GC C3.3 Low BSFC
45 — DE50 GC C3.3 Low BSFC
50 — DE55 GC C3.3 Low BSFC
60 — DE65 GC C3.3 Low BSFC
80 — DE88 GC C4.4 Low BSFC
100 — DE110 GC C4.4 Low BSFC
ekW
Generator
Standby Set Model Configuration
Mission
Critical Prime
PrimeDCP Contin.
1800 rpm
3000 3000 2725 2725 — 3516E ESE
3000 3000 2725 2725 2500 C175-16 EPA Tier 4 Final, ESE, Low BSFC
3250 3250 3000 3000 — C175-16 ESE
3500 3500 3180 3180 — C175-20 ESE
3900 3900 3500 3500 3150 C175-20 ESE, Low BSFC
4000* 4000* 3600* 3600* 3250* C175-20 ESE, Low BSFC
ESE = “EPA Stationary Emergency”.
*Rating does not include package mounted radiator.
60 Hz, 2725 – 4000 ekW RATINGS
LEXE7582-18 Ratings Booklet Final.indd 13 04/04/2023 14:21:30
12
DIESEL
60 Hz, 40 – 400 ekW RATINGS — Cat GC NORTH AMERICA
ekW Generator Set
Standby Prime Model Engine Configuration
Single Phase Output* 1800 rpm
40 — D40 GC C4.4 ESE
50 — D50 GC C4.4 ESE
60 — D60 GC C4.4 ESE
80 — D80 GC C4.4 ESE
100 — D100 GC C4.4 ESE
Three Phase Output** 1800 rpm
40 — D40 GC C4.4 ESE
50 — D50 GC C4.4 ESE
60 — D60 GC C4.4 ESE
80 — D80 GC C4.4 ESE
100 — D100 GC C4.4 ESE
125 — D125 GC C7.1 ESE
150 — D150 GC C7.1 ESE
175 — D175 GC C7.1 ESE
200 — D200 GC C7.1 ESE
250 — D250 GC C9 ESE
300 — D300 GC C9 ESE
350 — D350 GC C13 ESE
400 — D400 GC C13 ESE
ekW Generator Set
Standby Prime Model Engine Configuration
1800 rpm
132 — DE150 GC C7.1 Low BSFC
150 — DE165 GC C7.1 Low BSFC
175 — DE200 GC C7.1 Low BSFC
350 — DE350S GC C9.3 Low BSFC
400 — DE400S GC C9.3 Low BSFC
450 — DE450S GC C13 Low BSFC
500 — DE500S GC C13 Low BSFC
550 — DE550S GC C15 Low BSFC
600 — DE600S GC C15 Low BSFC
800 — DE800S GC C27 Low BSFC
1000 — DE1000S GC C32 Low BSFC
1250 — DE1250S GC C32 Low BSFC
60 Hz, 132 – 1250 ekW RATINGS — Cat GC GLOBAL
*All ratings at 1.0 pf. **All ratings at 0.8 pf. ESE = “EPA Stationary Emergency”.
LEXE7582-18 Ratings Booklet Final.indd 14 04/04/2023 14:21:30
13
DIESEL
Continuous Generator Set
ekW bkW Model* Configuration
900 rpm
1500 1570 3606 Low BSFC
2000 2090 3608 Low BSFC
3000 3140 3612 Low BSFC
4000 4180 3616 Low BSFC
*Special rating request required.
60 Hz, 1500 – 4000 ekW RATINGS — HEAVY FUEL
50 Hz, 30 – 2000 kVA RATINGS — RENTAL POWER
kVA Generator
Standby Prime Continuous Set Model Configuration
1500 rpm
22 20 — XQP20 EU Stage V
33 30 — XQP30 Low BSFC
65 60 — XQP60 R96/EU Stage IIIA Equivalent
110 100 — XQP100 Low BSFC
125 114 — XQP115 EU Stage V
165 150 — XQP150 Low BSFC
220 200 — XQP200 EU Stage V
330 300 — XQP300 Low BSFC
340 310 — XQP310 EU Stage V
550 500 — XQP500 Low BSFC
605 550 — XQP550 EU Stage V
1210 1100 — XQP1100 Low BSFC
— — 1438 XQC1200 Low BSFC / Low Emissions
— — 1893 XQC1600 Low BSFC / Low Emissions
— 2000 1750 XQ2000 DGB™ Low BSFC
ekW Generator Set
Standby Prime Model Engine Configuration
1800 rpm
450 — D450 GC C15 ESE
500 — D500 GC C15 ESE
550 — D550 GC C18 ESE
600 — D600 GC C18 ESE
800 — D800 GC C27 ESE
1000 — D1000 GC C32 ESE
1250 — D1250 GC C32 ESE
ESE = “EPA Stationary Emergency”.
