安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
自动跟踪定位射流灭火装置
ZDMS0.6/10S-HA-Q2(自动炮)
[安装使用说明书]
(HA.2019.10.31 V1.0)
无锡皓安安全技术有限公司
Wuxi haoan safety technology co., ltd
江苏省无锡市滨湖区胡埭路 8 号
目录
一、概述···························································································································1
系统组成················································································································1
设计与分布·············································································································1
二、产品安装设计及参数···································································································2
外观及技术参数··········································································································2
安装方式·····················································································································2
安装部件·····················································································································2
安装使用说明 ············································································································2
三、配套设施·····················································································································3
智能扫描灭火装置···································································································3
区域控制箱··············································································································4
电源解码器··············································································································4
手动控制盘··············································································································5
末端试水·················································································································5
四、产品调试及接线··········································································································6
五、注意事项·····················································································································6
第1页共 6 页
第一章 公司、产品概述
无锡皓安安全技术有限公司是一家专业从事消防产品的研发、生产、销售和服务于一体的现代化科技型企业。公司座落在中国
最具活力的长三角经济区-无锡经济开发区(滨湖区胡埭镇),苏南国际机场、京沪高速、沪宜高速、京沪高铁、沪宁城际、京杭大
运河均近在咫尺;现有员工 160 余名,其中工程技术人员 30 余人;公司产品包括自动跟踪定位射流灭火装置、防火门监控系统、
防火门消防联动相关配件等,成功地开发研制出多项高科技消防产品,所有产品均通过了国家消防电子产品检测中心的检测认证。
公司拥有专业的设备安装与调试队伍,建立了比较完善的销售服务体系,配备知识型高素质人员、售后服务人员、能为用户提
供完善的售前及售后服务;皓安是我们的品牌寄托,保障人民生命安全是我们的宗旨,我们秉承与时俱进的理念,用在最先进、最
稳定的技术和产品服务于人民和社会。
自动跟踪定位射流灭火装置系列产品是皓安公司自主研发生产的集报警、灭火于一体的新一代高科技消防产品。该系列产品将
红外/紫外传感器、计算机通信技术有机集合起来,具有主动探测火源、自动定位、对火点实施定点射水灭火,火灭后自动复位,
如有复燃,重新启动的特点,特别适用于大空间场所的灭火需求。产品方便安装,安装与维护费用低,节约水资源,最大程度的减
小了灭火后照成射水带来的危害,具有很高的性价比。
本系列产品广泛应用于:大型商场、会展中心、机场、火车站、汽车站、办公楼、医院、图书馆、电影院、体育馆、厂房、仓
库等空间大、楼间隔高的场所。
系统组成:
1.水系统:主要由蓄水池、消防水泵、电子流量计、管路、手动阀门、水流指示器、电磁(动)阀等组成,其目的在于能给装
置提供快速、充足的水源。
2.电系统:主要由灭火装置、电源解码器、手动控制盘、区域控制箱、控制主机(柜式、琴台),可灵活实现手动、自动以及现
场、消防中心的各种操作。有效完成从发现火灾直至灭火等一系列动作。
设计与分布
单排: 双排:
L=2×√(R×R-b×b) L=√2×R=1.414R
R 为装置保护半径 ,b 为实际需要保护半径 1/2 R 为装置保护半径 ,L 为装置距离
L 为装置距离
交叉:
L=(√3/2R)(2N-1)= (2N-1)0.866R
R 为装置保护半径,L 为装置距离,N 为装置每行用装置个数
第2页共 6 页
第二章 产品安装设计及参数
1、外观及技术参数 技术参数:
ZDMS0.6/10S-HA-Q2
注:5L/10L 自动跟踪定位射流灭火装置均带视频摄像头
2、安装方式
2.1 楼板或架空安装,如下图所示:
2.2 吊顶安装,如下图所示:
安装高度 6-15m 接口 DN32 法兰
执行标准号 GB25204-2010 俯仰角度 -90°~+30°
最大保护半径 35m 水平角度 0°~360°
射流半径 39m 通讯方式 CAN 总线
射水流量 10L/S 进水口口径 Φ32mm
工作压力 0.6MPa 出水口口径 Φ22mm
定位时间 ≤30s 装置自重 约 7.6KG
配接线束 12 芯航空线束 喷水方式 直射往复摆动
配套控制产品
灭火装置控制器 HA-P2000G
区域控制箱 HA-QKX1011
电源解码器 HA-JMQ1002A
火灾探测方式 水平垂直探测组件 HA-IR30
安装方式与边距
吊装;中心体距墙体≥300mm,
距吊顶≥300mm
第3页共 6 页
3、安装部件
3.1 闸阀
闸阀安装在配水管末端。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接
后应将连接处外部清理干净,闸阀的扳手部分应安装在管网上方。
3.2 电磁阀
电磁阀安装在闸阀后面管径为 DN50,中间用长 50~100mm 热镀锌管连接。电磁阀应安装在水平管段上,且保证水流方向要与
阀体的指示方向一致。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接后应将
连接处外部清理干净。电磁阀应安装在管网上方,应选用 AC220V 电源供电,电磁阀电源线应串入电源解码器接点使用,并作防水
处理。
4、安装使用说明
灭火装置的安装应按照国标喷水灭火系统设计、施工规范进行,各省、地方有自行规定的按自行规定安装。将灭火装置与管网
接口连接,固定灭火装置时注意按照规程操作。灭火装置连接线需用本公司原厂自带 12 芯航空线束与电源解码器相连接,并拧紧
螺帽。灭火装置安装牢固后通电,通电后灭火装置会自动复位,待复位后观察灭火装置底部红色运行指示灯是否闪烁(如不能复位
请安装人员现场联系调试人员),如果状态正常及安装完毕。
第三章 配套设备
智能扫描灭火装置控制器
智能扫描灭火装置控制器是自动跟踪定位射流灭火系统的信息处理和控制核心,采用可靠性高 CAN 总线结构设计,集火警自动
报警、自动跟踪定位射流灭火、联动控制、图像监控于一体,并能与其他报警系统协议联网,控制器内部采用模块化设计,方便系