60 Hz, 450 – 1250 ekW RATINGS — Cat GC NORTH AMERICA
LEXE7582-18 Ratings Booklet Final.indd 15 04/04/2023 14:21:31
14
DIESEL
60 Hz, 28 – 1705 ekW RATINGS — RENTAL POWER
ekW Generator Set
Standby Prime Continuous Model Configuration
1800 rpm
31 28 — XQP30 Low BSFC
60 54 — XQP60 R96/EU Stage IIIA Equivalent
103 94 — XQP100 Low BSFC
137 125 — XQP115 EU Stage V
149 135 — XQP150 Low BSFC
198 180 — XQP200 EU Stage V
302 275 — XQP300 Low BSFC
297 270 — XQP310 EU Stage V
460 420 — XQP500 Low BSFC
512 470 — XQP550 EU Stage V
1067 970 — XQP1100 Low BSFC
— — 1260 XQC1200 Low BSFC, Low Emissions
— — 1705 XQC1600 Low BSFC, Low Emissions
kVA Generator
Standby Prime Continuous Set Model Configuration
1800 rpm
20 20 — XQ20 EPA Tier 4 Final
38 34 — XQ35 EPA Tier 4 Final
— 59 — XQ60 EPA Tier 4 Final
138 125 — XQ125 EPA Tier 4 Final
250 228 — XQ230 EPA Tier 4 Final
360 330 — XQ330 EPA Tier 4 Final
469 425 — XQ425 EPA Tier 4 Final
625 568 — XQ570 EPA Tier 4 Final
1250 1136 — XQ1140 EPA Tier 4 Final
2500 2280 — XQ2280 EPA Tier 4 Final
60 Hz, 34 – 2500 kVA RATINGS — RENTAL POWER
LEXE7582-18 Ratings Booklet Final.indd 16 04/04/2023 14:21:31
15
DIESEL
Standby: Output available with varying load for the duration of the interruption
of the normal source power. Average power output is 70% of the standby
rated ekW. Typical operation is 200 hours per year, with maximum expected
usage of 500 hours per year.
Mission Critical: Output available with varying load for the duration of the
interruption of the normal source power. Average power output is 85% of the
mission critical rated ekW. Typical peak demand up to 100% of rated ekW for up
to 5% of the operating time. Typical operation is 200 hours per year, with
maximum expected usage of 500 hours per year.
Prime: Output available with varying load for an unlimited time. Average power
output is 70% of the prime rated ekW. Typical peak demand is 100% of prime
rated ekW with 10% overload capability for emergency use for a maximum of
1 hour in 12. Overload operation cannot exceed 25 hours per year.
Prime-DCP: For data center applications only. Prime-DCP power output available
with varying load for unlimited time. Average power output is not to exceed 100%
of Prime-DCP rated ekW. Typical peak demand is 100% of the prime-DCP rated
ekW with 10% overload capability for emergency use for a maximum of 1 hour in
12. Overload operation cannot exceed 25 hours per year.
Continuous: Output available with non-varying load for an unlimited time.
Average power output is 70-100% of the continuous rated ekW. Typical peak
demand is 100% of continuous rated ekW for 100% of the operating hours.
DEFINITIONS
LEXE7582-18 Ratings Booklet Final.indd 17 04/04/2023 14:21:31
G3520H
LEXE7582-18 Ratings Booklet Final.indd 18 04/04/2023 14:21:31
GAS
GENERATOR SETS
LEXE7582-18 Ratings Booklet Final.indd 19 04/04/2023 14:21:31
GAS
50 Hz, 374 – 2500 ekW RATINGS — NATURAL GAS
ekW Continuous* Generator Set Model
1500 rpm
374 G3412C
400 CG132B-8
600 CG132B-12
800 CG132B-16
983 G3516
1000 CG132B-16
1000 CG170-12
1125 CG170-12
1200 CG170-12
1380 CG170B-12
1500 G3512H
1500 CG170-16
1560 CG170-16
1603 G3516C
1976 G3520C
1840 CG170B-16
2000 G3516H
2000 CG170B-20
2300 CG170B-20
2500 G3520H
50 Hz, 158 – 400 kVA RATINGS — NATURAL GAS
kVA Generator Set
Standby Prime Model Engine
1500 rpm
175 158 DG175-1 GC 14.2
200 180 DG200-1 GC 14.2
230 207 DG230-1 GC 14.2
250 225 DG250-1 GC 14.2
275 248 DG275-1 GC 14.2
300 270 DG300-1 GC 14.2
350 315 DG350-1 GC 21.9
400 360 DG400-1 GC 21.9
18
*All ratings at 0.8 pf. Electric output depends on final generator specification.
<250mg NOx/Nm³ at an oxygen content of 5%.
LEXE7582-18 Ratings Booklet Final.indd 20 04/04/2023 14:21:31
19
GAS
50 Hz, 174 – 3770 ekW RATINGS — BIOGAS
ekW Continuous* Generator Set Model
1500 rpm
174 G3412
400 CG132B-8
600 CG132B-12
800 CG132B-16
1000 CG170-12
1041 G3516
1105 G3516+
1200 CG170-12
1380 CG170B-12
1560 CG170-16
1840 CG170B-16
1984 G3520C
2000 CG170B-20
2300 CG170B-20
1000 rpm
3770 CG260-16
*All ratings at 0.8 pf.
ekW Continuous* Generator Set Model
1000 rpm
3333 CG260-12
4300 CG260-16
4500 CG260-16
*All ratings at 0.8 pf. Electric output depends on final generator specification.
<250mg NOx/Nm³ at an oxygen content of 5%.
50 Hz, 3333 – 4500 ekW RATINGS — NATURAL GAS
LEXE7582-18 Ratings Booklet Final.indd 21 04/04/2023 14:21:31
20
GAS
60 Hz, 175 – 2500 ekW RATINGS — NATURAL GAS
ekW Generator Set
Standby Model Engine Configuration
Single Phase Output* 1800 rpm
100 DG100 6.2 ESE
125 DG125 6.2 ESE
175 DG175-2 GC 14.2 ESE
200 DG200-2 GC 14.2 ESE
Three Phase Output** 1800 rpm
100 DG100 6.2 ESE
125 DG125 6.2 ESE
175 DG175-2 GC 14.2 ESE
200 DG200-2 GC 14.2 ESE
230 DG230-2 GC 14.2 ESE
250 DG250-2 GC 14.2 ESE
275 DG275-2 GC 14.2 ESE
300 DG300-2 GC 14.2 ESE
350 DG350-2 GC 21.9 ESE
400 DG400-2 GC 21.9 ESE
450 DG450-2 GC 21.9 ESE
423 G3412C G3412C —
500 G3412 G3412 with FAST RESPONSE EPA Factory Certified
750 G3512 G3512 with FAST RESPONSE EPA Factory Certified
1000 G3512 G3512 with FAST RESPONSE EPA Factory Certified
1500 G3516 G3516 with FAST RESPONSE EPA Factory Certified
2000 G3520 G3520 with FAST RESPONSE EPA Factory Certified
2500 G3520 G3520 with FAST RESPONSE EPA Factory Certified
*All ratings at 1.0 pf. **All ratings at 0.8 pf.
The above Certifications are applicable for US Sales: ESE = “EPA Stationary Emergency”.
ekW Generator Set
Demand Response Model Engine Configuration
Single Phase Output 1800 rpm
175 DG175-2 GC 14.2 EPA Non-Emergency
200 DG200-2 GC 14.2 EPA Non-Emergency
Three Phase Output* 1800 rpm
175 DG175-2 GC 14.2 EPA Non-Emergency
200 DG200-2 GC 14.2 EPA Non-Emergency
230 DG230-2 GC 14.2 EPA Non-Emergency
250 DG250-2 GC 14.2 EPA Non-Emergency
275 DG275-2 GC 14.2 EPA Non-Emergency
300 DG300-2 GC 14.2 EPA Non-Emergency
350 DG350-2 GC 21.9 EPA Non-Emergency
400 DG400-2 GC 21.9 EPA Non-Emergency
450 DG450-2 GC 21.9 EPA Non-Emergency
*All ratings at 1.0 pf.
The above Certifications are applicable for US Sales: ESE = “EPA Stationary Emergency”.
60 Hz, 175 – 450 ekW RATINGS — NATURAL GAS
LEXE7582-18 Ratings Booklet Final.indd 22 04/04/2023 14:21:31
21
GAS
60 Hz, 253 – 4050 ekW RATINGS — NATURAL GAS
ekW Continuous* Generator Set Model
1800 rpm
253 G3412
400 CG132B-8
423 G3412
453 G3412C
600 CG132B-12
800 CG132B-16
1300 G3516
1663 G3516C
2077 G3520C
1500 rpm
1125 CG170-12
1200 CG170-12
1490 G3512H
1500 CG170-16
1560 CG170-16
1982 G3516H
2483 G3520H
900 rpm
3000 CG260-12
4000 CG260-16
4050 CG260-16
ekW
Continuous* Generator Set Model Engine / Configuration
1800 rpm
1500 CHP1500 G3512H w/CHP Solution
2000 CHP2000 G3516H w/CHP Solution
2500 CHP2500 G3520H w/CHP Solution
*All ratings at 0.8 pf.
60 Hz, GAS POWER SOLUTION RATINGS, 1500 – 2500 ekW
LEXE7582-18 Ratings Booklet Final.indd 23 04/04/2023 14:21:31
22
GAS
ekW Continuous* Generator Set Model
1800 rpm
194 G3412
400 CG132B-8
600 CG132B-12
800 CG132B-16
1200 rpm
824 G3516
1000 G3516+
1626 G3520C
1500 rpm
1200 CG170-12
1560 CG170-16
1950 G3520C
900 rpm
3510 CG260-16
*All ratings at 0.8 pf.