统兼容,抗干扰能力强大,通讯距离更远,操作维护更方便等优点。
HA-P2000G
性能特点:
CAN 总线通讯,可对现场区域控制箱进行手、自动转换,视屏切换
具备远程启停水泵、开关电磁阀的控制功能,实现对灭火装置的集中控制
配合视屏监控主机,远程控制灭火装置的启动、上下左右精准定位旋转,手动控制灭火装置对火源进行灭火
报警及扫描定位历史记录功能
现场图像显示、切换、记录功能
口令管理功能
故障检测功能
主要技术参数:
工作电压 AC220V 手/自动转换 有
通讯方式 CAN 地址编码 遥控编码
通讯距离 ≤1000m 装置远程控制 有
视频监控 有 水泵启停 有
报警记录 有 系统巡检: 有
电磁阀远程控制 有 外形尺寸 1717x550x480
第4页共 6 页
区域控制箱
区域控制箱是自动跟踪定位射流灭火系统的前端操作设备。其具有能够灵活设置灭火装置,手、自动控制功能切换、指示现场
灭火装置工作状态、设置灭火装置参数等功能,可与我公司所有产品配套使用,具有体积小、功能全、操作简单等特点。
HA-QKX1011
主要技术参数:
输入电压 AC220V/50Hz 通讯距离 ≤1000m
输出电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 外观尺寸 295x230x70
接入容量 32 台灭火装置 安装方式 水平安装距地 1.5m
性能特点:
4.3 寸 LCD 液晶彩色显示屏 灵活设置灭火装置的参数
实时显示电动阀及灭火装置的工作状态 设有 1、2、3 级用户权限,防止误操作
具有电磁阀手、自动控制功能 远程控制消防水泵启停动作
电源解码器
HA-JMQ1002A 型电源解码器是自动跟踪定位射流灭火系统的前端控制设备,与灭火装置配合使用。通过 CAN 总线实现与区域控
制箱、灭火装置控制器的实时数据传输,能够接收灭火装置控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟踪扫描
定位火源,控制电磁(动)阀启闭,接受灭火装置、电磁(动)阀的动作反馈信号,并传输给灭火装置控制器。
HA-JMQ1002A
主要技术参数:
输入电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
输出电压 DC24V 启阀输出功率 DC24V/2A
通讯方式 CAN 总线 外观尺寸 230x170x53
性能特点:
CAN 总线通讯,实现对电磁阀逻辑联动控制。
视频一体式集成功能,布线简洁。
电磁阀启阀双向逻辑输出,稳定性更强。
第5页共 6 页
手动控制盘
采用单片机控制,直接操作。它是通过 CAN 总线对最多 32 台消防炮进行现场控制,通过 CAN 总线与控制主机进行通讯,实
现远程操作和控制,与自动跟踪定位消防炮灭火装置配套使用。
HA-SKP1003A
主要技术参数:
输入电压 DC24V 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 安装方式 水平安装距地 1.5m
容量 可控制 32 台灭火装置 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,布线简洁,安装方便。
就地启动灭火装置自动寻火。
就地控制灭火装置上下左右移位,联锁对应电源解码器开启电动阀。
就地控制灭火装置的喷水方式。
末端试水
第6页共 6 页
第四章 产品接线及调试
灭火装置在通电之前应必须检查下联动柜、区域控制箱、手动控制盘、电源解码器之间的接线是否正确,区
域控制箱到电源解码器的接线:
电源解码器接线端子
装置电源输入: AC220V L、N、E(火、零、地线)
启阀电源输入: AC220V L、N (火、零)
启阀电源输出: AC220V L、N (火、零)
启泵接点:泵房启泵线或开关量输出(无源信号)
CANH/CANL:CAN 通讯线输入(注意高低极性)
外部启动:第三方火警启动输入信号(无源信号)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电磁阀无回答信号线时,需将启泵接点与电磁阀反馈接口短接,不短接的话,开阀动作后控制器及区控箱会报阀反馈故障。
整机调试:
a)通电后炮管垂直 45°向下运动到限位点,5s 后灭火装置主程序复位,此时灭火装置处于待命状态。
b)短接电源解码器的端子排外部启动(模拟火灾信号)启动灭火装置,灭火装置水平顺时针旋转。
c)灭火装置水平旋转时可用模拟火源(如打火机)在灭火装置水平传感器前点火,灭火装置应水平定位。
d)灭火装置水平定位后可在垂直传感器前点火,灭火装置应垂直定位。
e)灭火装置垂直定位 3s 后发出报警声,炮管喷水并做上下左右往复运动。
通过以上调试,无异常发生后方可交付验收。
灭火装置精准度补偿调试:
本公司所有产品均为厂里调试好后出厂销售,如需调整请联系现场技术员或直接与本公司技术部沟通。
第五章 注意事项
1. 在开机前必须检查线路无问题,切勿短路、开路、错接等。
2. 本机需由经专业培训人员进行维护、维修,严禁他人随意操作。
3. 我公司负责本产品的维修,发现问题时请及时与我公司技术服务中心联系,用户不得擅自开箱维修,否则后果自负。
4. 在安装前应进行功能检查,避免为运输过程中造成损坏的设备。
5. 严禁带电拆装各电路连接线和信号线,所有的操作均需在断电关机情况下进行。
6. 外壳、电源部分和外接导线的金属软管应作接地保护。
7. 本产品保修期为 12 个月,如在一年内出现非人为损坏的情况请即与本公司或者经销单位联系。
从本公司购买设备者,自本公司发运日期起计算;从经销部门购买者,以经销单位发运日起计算,整机保修为 12 个月
安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
自动跟踪定位射流灭火装置
ZDMS0.8/20S-HA-Q2(自动炮)
[安装使用说明书]
(HA.2019.10.31 V1.0)
无锡皓安安全技术有限公司
Wuxi haoan safety technology co., ltd
江苏省无锡市滨湖区胡埭路 8 号
目录
一、概述···························································································································1
系统组成················································································································1
设计与分布·············································································································1
二、产品安装设计及参数···································································································2
外观及技术参数··········································································································2
安装方式·····················································································································2
安装部件·····················································································································2
安装使用说明 ············································································································2
三、配套设施·····················································································································3
智能扫描灭火装置···································································································3
区域控制箱··············································································································4
电源解码器··············································································································4
手动控制盘··············································································································5