60 Hz, 194 – 3510 ekW RATINGS — BIOGAS
ekW Generator Set
Continuous* Model Configuration
1500/1800 rpm
1475 XQ1475 US EPA NSPS SI Capable
1900 XGC1900 500 mg/Nm3
NOx
1800 rpm
1900 XGC1900 250 mg/Nm3
NOx
*All ratings at 0.8 pf.
At an oxygen content of 5%.
50/60 Hz, 1475 – 1900 ekW RENTAL POWER RATINGS
LEXE7582-18 Ratings Booklet Final.indd 24 04/04/2023 14:21:31
GAS
23
DEFINITIONS
Standby: Output available with varying load for the duration of an emergency
outage. Average power output is 70% of the standby power rating. Typical operation
is 200 hours per year, with maximum expected usage of 500 hours per year.
Demand Response: Output available with varying load for the duration of the
interruption of normal source power. Average power output is 70% of the standby
power rating. Typical operation is 200 hours per year, with maximum expected
usage of 500 hours per year.
Prime: Output available with varying load for an unlimited time. Average power
output is 70% of the prime power rating. Typical peak demand of 100% of primerated ekW with 10% of overload capability for emergency use for a maximum of
1 hour in 12. Overload operation cannot exceed 25 hours per year.
Continuous: Output available with non-varying load for an unlimited time.
Average power output is 70-100% of the continuous power rating. Typical peak
demand is 100% of continuous rated ekW for 100% of operating hours.
LEXE7582-18 Ratings Booklet Final.indd 25 04/04/2023 14:21:31
LEXE7582-18 Ratings Booklet Final.indd 26 04/04/2023 14:21:32
RENEWABLE
HYBRID ENERGY
SOLUTIONS
LEXE7582-18 Ratings Booklet Final.indd 27 04/04/2023 14:21:33
26
RENEWABLE HYBRID SOLUTIONS
Monofacial Model Power Output per Panel Type
PVC415 MP02 415 watt Monocrystalline PERC
PVC445 MP03 H 445 watt Monocrystalline PERC Half-cut
PVC450 MP03 H 450 watt Monocrystalline PERC Half-cut
Silver Frame / White Backsheet
PVC540 MP03HC 540 watt Monocrystalline PERC Half-cut
PVC545 MP03HC 545 watt Monocrystalline PERC Half-cut
Black Frame / Black Backsheet
PVC350 MP03HA 350 watt Monocrystalline PERC Half-cut
PVC355 MP03HA 355 watt Monocrystalline PERC Half-cut
PVC360 MP03HA 360 watt Monocrystalline PERC Half-cut
PVC355 MP03HB 355 watt Monocrystalline PERC Half-cut
PVC360 MP03HB 360 watt Monocrystalline PERC Half-cut
PVC365 MP03HB 365 watt Monocrystalline PERC Half-cut
Note: Check with local dealer for product availability which varies by region and delivery date.
Photovoltaic Panels (PV)
Bifacial Model Power Output per Panel Type
PVC435 MB03H 435 watt Monocrystalline PERC Half-cut
PVC440 MB03H 440 watt Monocrystalline PERC Half-cut
PVC445 MB03H 445 watt Monocrystalline PERC Half-cut
Silver Frame / Dual Glass
PVC530 MB03HE 530 watt Monocrystalline PERC Half-cut
PVC535 MB03HE 535 watt Monocrystalline PERC Half-cut
PVC540 MB03HE 540 watt Monocrystalline PERC Half-cut
Note: Check with local dealer for product availability which varies by region and delivery date.
LEXE7582-18 Ratings Booklet Final.indd 28 04/04/2023 14:21:33
Output Voltage Frequency
3 kW 220V – 240V, 1 Phase 50 – 60 Hz
3.6 kW 220V – 240V, 1 Phase 50 – 60 Hz
4 kW 220V – 240V, 1 Phase 50 – 60 Hz
5 kW 220V – 240V, 1 Phase 50 – 60 Hz
6 kW 220V – 240V, 1 Phase 50 – 60 Hz
5 kW 380V – 415V, 3 Phase 50 – 60 Hz
6 kW 380V – 415V, 3 Phase 50 – 60 Hz
8 kW 380V – 415V, 3 Phase 50 – 60 Hz
10 kW 380V – 415V, 3 Phase 50 – 60 Hz
15 kW 380V – 415V, 3 Phase 50 – 60 Hz
20 kW 380V – 415V, 3 Phase 50 – 60 Hz
25 kW 380V – 415V, 3 Phase 50 – 60 Hz
50 kW 380V – 415V, 3 Phase 50 – 60 Hz
100 kW 380V – 415V, 3 Phase 50 – 60 Hz
150 kW 380V – 415V, 3 Phase 50 – 60 Hz
PV Inverter Options – CE Mark
27
RENEWABLE HYBRID SOLUTIONS
Output Voltage Frequency
3 kW 208V – 240V, 1 Phase 60 Hz
3.8 kW 208V – 240V, 1 Phase 60 Hz
5 kW 208V – 240V, 1 Phase 60 Hz
6 kW 208V – 240V, 1 Phase 60 Hz
7 kW 208V – 240V, 1 Phase 60 Hz
7.7 kW 208V – 240V, 1 Phase 60 Hz
33.3 kW 480V, 3 Phase 60 Hz
50 kW 480V, 3 Phase 60 Hz
62.5 kW 480V, 3 Phase 60 Hz
125 kW 480V, 3 Phase 60 Hz
150 kW 480V, 3 Phase 60 Hz
Note 1: Inverter products are not Cat branded.