末端试水·················································································································5
四、产品调试及接线··········································································································6
五、注意事项·····················································································································6
第1页共 6 页
第一章 公司、产品概述
无锡皓安安全技术有限公司是一家专业从事消防产品的研发、生产、销售和服务于一体的现代化科技型企业。公司座落在中国
最具活力的长三角经济区-无锡经济开发区(滨湖区胡埭镇),苏南国际机场、京沪高速、沪宜高速、京沪高铁、沪宁城际、京杭大
运河均近在咫尺;现有员工 160 余名,其中工程技术人员 30 余人;公司产品包括自动跟踪定位射流灭火装置、防火门监控系统、
防火门消防联动相关配件等,成功地开发研制出多项高科技消防产品,所有产品均通过了国家消防电子产品检测中心的检测认证。
公司拥有专业的设备安装与调试队伍,建立了比较完善的销售服务体系,配备知识型高素质人员、售后服务人员、能为用户提
供完善的售前及售后服务;皓安是我们的品牌寄托,保障人民生命安全是我们的宗旨,我们秉承与时俱进的理念,用在最先进、最
稳定的技术和产品服务于人民和社会。
自动跟踪定位射流灭火装置系列产品是皓安公司自主研发生产的集报警、灭火于一体的新一代高科技消防产品。该系列产品将
红外/紫外传感器、计算机通信技术有机集合起来,具有主动探测火源、自动定位、对火点实施定点射水灭火,火灭后自动复位,
如有复燃,重新启动的特点,特别适用于大空间场所的灭火需求。产品方便安装,安装与维护费用低,节约水资源,最大程度的减
小了灭火后照成射水带来的危害,具有很高的性价比。
本系列产品广泛应用于:大型商场、会展中心、机场、火车站、汽车站、办公楼、医院、图书馆、电影院、体育馆、厂房、仓
库等空间大、楼间隔高的场所。
系统组成:
1.水系统:主要由蓄水池、消防水泵、电子流量计、管路、手动阀门、水流指示器、电磁(动)阀等组成,其目的在于能给装
置提供快速、充足的水源。
2.电系统:主要由灭火装置、电源解码器、手动控制盘、区域控制箱、控制主机(柜式、琴台),可灵活实现手动、自动以及现
场、消防中心的各种操作。有效完成从发现火灾直至灭火等一系列动作。
设计与分布
单排: 双排:
L=2×√(R×R-b×b) L=√2×R=1.414R
R 为装置保护半径 ,b 为实际需要保护半径 1/2 R 为装置保护半径 ,L 为装置距离
L 为装置距离
交叉:
L=(√3/2R)(2N-1)= (2N-1)0.866R
R 为装置保护半径,L 为装置距离,N 为装置每行用装置个数
第2页共 6 页
第二章 产品安装设计及参数
1、外观及技术参数 技术参数
ZDMS0.8/20S-HA-Q2
注:20L/30L 自动跟踪定位射流灭火装置均带视频摄像头
2、安装方式
2.1 楼板或架空安装,如下图所示:
2.2 坐式安装,如下图所示:
注意:坐装式消防炮订货时需特别标明。
安装高度 8-15m 接口法兰 DN80
执行标准号 GB25204-2010 俯仰角度 -90°~+30°
最大保护半径 50m 水平角度 0°~360°
射流半径 56m 通讯方式 CAN 总线
射水流量 20L/S 进水口口径 Φ58mm
工作压力 0.8MPa 出水口口径 Φ42mm
定位时间 ≤60s 装置自重 约 19KG
配接线束 12 芯航空线束 喷水方式 直射往复摆动
配套控制产品
灭火装置控制器 HA-P2000G
区域控制箱 HA-QKX1011
电源解码器 HA-JMQ1012A
手动控制盘 HA-SKP1013A
火灾探测方式 水平垂直探测组件 HA-IR30
安装方式与边距
吊 装 ; 法 兰 中 心 体 距 墙 体 ≥
600mm,距吊顶≥600mm
第3页共 6 页
3、安装部件
3.1 检修阀(闸阀)
闸阀安装在配水管末端。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接
后应将连接处外部清理干净,闸阀的扳手部分应安装在管网上方。
3.2 电动阀
电动阀安装在闸阀后面管径为 DN80,中间用长 50~100mm 热镀锌管连接。电动阀应安装在水平管段上,且保证水流方向要与
阀体的指示方向一致。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接后应将
连接处外部清理干净。电动阀应安装在管网上方,应选用 DC24V 电源供电,电动阀电源线应串入电源解码器接点使用,并作防水处
理。
3.3 水流指示器
水流指示器应安装在电动阀前面,接口直径为 DN80。
4、安装使用说明及示意图
灭火装置的安装应按照国标喷水灭火系统设计、施工规范进行,各省、地方有自行规定的按自行规定安装。将灭火装置与管网
法兰连接,固定灭火装置时注意按照规程操作。灭火装置连接线需用本公司原厂自带 12 芯航空线束与电源解码器相连接,并拧紧
螺帽。灭火装置安装牢固后通电,通电后灭火装置会自动复位,待复位后观察灭火装置红色运行指示灯是否闪烁(如工作不正常请
及时联系现场调试人员),如果状态正常及安装完毕,安装布线示意图如下:
第三章 配套设备
智能扫描灭火装置控制器
智能扫描灭火装置控制器是自动跟踪定位射流灭火系统的信息处理和控制核心,采用可靠性高 CAN 总线结构设计,集火警自动
报警、自动跟踪定位射流灭火、联动控制、图像监控于一体,并能与其他报警系统协议联网,控制器内部采用模块化设计,方便系
统兼容,抗干扰能力强大,通讯距离更远,操作维护更方便等优点。
HA-P2000G
性能特点:
CAN 总线通讯,可对现场区域控制箱进行手、自动转换,视屏切换
具备远程启停水泵、开关电磁阀的控制功能,实现对灭火装置的集中控制
配合视屏监控主机,远程控制灭火装置的启动、上下左右精准定位旋转,手动控制灭火装置对火源进行灭火
报警及扫描定位历史记录功能
现场图像显示、切换、记录功能
口令管理功能,故障检测功能
主要技术参数:
工作电压 AC220V 手/自动转换 有
通讯方式 CAN 地址编码 遥控编码
通讯距离 ≤1000m 装置远程控制 有
视频监控 有 水泵启停 有
报警记录 有 系统巡检: 有
电磁阀远程控制 有 外形尺寸 1717x550x480
第4页共 6 页
区域控制箱
区域控制箱是自动跟踪定位射流灭火系统的前端操作设备。其具有能够灵活设置灭火装置,手、自动控制功能切换、指示现场
灭火装置工作状态、设置灭火装置参数等功能,可与我公司所有产品配套使用,具有体积小、功能全、操作简单等特点。
HA-QKX1011
主要技术参数:
输入电压 AC220V/50Hz 通讯距离 ≤1000m
输出电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 外观尺寸 295x230x70
接入容量 32 台灭火装置 安装方式 水平安装距地 1.5m
性能特点:
4.3 寸 LCD 液晶彩色显示屏 灵活设置灭火装置的参数
实时显示电动阀及灭火装置的工作状态 设有 1、2、3 级用户权限,防止误操作
具有电磁阀手、自动控制功能 远程控制消防水泵启停动作
电源解码器
电源解码器是自动跟踪定位射流灭火系统的前端控制设备,与灭火装置配合使用。通过 CAN 总线实现与区域控制箱、灭火装置
控制器的实时数据传输,能够接收灭火装置控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟踪扫描定位火源,控制
电磁(动)阀启闭,接受灭火装置、电磁(动)阀的动作反馈信号,并传输给灭火装置控制器。
HA-JMQ1012
主要技术参数:
输入电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
输出电压 DC24V 启阀输出功率 DC24V/3.5A
通讯方式 CAN 总线 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,实现对电动阀逻辑联动控制。
视频一体式集成功能,布线简洁。
电动阀启阀双向逻辑输出,稳定性更强。
第5页共 6 页
手动控制盘
采用单片机控制,直接控制操作;通过 CAN 总线对最多 32 台灭火装置进行现场控制,通过 CAN 总线与控制主机进行通讯,
实现远程操作和控制,与自动跟踪定位消防炮灭火装置配套使用。
HA-SKP1013A
主要技术参数:
输入电压 DC24V(无极性) 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 安装方式 水平安装距地 1.5m
容量 可控制 32 台灭火装置 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,布线简洁,安装方便。
就地启动灭火装置自动寻火。
就地控制灭火装置上下左右移位,联锁对应解码器开启电动阀。
就地控制灭火装置的喷水方式。
末端试水
第6页共 6 页
第四章 产品接线及调试
设备在通电之前应必须检查下联动柜、区域控制箱、手动控制盘、电源解码器之间的连线是否正确。
区域控制箱到电源解码器的接线:
电源解码器接线端子
电源解码器与电动阀的接线:
装置电源输入: AC220V L、N、E(火、零、地线)
启阀电源输出: DC24V (端子左侧正极、右侧负极)
启泵接点:泵房启泵线或开关量输出(无源信号)
CANH/CANL:CAN 通讯线输入(注意高低极性)
外部启动:第三方火警启动输入信号(无源信号)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电磁阀无回答信号线时,需将启泵接点与电磁阀反馈接口短接,不短接的话,开阀动作后控制器及区控箱会报阀反
馈故障
整机调试:
a)通电后炮管垂直 45°向下运动到限位点,5s 后灭火装置主程序复位,此时灭火装置处于待命状态。
b)短接电源解码器的端子排外部启动(模拟火灾信号)启动灭火装置,灭火装置水平顺时针旋转。
c)灭火装置水平旋转时可用模拟火源(如打火机)在灭火装置水平传感器前点火,灭火装置应水平定位。
d)灭火装置水平定位后可在垂直传感器前点火,灭火装置应垂直定位。
e)灭火装置垂直定位 3s 后发出报警声,炮管喷水并做上下左右往复运动。
通过以上调试,无异常发生后方可交付验收。
灭火装置精准度补偿调试:
本公司所有产品均为厂里调试好后出厂销售,如需调整请联系现场技术员或直接与本公司技术部沟通。
第五章 注意事项
1. 在开机前必须检查线路无问题,切勿短路、开路、错接等。
2. 本机需由经专业培训人员进行维护、维修,严禁他人随意操作。
3. 我公司负责本产品的维修,发现问题时请及时与我公司技术服务中心联系,用户不得擅自开箱维修,否则后果自负。
4. 在安装前应进行功能检查,避免为运输过程中造成损坏的设备。
5. 严禁带电拆装各电路连接线和信号线,所有的操作均需在断电关机情况下进行。
6. 外壳、电源部分和外接导线的金属软管应作接地保护。
7. 本产品保修期为 12 个月,如在一年内出现非人为损坏的情况请即与本公司或者经销单位联系。
从本公司购买设备者,自本公司发运日期起计算;从经销部门购买者,以经销单位发运日起计算,整机保修为 12 个月
安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
自动跟踪定位射流灭火装置
ZDMS0.9/30S-HA-G2(自动炮)
[安装使用说明书]
(HA.2019.10.31 V1.0)
无锡皓安安全技术有限公司
Wuxi haoan safety technology co., ltd
江苏省无锡市滨湖区胡埭路 8 号
目录
一、概述···························································································································1
系统组成················································································································1
设计与分布·············································································································1
二、产品安装设计及参数···································································································2
外观及技术参数··········································································································2
安装方式·····················································································································2
安装部件·····················································································································2
安装使用说明 ············································································································2
三、配套设施·····················································································································3
智能扫描灭火装置···································································································3
区域控制箱··············································································································4
电源解码器··············································································································4
手动控制盘··············································································································5
末端试水·················································································································5
四、产品调试及接线··········································································································6
五、注意事项·····················································································································6
第1页共 6 页
第一章 公司、产品概述
无锡皓安安全技术有限公司是一家专业从事消防产品的研发、生产、销售和服务于一体的现代化科技型企业。公司座落在中国
最具活力的长三角经济区-无锡经济开发区(滨湖区胡埭镇),苏南国际机场、京沪高速、沪宜高速、京沪高铁、沪宁城际、京杭大
运河均近在咫尺;现有员工 160 余名,其中工程技术人员 30 余人;公司产品包括自动跟踪定位射流灭火装置、防火门监控系统、
防火门消防联动相关配件等,成功地开发研制出多项高科技消防产品,所有产品均通过了国家消防电子产品检测中心的检测认证。
公司拥有专业的设备安装与调试队伍,建立了比较完善的销售服务体系,配备知识型高素质人员、售后服务人员、能为用户提
供完善的售前及售后服务;皓安是我们的品牌寄托,保障人民生命安全是我们的宗旨,我们秉承与时俱进的理念,用在最先进、最
稳定的技术和产品服务于人民和社会。
自动跟踪定位射流灭火装置系列产品是皓安公司自主研发生产的集报警、灭火于一体的新一代高科技消防产品。该系列产品将
红外/紫外传感器、计算机通信技术有机集合起来,具有主动探测火源、自动定位、对火点实施定点射水灭火,火灭后自动复位,
如有复燃,重新启动的特点,特别适用于大空间场所的灭火需求。产品方便安装,安装与维护费用低,节约水资源,最大程度的减
小了灭火后照成射水带来的危害,具有很高的性价比。
本系列产品广泛应用于:大型商场、会展中心、机场、火车站、汽车站、办公楼、医院、图书馆、电影院、体育馆、厂房、仓
库等空间大、楼间隔高的场所。
系统组成:
1.水系统:主要由蓄水池、消防水泵、电子流量计、管路、手动阀门、水流指示器、电磁(动)阀等组成,其目的在于能给装
置提供快速、充足的水源。
2.电系统:主要由灭火装置、电源解码器、手动控制盘、区域控制箱、控制主机(柜式、琴台),可灵活实现手动、自动以及现
场、消防中心的各种操作。有效完成从发现火灾直至灭火等一系列动作。
设计与分布
单排: 双排:
L=2×√(R×R-b×b) L=√2×R=1.414R
R 为装置保护半径 ,b 为实际需要保护半径 1/2 R 为装置保护半径 ,L 为装置距离
L 为装置距离
交叉:
L=(√3/2R)(2N-1)= (2N-1)0.866R
R 为装置保护半径,L 为装置距离,N 为装置每行用装置个数
第2页共 6 页
第二章 产产品安装设计及参数
1、外观及技术参数 技术参数:
ZDMS0.9/30S-HA-G2
注:20L/30L 自动跟踪定位射流灭火装置均带视频摄像头
2、安装方式
2.1 楼板或架空安装,如下图所示:
2.2 坐式安装,如下图所示:
注意:坐装式消防炮订货时需特别标明。
安装高度 8-15m 接口法兰 DN80
执行标准号 GB25204-2010 俯仰角度 -90°~+30°
最大保护半径 55m 水平角度 0°~360°
射流半径 62m 通讯方式 CAN 总线
射水流量 30L/S 进水口口径 Φ58mm
工作压力 0.9MPa 出水口口径 Φ56mm
定位时间 ≤60s 装置自重 约 20.8KG
配接线束 12 芯航空线束 喷水方式 直射往复摆动
配套控制产品