Note 2: Check with local dealer for product availability which varies by region and delivery date.
PV Inverter Options – UL Listed
LEXE7582-18 Ratings Booklet Final.indd 29 04/04/2023 14:21:33
RENEWABLE HYBRID SOLUTIONS
28
Weather Stations
Weather Stations provide a pre-engineered system that cost-effectively scales to
Microgrid Solution size and complexity. The Weather station delivers best-practice
PV performance tracking and correlation technology.
Basic Features Class A Class B Class C
Plane of Array • • •
Back of Module Temperature • • •
Air Temperature • • •
Relative Humidity • • —
Wind Speed • • —
Wind Direction • • —
Barometric Pressure • • —
Global Horizontal Irradiance • — —
LEXE7582-18 Ratings Booklet Final.indd 30 04/04/2023 14:21:33
RENEWABLE HYBRID SOLUTIONS
29
MMC-M
The MMC-M is designed for applications with a
moderate number of power generation assets.
It integrates with the photovoltaic (PV) system,
generator set, and energy storage system.
The MMC-M provides intermediate
controls functionality.
MMC-Custom
The MMC-Custom is designed for applications
with a high number of power generation assets.
It integrates with the photovoltaic (PV) system,
generator set, and energy storage system. The
MMC-Custom provides advanced or specialized
controls functionality.
Microgrid Master Controllers (MMC)
MMC-S
The MMC-S is designed for applications with
a limited number of power generation assets.
It integrates the photovoltaic (PV) system,
generator set, and energy storage system.
It provides basic controls functionality.
LEXE7582-18 Ratings Booklet Final.indd 31 04/04/2023 14:21:34
30
RENEWABLE HYBRID SOLUTIONS
Microgrids & Renewable Energy Systems
Cat microgrids provide cost-effective power for on- and off-grid communities and
commercial or industrical installations. By combinining our advanced energy
storage solutions with renewable energy from photovoltaic solar modules and
traditional generation from utilities or generator sets, we can develop an energy
system specifically designed for your needs. The Cat microgrid combines all
sources into a single, controllable entity to optimize the flow of energy so it can be
produced at the lowest total cost.
Power Grid Stabilization (PGS)
Power Grid Stabilization modules provide a pre-engineered solution to energy
storage needs. The modules integrate with diesel or gas generator sets,
photovoltaic (PV), or other renewable systems to provide short duration power.
The module holds closely regulated system voltage and frequency during periods
of rapid load addition or removal, or during periods of intermittent output from
the renewables.
Model Nameplate Energy 15 Minutes Output 5 Second Output
PGS840 448 kWh 840 kW 840 kW
PGS1260 672 kWh 1170 kW 1260 kW
PGS1260 HD mobile 672 kWh 1170 kW 1260 kW
LEXE7582-18 Ratings Booklet Final.indd 32 04/04/2023 14:21:34
31
RENEWABLE HYBRID SOLUTIONS
Energy Time Shift (ETS)
Energy Time Shift modules provide a pre-engineered solution to energy storage
needs. The scalable system integrates with photovoltaic (PV) or other renewable
systems to store energy from renewables, generator sets, or the grid for use at a
later time. The ETS module contains the bi-directional power inverter with a fized
number of batteries and support equipment.
Model Nameplate Energy Continuous Output
ETS1500 1518 kWh 570 kW
ETS1500 1518 kWh 1000 kW*
*When paired with ECE below.
Energy Capacity Expansion (ECE)
The Energy Capacity Expansion modules provide increased energy capacity and
discharge duration when connected for use with the ETS module.