灭火装置控制器 HA-P2000G
区域控制箱 HA-QKX1011
电源解码器 HA-JMQ1012A
手动控制盘 HA-SKP1013A
火灾探测方式 水平垂直探测组件 HA-IR30
安装方式与边距
吊 装 ; 法 兰 中 心 体 距 墙 体 ≥
600mm,距吊顶≥600mm
第3页共 6 页
3、安装部件
3.1 检修阀(闸阀)
闸阀安装在配水管末端。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接
后应将连接处外部清理干净,闸阀的扳手部分应安装在管网上方。
3.2 电动阀
电动阀安装在闸阀后面管径为 DN80,中间用长 50~100mm 热镀锌管连接。电动阀应安装在水平管段上,且保证水流方向要与
阀体的指示方向一致。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接后应将
连接处外部清理干净。电动阀应安装在管网上方,应选用 DC24V 电源供电,电动阀电源线应串入电源解码器接点使用,并作防水处
理。
3.3 水流指示器
水流指示器应安装在电动阀前面,接口直径为 DN80。
4、安装使用说明及示意图
灭火装置的安装应按照国标喷水灭火系统设计、施工规范进行,各省、地方有自行规定的按自行规定安装。将灭火装置与管网
法兰连接,固定灭火装置时注意按照规程操作。灭火装置连接线需用本公司原厂自带 12 芯航空线束与电源解码器相连接,并拧紧
螺帽。灭火装置安装牢固后通电,通电后灭火装置会自动复位,待复位后观察灭火装置红色运行指示灯是否闪烁(如工作不正常请
及时联系现场调试人员),如果状态正常及安装完毕,安装布线示意图如下:
第三章 配套设备
智能扫描灭火装置控制器
智能扫描灭火装置控制器是自动跟踪定位射流灭火系统的信息处理和控制核心,采用可靠性高 CAN 总线结构设计,集火警自动
报警、自动跟踪定位射流灭火、联动控制、图像监控于一体,并能与其他报警系统协议联网,控制器内部采用模块化设计,方便系
统兼容,抗干扰能力强大,通讯距离更远,操作维护更方便等优点。
HA-P2000G
性能特点:
CAN 总线通讯,可对现场区域控制箱进行手、自动转换,视屏切换
具备远程启停水泵、开关电磁阀的控制功能,实现对灭火装置的集中控制
配合视屏监控主机,远程控制灭火装置的启动、上下左右精准定位旋转,手动控制灭火装置对火源进行灭火
报警及扫描定位历史记录功能
现场图像显示、切换、记录功能
口令管理功能,故障检测功能
主要技术参数:
工作电压 AC220V 手/自动转换 有
通讯方式 CAN 地址编码 遥控编码
通讯距离 ≤1000m 装置远程控制 有
视频监控 有 水泵启停 有
报警记录 有 系统巡检: 有
电磁阀远程控制 有 外形尺寸 1717x550x480
第4页共 6 页
区域控制箱
区域控制箱是自动跟踪定位射流灭火系统的前端操作设备。其具有能够灵活设置灭火装置,手、自动控制功能切换、指示现场
灭火装置工作状态、设置灭火装置参数等功能,可与我公司所有产品配套使用,具有体积小、功能全、操作简单等特点。
HA-QKX1011
主要技术参数:
输入电压 AC220V/50Hz 通讯距离 ≤1000m
输出电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 外观尺寸 295x230x70
接入容量 32 台灭火装置 安装方式 水平安装距地 1.5m
性能特点:
4.3 寸 LCD 液晶彩色显示屏 灵活设置灭火装置的参数
实时显示电动阀及灭火装置的工作状态 设有 1、2、3 级用户权限,防止误操作
具有电磁阀手、自动控制功能 远程控制消防水泵启停动作
电源解码器
电源解码器是自动跟踪定位射流灭火系统的前端控制设备,与灭火装置配合使用。通过 CAN 总线实现与区域控制箱、灭火装置
控制器的实时数据传输,能够接收灭火装置控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟踪扫描定位火源,控制
电磁(动)阀启闭,接受灭火装置、电磁(动)阀的动作反馈信号,并传输给灭火装置控制器。
HA-JMQ1012
主要技术参数:
输入电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
输出电压 DC24V 启阀输出功率 DC24V/3.5A
通讯方式 CAN 总线 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,实现对电动阀逻辑联动控制。
视频一体式集成功能,布线简洁。
电动阀启阀双向逻辑输出,稳定性更强。
第5页共 6 页
手动控制盘
采用单片机控制,直接控制操作;通过 CAN 总线对最多 32 台灭火装置进行现场控制,通过 CAN 总线与控制主机进行通讯,
实现远程操作和控制,与自动跟踪定位消防炮灭火装置配套使用。
HA-SKP1013A
主要技术参数:
输入电压 DC24V(无极性) 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 安装方式 水平安装距地 1.5m
容量 可控制 32 台灭火装置 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,布线简洁,安装方便。
就地启动灭火装置自动寻火。
就地控制灭火装置上下左右移位,联锁对应解码器开启电动阀。
就地控制灭火装置的喷水方式。
末端试水
第6页共 6 页
第四章 产品接线及调试
设备在通电之前应必须检查下联动柜、区域控制箱、手动控制盘、电源解码器之间的连线是否正确。
区域控制箱到电源解码器的接线:
电源解码器接线端子
电源解码器与电动阀的接线:
装置电源输入: AC220V L、N、E(火、零、地线)
启阀电源输出: DC24V (端子左侧正极、右侧负极)
启泵接点:泵房启泵线或开关量输出(无源信号)
CANH/CANL:CAN 通讯线输入(注意高低极性)
外部启动:第三方火警启动输入信号(无源信号)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电磁阀无回答信号线时,需将启泵接点与电磁阀反馈接口短接,不短接的话,开阀动作后控制器及区控箱会报阀反
馈故障
整机调试:
a)通电后炮管垂直 45°向下运动到限位点,5s 后灭火装置主程序复位,此时灭火装置处于待命状态。
b)短接电源解码器的端子排外部启动(模拟火灾信号)启动灭火装置,灭火装置水平顺时针旋转。
c)灭火装置水平旋转时可用模拟火源(如打火机)在灭火装置水平传感器前点火,灭火装置应水平定位。
d)灭火装置水平定位后可在垂直传感器前点火,灭火装置应垂直定位。
e)灭火装置垂直定位 3s 后发出报警声,炮管喷水并做上下左右往复运动。
通过以上调试,无异常发生后方可交付验收。
灭火装置精准度补偿调试:
本公司所有产品均为厂里调试好后出厂销售,如需调整请联系现场技术员或直接与本公司技术部沟通。
第五章 注意事项
1. 在开机前必须检查线路无问题,切勿短路、开路、错接等。
2. 本机需由经专业培训人员进行维护、维修,严禁他人随意操作。
3. 我公司负责本产品的维修,发现问题时请及时与我公司技术服务中心联系,用户不得擅自开箱维修,否则后果自负。
4. 在安装前应进行功能检查,避免为运输过程中造成损坏的设备。
5. 严禁带电拆装各电路连接线和信号线,所有的操作均需在断电关机情况下进行。
6. 外壳、电源部分和外接导线的金属软管应作接地保护。
7. 本产品保修期为 12 个月,如在一年内出现非人为损坏的情况请即与本公司或者经销单位联系。
从本公司购买设备者,自本公司发运日期起计算;从经销部门购买者,以经销单位发运日起计算,整机保修为 12 个月
安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
电控消防炮
PSKD20A-HA(固定炮)
[安装使用说明书]
(HA.2019.10.31 V1.0)
无锡皓安安全技术有限公司
Wuxi haoan safety technology co., ltd
江苏省无锡市滨湖区胡埭路 8 号
目录
一、概述·······················································································································1
系统组成············································································································1
设计与分布·········································································································1
二、产品安装设计及参数·······························································································1
外观及技术参数······································································································1
安装方式·················································································································2