Model Energy
ECE1500 1518 kWh
ECE2000 2024 kWh
ECE2500 2530 kWh
LEXE7582-18 Ratings Booklet Final.indd 33 04/04/2023 14:21:35
LEXE7582-18 Ratings Booklet Final.indd 34 04/04/2023 14:21:35
EMCP 4
LEXE7582-18 Ratings Booklet Final.indd 35 04/04/2023 14:21:36
34
EMCP 4
EMCP 4.1
The EMCP 4.1 provides basic engine controls – stop/run/auto push button controls,
cycle crank, and cool down timer. The 3.8 inch graphical display supports multiple
languages, including character languages such as Chinese, Arabic, Russian,
and Japanese. The EMCP 4.1 provides monitoring of generator electrical output,
including AC voltage, current, frequency, and mechanical information such as oil
pressure, coolant temperature, engine speed, and battery voltage along with fuel
level if a sensor is provided. It also provides a number of protective functions, such
as warnings and shutdowns for over/under voltage, over/under frequency, low oil
pressure, high coolant temperature, low coolant level, failure to start, and overspeed.
EMCP 4.2
The EMCP 4.2 builds on the features of the EMCP 4.1 controller, offering
expanded engine monitoring based on information available from the engine
ECM, along with expanded generator set protection and monitoring, such
as generator kW, kVA, and kWh.
Flexibility is also increased with the addition of a modbus RTU communication
port, remote annunciator modules, and expansion I/O modules to allow the
EMCP 4 system to be configured to meet site specific design requirements.
With the additional monitoring and expansion modules available, the EMCP 4.2
is designed to provide control and protection for critical installations, such as
NFPA-110 Level 1 applications.
EMCP 4.2B
The EMCP 4.2B adds advanced features to the EMCP 4.2 controller, offering
expanded generator set protection and monitoring, such as additional overcurrent
protection curve selection, real (kW) load histogram, trip kWh and trip kVArh.
Display screens are configurable for customer desired parameters.
An integrated basic programmable logic control (PLC) function to read controller
inputs and drive controller outputs is also provided with the EMCP 4.2B.
LEXE7582-18 Ratings Booklet Final.indd 36 04/04/2023 14:21:36
35
EMCP 4
EMCP 4.3
The EMCP 4.3 further expands the EMCP 4 product line with the addition of
5.5 inch graphical display and additional context specific navigation keys.
With the addition of a Modbus TCP port, the EMCP 4.3 controller can be easily
integrated into complex systems requiring complete generator set monitoring.
EMCP 4.4
The EMCP 4.4 builds on the EMCP 4.3 functionality with the addition of fully
automatic multi generator set paralleling. The EMCP 4.4 provides all of the
functions required to automatically parallel generator sets, including dead
bus arbitration, automatic or manual modes of operation, and load sharing (real
and reactive). Optional provisions allow for extended parallel operation of a
single generator with Utility for Base Load/Import/Export capability.
Extended Service Coverage (ESC)
Since 2021, new EMCP replacements (i.e. from older EMCP to current versions)
performed by Cat dealers are covered by ESC, see excerpt from ESC Contract.
Platinum Level Covered Components: All as-shipped consist from
the factory with Caterpillar part numbers, including DOC (when DOC is
not part of a DPF) are Covered Components with the exception of the
following: DPF and SCR, filters, fluids, vee-belts, hoses, power take-offs,
paint, batteries, and clutches. New replacement EMCP control panels
with Cat part numbers installed on electric power generator sets by an
authorized dealer are covered components.
LEXE7582-18 Ratings Booklet Final.indd 37 04/04/2023 14:21:36
EMCP 4
Description EMCP 4.1 EMCP 4.2 EMCP 4.2B EMCP 4.3
EMCP 4.4
Standard (1G1U)
Operating Modes
Emergency Standby / Island Mode ● ● ● ● ● ●
Utility Paralleling – – – – – ●
System Capacity
Number of Units 1 1 1 1
8 –
Hardwired
16 –
MGDL
1
Voltages
Voltage ● ● ● ● ● ●
(208V – 15 kV)
Generator Paralleling Functions
Dead Bus Arbitration – – – – ● –
Synchronization – – – – ● ●
Load Sharing – – – – ● –
Load Sense / Load Demand
(LS / LD) – – – – ● –
LS / LD – Engine Hours Balancing – – – – ● –
Load Shed / Load Add Stages – – – – Up to 4
(Note 1) ●
Utility Paralleling Functions
Base Load Control – – – – ● ●
Load Management /
Peak Shaving (Utility) – – – – – ●
Utility Transfer / Control – – – – – ●
Utility Protection Relaying
(Industrial Grade) – – – – – ●
Product Features
Notes:
(1) Includes 1 fully featured load shed stage (feeder breaker control) plus 3 programmable generator set
kW-based load shed stages.
Other: Multi-Gen Data Link (MGDL).
KEY
● Standard
– Not Available
36
LEXE7582-18 Ratings Booklet Final.indd 38 04/04/2023 14:21:36
37
LEXE7582-18 Ratings Booklet Final.indd 39 04/04/2023 14:21:36
LEXE7582-18 Ratings Booklet Final.indd 40 04/04/2023 14:21:36
SYSTEMS
PRODUCTS
LEXE7582-18 Ratings Booklet Final.indd 41 04/04/2023 14:21:36
40
SYSTEMS PRODUCTS
Description
EMCP 4.4
SCP
Supervisory
Control
EMCP 4.4 Master Control Panel (EGP4) (EGP) (XLM)
PaAOperating Modes
Emergency Standby / Island Mode ● ● ● ● Utility Paralleling – – – ● System Capacity
Number of Units 16 4 8
(Standard)
8
(Standard) Voltages
Voltage ● ● ● ● (208V – 15 kV) Generator Paralleling Functions
Dead Bus Arbitration
(Note 1)
● ● ● Synchronization (Note 1) (Note 1) (Note 1) Load Sharing ● ● ● Load Sense / Load Demand
(LS / LD) ● ● ● LS / LD – Engine Hours Balancing ● ● ● Load Shed / Load Add Stages 16 4 8 8 Utility Paralleling Functions
Base Load Control – – – ● Load Management /
Peak Shaving (Utility) – – – ● Utility Transfer / Control – – – ● Utility Protection Relaying
(Industrial Grade) – – – ● Advanced Control
Notes:
(1) Function included as part of the system – performed by the EMCP 4.4 Generator Set Controller.
KEY
● Standard
– Not Available
Flexible control products and architectures for tailoring the performance of
Cat Electric Power sources to meet any application. Designed around
customer requirements or pre-configurable solutions.
LEXE7582-18 Ratings Booklet Final.indd 42 04/04/2023 14:21:37
EPIC CHP Controls and Switchgear
Modular Control
Panels Ideal for Adding
Additional Generation
Capacity
Combined Heat and
Power (CHP) Loop
System Controls
Configurable Controls
and Switchgear
with Standardized
Sequence of
Operations
Design to Order
Controls and
Switchgear with
Customizable
Sequence of
Operations
● – ● ●
● ● ● ●
)≤12 ≤12 ≤12 Unlimited
● ● ● ●
(208V – 38 kV)
● – ● ●
● ● ● ●
● – ● ●
● – ● ●
● – ● ●
12 – 12 Unlimited
– ● – –
● ● ● ●
● – ● ●
– ● ● ●
41
SYSTEMS PRODUCTS
LEXE7582-18 Ratings Booklet Final.indd 43 04/04/2023 14:21:37
SYSTEMS PRODUCTS
Paralleling Switchgear
Cat standard switchgear products can support a wide variety of applications,
or we can provide a custom Voltage designed system to meet your specific
project needs. The XLM product supports transfer between the utility source and
generator bus and allows for sustained parallel operation with the utility for load
management applications. The EGP product supports paralleling on an
Cat Switchgear Selector
Application
Guide Tab
Section
Voltage
Range
Parallel
Multiple
Gensets
Parallel
with
Utility
Standby
Applications
Transfer
Switches
EEmergency Generator Paralling Switchgear (EGP)
3
208-600V
UL 1558, UI 891
CSA
Arc Res 2B
● – ● ● 2.4-27 kV
ANSI C37.20.2
ANSI C37.20.3
UL MV, CSA
Arc Res 2B, 2C, 2BC
● – ● ● Transfer and Load Management Paralleling Switchgear (XLM)
4
208-600V
UL 1558, Ul 891
CSA
Arc Res 2B
● ● ● – 2.4-27 kV
ANSI C37.20.2
ANSI C37.20.3
UL MV, CSA
Arc Res 2B, 2C, 2BC
● ● ● – Additional Medium Voltage Features
5
2.4-27 kV
ANSI C37.20.2
ANSI C37.20.3
UL MV, CSA
Arc Res 2B, 2C, 2BC
● ● ● ● Custom Paralleling Switchgear Features
6
208V-27 kV
UL 1558
Ul 891
CSA
Arc Res 2B
ANSI C37.20.2
ANSI C37.20.3
UL MV, CSA
Arc Res 2B, 2C, 2BC
● ● ● ● 42
LEXE7582-18 Ratings Booklet Final.indd 44 04/04/2023 14:21:37
SYSTEMS PRODUCTS
er
es
Modes of Operation
Application Considerations
Emergency
Standby
Closed
Transition /
Soft Load
Peak
Shaving
Load
Shed /
Add
Control
Utility
Export
● – – ● – EGP product is used to parallel
multiple gensets to a common bus
where interconnect with the uility
is not required. EGP systems are
commonly used where there are
downstream transfer switches. ● – – ● –
● ● ● ● ● XLM Product is used when
generators will be paralleled with a
utility (Utility Breaker may be local
or remote). Allows closed transition
transfer to/from utility as well as
continuous paralleling.
● ● ● ● ●
● ● ● ● ●
Medium Voltage product utilize
vaccum circuit breakers. This
section covers equipment specific
to applications >600V.