安装部件·················································································································3
安装使用说明及示意图····························································································3
三、配套设施·················································································································4
电源解码器··········································································································4
手动控制盘··········································································································4
四、产品调试及接线·······································································································5
五、注意事项·················································································································6
第1页共 6 页
第一章 公司、产品概述
无锡皓安安全技术有限公司是一家专业从事消防产品的研发、生产、销售和服务于一体的现代化科技型企业。公司座落在中国
最具活力的长三角经济区-无锡经济开发区(滨湖区胡埭镇),苏南国际机场、京沪高速、沪宜高速、京沪高铁、沪宁城际、京杭大
运河均近在咫尺;现有员工 160 余名,其中工程技术人员 30 余人;公司产品包括自动跟踪定位射流灭火装置、防火门监控系统、
防火门消防联动相关配件等,成功地开发研制出多项高科技消防产品,所有产品均通过了国家消防电子产品检测中心的检测认证。
公司拥有专业的设备安装与调试队伍,建立了比较完善的销售服务体系,配备知识型高素质人员、售后服务人员、能为用户提
供完善的售前及售后服务;皓安是我们的品牌寄托,保障人民生命安全是我们的宗旨,我们秉承与时俱进的理念,用在最先进、最
稳定的技术和产品服务于人民和社会。
自动跟踪定位射流灭火装置系列产品是皓安公司自主研发生产的集报警、灭火于一体的新一代高科技消防产品。该系列产品将
红外/紫外传感器、计算机通信技术有机集合起来,具有主动探测火源、自动定位、对火点实施定点射水灭火,火灭后自动复位,
如有复燃,重新启动的特点,特别适用于大空间场所的灭火需求。产品方便安装,安装与维护费用低,节约水资源,最大程度的减
小了灭火后照成射水带来的危害,具有很高的性价比。
本系列产品广泛应用于:大型商场、会展中心、机场、火车站、汽车站、办公楼、医院、图书馆、电影院、体育馆、厂房、仓
库等空间大、楼间隔高的场所。
用途及特点:
固定式消防炮同时具有电控、手控,可交叉操作,不受手动电控转换制约,完成水平回转、俯仰转动、喷射流态(直流和喷雾)
可调的特点。该炮与同类产品相比,具有体积小、重量轻、流量大、射程远、操作简便,可方便快速地装上专用泡沫管,直接喷射
水成膜泡沫混合液,非常适用于易燃易爆危险石油化工企业、油罐区、输油码头、大型仓库或消防车难以进入的火场。
第二章 产品安装设计及参数
1、外观及技术参数
PSKD20A-HA
技术参数:
型号规格 PSKD20A-HA 执行标准 GB19156-2003/GB25204-2010
额定工作压力 0.8MPa 俯仰角度 -90°~+30°
工作压力范围 0.8 MPa~1.2MPa 水平角度 0°~360°
射水流量 20L/S 通讯方式 CAN 总线
喷水方式 柱状或雾状 进水口口径 Φ58mm
接口法兰 DN80 出水口口径 Φ42mm
配接线束(至装置电源盒) 12 芯航空线束 装置自重 约 19KG
配套控制产品 手动控制盘 HA-SKP1013A 电源解码器 HA-JMQ1012A
安装方式与边距 吊装;法兰盘中心距墙体≥600mm,距吊顶≥300mm
第2页共 6 页
2、安装方式
2.1 吊装方式
灭火装置水平安装在法兰盘下的一种方式,一般吊装在大空间建筑物的框架等位置,如下图所示:
2.2 坐式方式
注意:坐装式消防炮订货时需特别标明。
灭火装置水平安装在法兰盘上的一种方式,一般安装在建筑物的顶部等位置,如下图所示
第3页共 6 页
3、安装部件
3.1 闸阀
闸阀安装在配水管末端。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接
后应将连接处外部清理干净,闸阀的扳手部分应安装在管网上方。
3.2 电动阀
电动阀安装在闸阀后面管径为 DN80,中间用长 50~100mm 热镀锌管连接。电动阀应安装在水平管段上,且保证水流方向要与
阀体的指示方向一致。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接后应将
连接处外部清理干净。电动阀应安装在管网上方,应选用 DC24V 电源供电,电动阀电源线应串入电源解码器接点使用,并作防水处
理。
3.3 水流指示器
水流指示器应安装在电动阀前面,接口直径为 DN80。
4、安装使用说明及示意图
灭火装置的安装应按照国标喷水灭火系统设计、施工规范进行,各省、地方有自行规定的按自行规定安装。将灭火装置与管网
法兰连接,固定灭火装置时注意按照规程操作。灭火装置连接线需用本公司原厂自带 12 芯航空线束与电源解码器相连接,并拧紧
螺帽。灭火装置安装牢固后通电,待复位后观察灭火装置绿色运行指示灯是否闪烁(如不能复位请技术联系现场调试人员),如果
状态正常及安装完毕,安装示意图如下:
第4页共 6 页
第三章 配套设备
电源解码器
电源解码器是自动跟踪定位射流灭火系统的前端控制设备,与灭火装置配合使用。通过 CAN 总线实现与区域控制箱、灭火装置
控制器的实时数据传输,能够接收灭火装置控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟踪扫描定位火源,控制
电磁(动)阀启闭,接受灭火装置、电磁(动)阀的动作反馈信号,并传输给灭火装置控制器。
HA-JMQ1012A
主要技术参数:
输入电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
输出电压 DC24V 启阀输出功率 DC24V/3.5A
通讯方式 CAN 总线 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,实现对电动阀逻辑联动控制。
视频一体式集成功能,布线简洁。
电动阀启阀双向逻辑输出,稳定性更强。
手动控制盘
采用单片机控制,直接操作。它是通过 CAN 总线对最多 32 台消防炮进行现场控制,通过 CAN 总线与控制主机进行通讯,实
现远程操作和控制,与自动跟踪定位消防炮灭火装置配套使用。
HA-SKP1013A
主要技术参数:
输入电压 DC24V(无极性) 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 安装方式 水平安装距地 1.5m
容量 可控制 32 台灭火装置 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,布线简洁,安装方便。
就地启动灭火装置自动寻火。
就地控制灭火装置上下左右移位,联锁对应解码器开启电动阀。
就地控制灭火装置的喷水方式。
第5页共 6 页
第四章 产品接线及调试
灭火装置在通电之前应必须检查下、手动控制盘、电源解码器之间的接线是否正确。
电源解码器的接线如下图所示:
电源解码器接线端子
电源解码器与电动阀的接线:
装置电源输入: AC220V L、N、E(火、零、地线)
启阀电源输出: DC24V (端子左侧正极、右侧负极)
启泵接点:泵房启泵线或开关量输出(无源信号)
CANH/CANL:CAN 通讯线输入(注意高低极性)
外部启动:第三方火警启动输入信号(无源信号)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电动阀无回答信号线时,需将启泵接点与电磁阀反馈接口短接,不短接的话,开阀动作后控制器及区控箱会报阀反
馈故障
电源解码器与灭火装置的接线:
此连线为 12 芯专用航空线束连接,出厂为标配。
整机调试:
a)通电后炮管垂直向上运动到限位点,5s 后灭火装置主程序复位,此时灭火装置处于待命状态;
b)短接电源解码器的端子排外部启动(模拟火灾信号)启动灭火装置,灭火装置水平顺时针旋转;
c)水平旋转后,观察左右限位是否正常限位;
通过以上调试,无异常发生后方可交付验收。
灭火装置简易操作:
1.产品外观及按键说明
HA-SKP1013A 型手动控制盘装配有 10 个按键及两个指示灯;用于控制灭火设备向上、向下、向左、向右运动的方向按键;用
于控制灭火装置开阀、关阀、启动巡查、设置地址的操作按键;柱状、雾状喷射方式的操作按键;六个指示灯:电源灯常亮、运行
指示灯闪烁。
HA-SKP1013A 型手动控制盘
第6页共 6 页
2.安装说明
①、手动控制盘采用 DC24V(无极性)供电,直接从电源解码器引线即可。线路连接如下图所示:
②、采用明装方式安装在灭火装置下方,手动控制盘外壳底部距离地面 1.5m(装修后),可明确看到灭火装