● ● ● ● ●
Customize products are available to
meet the most demanding or unique
requirements including multiple
utilities, multiple ties, custom
sequence of operations, etc.
isolated generator bus and is commonly used in prime power or emergency
standby systems. Caterpillar switchgear is available in ratings from 600V through
27 kV and provides a solution able to combine all elements of monitoring and
control for Cat generator sets in a single-source package.
43
LEXE7582-18 Ratings Booklet Final.indd 45 04/04/2023 14:21:37
ATC Line
Product Amp Range Controllers
ATC – Contactor-type ATS 40A – 3000A ATC 300+ or 900
ATC – Power Breaker & Power Case-type ATS 200A – 5000A ATC 900
ATC – Molded Case-type ATS 30A – 1000A ATC 300+ or 900
ATC – Service Entrance Rated MCCB &
Power Breaker-type ATS 30A – 5000A ATC 300+ or 900
ATC – Contactor-type ATS with Bypass Isolation 100A – 3000A ATC 300+ or 900
ATC – Power Breaker-type ATS with Bypass Isolation 200A – 5000A ATC 900
SYSTEMS PRODUCTS
44
Product Amp Range Controllers
CX – Contactor-type ATS for light commercial
or residential 30A – 1200A TruOne L2 Type
CG – Contactor-type, Open Transition ATS for general
purpose applications 30A – 3000A TruOne L3 Type
CGD – Contactor-type, Delayed Transition ATS for
general purpose applications 30A – 3000A TruOne L3 Type
CS – Contactor-type, Open Transition ATS (Spec Grade) 30A – 3000A TruOne L4 Type
CSD – Contactor-type, Delayed Transition ATS
(Spec Grade) 30A – 3000A TruOne L4 Type
CSCT – Contactor-type, Closed Transition ATS
(Spec Grade) 400A – 3000A TruOne L4 Type
CBS – Contactor-type, Open Transition ATS w/ Bypass
Isolation (Spec Grade) 30A – 3000A TruOne L4 Type
CBSD – Contactor-type, Delayed Transition ATS
w/ Bypass Isolation (Spec Grade) 30A – 3000A TruOne L4 Type
CBSCT – Contactor-type, Closed Transition ATS w/
Bypass Isolation (Spec Grade) 1000A – 3000A TruOne L4 Type
TruOne & MX Line
ATS
Operating Modes:
• Open Transition
• Closed Transition
• Delayed Transition
• Bypass Isolation
LEXE7582-18 Ratings Booklet Final.indd 46 04/04/2023 14:21:37
SYSTEMS PRODUCTS
45
Product Amp Range Enclosures Controllers
Lug-to-Lug Tap
Box 200A – 3000A NEMA3R Lugs Only
Wallmount
Camlock Tap Box 400A – 2400A NEMA3R or NEMA3R
316 Stainless Male or Female
Free Standing
Camlock Tap Box 1600A – 4000A NEMA3R or NEMA3R
316 Stainless Male or Female
Enclosed Circuit
Breaker Box 200A – 800A NEMA3R, 4X Stainless Male or Female
Temporary Generator Connections
Features:
• UL508A
• Visual indication of L-L voltage (3 phase)
• Color Coded Cam-Locks
• Selectable Cam-Lock receptacle gender or mechanical lug connection
to generator
• Available Phase Rotation, Loss and Undervoltage Protection
• Padlockable Wingnob latch
• Density rated (1000A/in2
) bus
• Mechanically Interlocked access doors
Functions:
• Provides simple connection of temporary generator or load bank
• Provides for permanent lug or circuit breaker connection to building
distribution equipment
• Weatherproof enclosures with temporary generator cable access doors
LEXE7582-18 Ratings Booklet Final.indd 47 04/04/2023 14:21:37
LEXE7582-18 Ratings Booklet Final.indd 48 04/04/2023 14:21:38
CAT®
CONNECT AND
PRODUCT SUPPORT
LEXE7582-18 Ratings Booklet Final.indd 49 04/04/2023 14:21:38
48
CAT CONNECT
Technologies and Services
Caterpillar’s connectivity solution of Remote Asset Monitoring with Cat® Connect
turns data into insights and insights into profits.
Customer Benefits:
• Monitor and manage your assets from any location on any device
• Decrease owning and operating costs
• Boost efficiency
• Increase uptime
• Improve safety
• Meet sustainability goals
• Reduce risk
Key Features:
• Customized alerts
• View your asset’s: status, location, current faults, and engine & electrical
parameters
• Manage maintenance
• Geofencing
• Remote start/stop
• Storm preparedness
• Condition monitoring (CVA connected customers)
• View, see and compare all your assets on one screen
• Fleet Performance enabled by reports & analytics
LEXE7582-18 Ratings Booklet Final.indd 50 04/04/2023 14:21:38