置的位置。安装孔尺寸如图所示:
安装尺寸图
3.使用说明:
①、线路连接正确,此时如果灭火装置工作正常,则运行灯闪烁。每次改变地址码后,手动控制盘都无需重新上电。
②、手动控制盘通过 CAN 总线可对固定炮灭火装置进行控制,手动控制盘必须与被控制的灭火装置地址码一致。
③、手动控制盘通过 CAN 总线可对灭火装置进行上、下、左、右、开阀、关阀、启动、柱状、雾状操作。灭火装置电动阀打开
时,开阀指示灯常亮;灭火装置电动阀关闭时,关阀指示灯常亮。
④、手动控制盘进行控制时请将钥匙开关转至“运行”位置时才可以操作手动控制盘,停止位置则锁住禁止操作。
4.注意事项:
①、电源接线必须正确无误,以免损坏手动控制盘。
②、手动控制盘操作时必须能明确看到灭火装置的运行方向。
③、严禁超限位控制,以免损坏灭火装置。
本公司所有产品均为调试后出厂销售,如需调整参数请联系现场技术员或直接与本公司技术部沟通。
第五章 注意事项
1. 在开机前必须检查线路无问题,切勿短路、开路、错接等。
2. 本机需由经专业培训人员进行维护、维修,严禁他人随意操作。
3. 我公司负责本产品的维修,发现问题时请及时与我公司技术服务中心联系,用户不得擅自开箱维修,否则后果自负。
4. 在安装前应进行功能检查,避免为运输过程中造成损坏的设备。
5. 严禁带电拆装各电路连接线和信号线,所有的操作均需在断电关机情况下进行。
6. 外壳、电源部分和外接导线的金属软管应作接地保护。
7. 本产品保修期为 12 个月,如在一年内出现非人为损坏的情况请即与本公司或者经销单位联系。
从本公司购买设备者,自本公司发运日期起计算;从经销部门购买者,以经销单位发运日起计算,整机保修为 12 个月
第7页共 6 页
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
全国 24 小时服务热线:400-0496-119
安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
电控消防炮
PSKD30A-HA(固定炮)
[安装使用说明书]
(HA.2019.10.31 V1.0)
无锡皓安安全技术有限公司
Wuxi haoan safety technology co., ltd
江苏省无锡市滨湖区胡埭路 8 号
目录
一、概述·······················································································································1
系统组成············································································································1
设计与分布·········································································································1
二、产品安装设计及参数·······························································································1
外观及技术参数······································································································1
安装方式·················································································································2
安装部件·················································································································3
安装使用说明及示意图····························································································3
三、配套设施·················································································································4
电源解码器··········································································································4
手动控制盘··········································································································4
四、产品调试及接线·······································································································5
五、注意事项·················································································································6
第1页共 6 页
第一章 公司、产品概述
无锡皓安安全技术有限公司是一家专业从事消防产品的研发、生产、销售和服务于一体的现代化科技型企业。公司座落在中国
最具活力的长三角经济区-无锡经济开发区(滨湖区胡埭镇),苏南国际机场、京沪高速、沪宜高速、京沪高铁、沪宁城际、京杭大
运河均近在咫尺;现有员工 160 余名,其中工程技术人员 30 余人;公司产品包括自动跟踪定位射流灭火装置、防火门监控系统、
防火门消防联动相关配件等,成功地开发研制出多项高科技消防产品,所有产品均通过了国家消防电子产品检测中心的检测认证。
公司拥有专业的设备安装与调试队伍,建立了比较完善的销售服务体系,配备知识型高素质人员、售后服务人员、能为用户提
供完善的售前及售后服务;皓安是我们的品牌寄托,保障人民生命安全是我们的宗旨,我们秉承与时俱进的理念,用在最先进、最
稳定的技术和产品服务于人民和社会。
自动跟踪定位射流灭火装置系列产品是皓安公司自主研发生产的集报警、灭火于一体的新一代高科技消防产品。该系列产品将
红外/紫外传感器、计算机通信技术有机集合起来,具有主动探测火源、自动定位、对火点实施定点射水灭火,火灭后自动复位,
如有复燃,重新启动的特点,特别适用于大空间场所的灭火需求。产品方便安装,安装与维护费用低,节约水资源,最大程度的减
小了灭火后照成射水带来的危害,具有很高的性价比。
本系列产品广泛应用于:大型商场、会展中心、机场、火车站、汽车站、办公楼、医院、图书馆、电影院、体育馆、厂房、仓
库等空间大、楼间隔高的场所。
用途及特点:
固定式消防炮同时具有电控、手控,可交叉操作,不受手动电控转换制约,完成水平回转、俯仰转动、喷射流态(直流和喷雾)
可调的特点。该炮与同类产品相比,具有体积小、重量轻、流量大、射程远、操作简便,可方便快速地装上专用泡沫管,直接喷射
水成膜泡沫混合液,非常适用于易燃易爆危险石油化工企业、油罐区、输油码头、大型仓库或消防车难以进入的火场。
第二章 产品安装设计及参数
1、外观及技术参数
PSKD30A-HA
技术参数:
型号规格 PSKD30A-HA 执行标准 GB19156-2003/GB25204-2010
额定工作压力 0.9MPa 俯仰角度 -90°~+30°
工作压力范围 0.9 MPa~1.2MPa 水平角度 0°~360°
射水流量 30L/S 通讯方式 CAN 总线
喷水方式 柱状或雾状 进水口口径 Φ58mm
接口法兰 DN80 出水口口径 Φ56mm
配接线束(至装置电源盒) 12 芯航空线束 装置自重 约 20.8KG
配套控制产品 手动控制盘 HA-SKP1013A 电源解码器 HA-JMQ1012A
安装方式与边距 吊装;法兰盘中心距墙体≥600mm,距吊顶≥300mm
第2页共 6 页
2、安装方式
2.1 吊装方式
灭火装置水平安装在法兰盘下的一种方式,一般吊装在大空间建筑物的框架等位置,如下图所示:
2.2 坐式方式
灭火装置水平安装在法兰盘上的一种方式,一般安装在建筑物的顶部等位置,如下图所示
第3页共 6 页
3、安装部件
3.1 闸阀
闸阀安装在配水管末端。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接
后应将连接处外部清理干净,闸阀的扳手部分应安装在管网上方。
3.2 电动阀
电动阀安装在闸阀后面管径为 DN80,中间用长 50~100mm 热镀锌管连接。电动阀应安装在水平管段上,且保证水流方向要与
阀体的指示方向一致。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接后应将
连接处外部清理干净。电动阀应安装在管网上方,应选用 DC24V 电源供电,电动阀电源线应串入电源解码器接点使用,并作防水处
理。
3.3 水流指示器
水流指示器应安装在电动阀前面,接口直径为 DN80。
4、安装使用说明及示意图
灭火装置的安装应按照国标喷水灭火系统设计、施工规范进行,各省、地方有自行规定的按自行规定安装。将灭火装置与管网
法兰连接,固定灭火装置时注意按照规程操作。灭火装置连接线需用本公司原厂自带 12 芯航空线束与电源解码器相连接,并拧紧
螺帽。灭火装置安装牢固后通电,待复位后观察灭火装置绿色运行指示灯是否闪烁(如不能复位请技术联系现场调试人员),如果
状态正常及安装完毕,安装示意图如下:
第4页共 6 页
第三章 配套设备电源解码器
器的实时数据传输,能够接收灭火装置控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟踪扫描定位火源,控制
电磁(动)阀启闭,接受灭火装置、电磁(动)阀的动作反馈信号,并传输给灭火装置控制器。
HA-JMQ1012A
主要技术参数:
输入电压 AC220V 工作环境 -10℃~+40℃,≤95%RH
输出电压 DC24V 启阀输出功率 DC24V/3.5A
通讯方式 CAN 总线 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,实现对电动阀逻辑联动控制。
视频一体式集成功能,布线简洁。
电动阀启阀双向逻辑输出,稳定性更强。
手动控制盘
采用单片机控制,直接操作。它是通过 CAN 总线对最多 32 台消防炮进行现场控制,通过 CAN 总线与控制主机进行通讯,实
现远程操作和控制,与自动跟踪定位消防炮灭火装置配套使用。
HA-SKP1013A
主要技术参数:
输入电压 DC24V(无极性) 工作环境 -10℃~+40℃,≤95%RH
通讯方式 CAN 总线 安装方式 水平安装距地 1.5m
容量 可控制 32 台灭火装置 外观尺寸 220x160x70
性能特点:
CAN 总线通讯,布线简洁,安装方便。
就地启动灭火装置自动寻火。
就地控制灭火装置上下左右移位,联锁对应解码器开启电动阀。
就地控制灭火装置的喷水方式。
第四章 产品接线及调试
第5页共 6 页
灭火装置在通电之前应必须检查下、手动控制盘、电源解码器之间的接线是否正确。
电源解码器的接线如下图所示:
电源解码器接线端子
电源解码器与电动阀的接线:
装置电源输入: AC220V L、N、E(火、零、地线)
启阀电源输出: DC24V (端子左侧正极、右侧负极)
启泵接点:泵房启泵线或开关量输出(无源信号)
CANH/CANL:CAN 通讯线输入(注意高低极性)
外部启动:第三方火警启动输入信号(无源信号)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电动阀无回答信号线时,需将启泵接点与电磁阀反馈接口短接,不短接的话,开阀动作后控制器及区控箱会报阀反
馈故障
电源解码器与灭火装置的接线:
此连线为 12 芯专用航空线束连接,出厂为标配。
整机调试:
a)通电后炮管垂直向上运动到限位点,5s 后灭火装置主程序复位,此时灭火装置处于待命状态;
b)短接电源解码器的端子排外部启动(模拟火灾信号)启动灭火装置,灭火装置水平顺时针旋转;
c)水平旋转后,观察左右限位是否正常限位;
通过以上调试,无异常发生后方可交付验收。
灭火装置简易操作:
1.产品外观及按键说明
HA-SKP1013A 型手动控制盘装配有 10 个按键及两个指示灯;用于控制灭火设备向上、向下、向左、向右运动的方向按键;用
于控制灭火装置开阀、关阀、启动巡查、设置地址的操作按键;柱状、雾状喷射方式的操作按键;六个指示灯:电源灯常亮、运行
指示灯闪烁。
HA-SKP1013A 型手动控制盘
2.安装说明
第6页共 6 页
①、手动控制盘采用 DC24V(无极性)供电,直接从电源解码器引线即可。线路连接如下图所示:
②、采用明装方式安装在灭火装置下方,手动控制盘外壳底部距离地面 1.5m(装修后),可明确看到灭火装
置的位置。安装孔尺寸如图所示:
安装尺寸图
3.使用说明:
①、线路连接正确,此时如果灭火装置工作正常,则运行灯闪烁。每次改变地址码后,手动控制盘都无需重新上电。
②、手动控制盘通过 CAN 总线可对固定炮灭火装置进行控制,手动控制盘必须与被控制的灭火装置地址码一致。
③、手动控制盘通过 CAN 总线可对灭火装置进行上、下、左、右、开阀、关阀、启动、柱状、雾状操作。灭火装置电动阀打开
时,开阀指示灯常亮;灭火装置电动阀关闭时,关阀指示灯常亮。
④、手动控制盘进行控制时请将钥匙开关转至“运行”位置时才可以操作手动控制盘,停止位置则锁住禁止操作。
4.注意事项:
①、电源接线必须正确无误,以免损坏手动控制盘。
②、手动控制盘操作时必须能明确看到灭火装置的运行方向。
③、严禁超限位控制,以免损坏灭火装置。
本公司所有产品均为调试后出厂销售,如需调整参数请联系现场技术员或直接与本公司技术部沟通。
第五章 注意事项
1. 在开机前必须检查线路无问题,切勿短路、开路、错接等。
2. 本机需由经专业培训人员进行维护、维修,严禁他人随意操作。
3. 我公司负责本产品的维修,发现问题时请及时与我公司技术服务中心联系,用户不得擅自开箱维修,否则后果自负。
4. 在安装前应进行功能检查,避免为运输过程中造成损坏的设备。
5. 严禁带电拆装各电路连接线和信号线,所有的操作均需在断电关机情况下进行。
6. 外壳、电源部分和外接导线的金属软管应作接地保护。
7. 本产品保修期为 12 个月,如在一年内出现非人为损坏的情况请即与本公司或者经销单位联系。
从本公司购买设备者,自本公司发运日期起计算;从经销部门购买者,以经销单位发运日起计算,整机保修为 12 个月
第7页共 6 页
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
全国 24 小时服务热线:400-0496-119
HA-SKP1003A 型手动控制盘
安装使用说明
1.概述
HA-SKP1003A 型智能灭火装置现场控制盘采用现场控制器局
域网技术,点对点控制自动跟踪定位射流灭火装置。报文采用短
帧结构,传输时间短,受干扰概率低,保证了数据的零出错率。
近距离操控灭火装置的通信速率可达 1Mbps,现场控制盘的
近距离操控可彻底解决消控中心控制的盲目性以及遥控器控制
的易受干扰性,该控制盘采用薄膜面板按键组合 LED 技术,整体
外形新颖美观,体积小、重量轻、耐腐蚀、防潮、防尘、防油、
有利于向高智能化方向发展。主控制器采用 IC 芯片集成 CAN 总
线内核,使得系统更加稳定可靠。
2.产品外观及按键说明
HA-SKP1003A 型手动控制盘装配有 7 枚按键、1 块 LED 数码
管以及 4 只状态指示灯;分别为用于控制灭火装置向上、向下、
向左、向右运动的方向按键;用于控制灭火装置开阀、关阀、启
动、地址选择的操作按键;以及 4 只状态指示灯:电源指示灯、
运行指示灯、启动指示灯、阀状态指示灯。
HA-SKP1003A 型手动控制盘
3.安装说明
①、手动控制盘采用无极性 DC24V 供电,直接从电源解码
器引线即可。线路连接如下图所示:
②、采用明装方式安装在灭火装置下方,手动控制
盘外壳底部距离地面 1.5m(装修后),可明确看到灭火
装置的位置。安装孔尺寸如图所示:
安装尺寸图
4.使用说明:
①、线路连接正确,此时如果灭火装置工作正常,则运行灯
闪烁。每次改变地址码后,手控盘都无需重新上电。
②、现场控制盘通过 CAN 总线可对灭火装置进行控制,现场
控制盘必须与被控制的灭火装置地址码一致。有关地址码设置请
参照附录“现场手动控制盘编码规则”。
③、现场控制盘通过 CAN 总线可对灭火装置进行上、下、左、
右、开阀、关阀、启动操作。当设备电磁阀打开后,阀状态指示
灯常亮;当设备电磁阀关闭时,阀状态指示灯常灭。
④、使用现场控制盘进行控制时请将钥匙开关转至“运行”
位置时才可以操作现场控制盘,停止位置则锁住禁止操作。
5.注意事项:
①、电源接线必须正确无误,以免损坏现场控制盘
②、现场控制盘操作时必须能明确看到灭火装置的运行方向,严
禁超限位控制,以免损坏灭火装置
附录
现场手动控制盘编码规则:
采用单片机 IC 内部地址码进行手动编码,编码方式:点按“地
址键”,当 LED 数码管编码号出现闪亮时,可通过上下方向键对
地址码进行设置,设置完成时常按“地址键”1S 后退出锁定地址,
控制盘锁定地址码后即可对对应地址的灭火装置进行手动控制:
如需重新设置地址码,可重复上述方式设置。
地址编码设置后,无需重新启动电源使设置生效。
无锡皓安安全技术有限公司研发部
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
24 小时服务热线:400-0496-119
HA-SKP1013A 型手动控制盘
安装使用说明
1.概述
HA-SKP1013A 型智能灭火装置现场控制盘采用现场控制器局
域网技术,点对点控制自动跟踪定位射流灭火装置。报文采用短
帧结构,传输时间短,受干扰概率低,保证了数据的零出错率。
近距离操控灭火装置的通信速率可达 1Mbps,现场控制盘的
近距离操控可彻底解决消控中心控制的盲目性以及遥控器控制
的易受干扰性,该控制盘采用薄膜面板按键组合 LED 技术,整体
外形新颖美观,体积小、重量轻、耐腐蚀、防潮、防尘、防油、
有利于向高智能化方向发展。主控制器采用 IC 芯片集成 CAN 总
线内核,使得系统更加稳定可靠。
2.产品外观及按键说明
HA-SKP1013A 型手动控制盘装配有 9 枚按键、1 块 LED 数码
管以及 6 只状态指示灯;分别为用于控制灭火装置向上、向下、
向左、向右运动的方向按键;用于控制灭火装置开阀、关阀、柱
状、雾状、启动、地址选择的操作按键;以及 6 只状态指示灯:
电源指示灯、运行指示灯、启动指示灯、阀状态指示灯、柱状指
示灯、雾状指示灯。
HA-SKP1013A 型手动控制盘
3.安装说明
①、手动控制盘采用无极性 DC24V 供电,直接从电源解码
器引线即可。线路连接如下图所示:
②、采用明装方式安装在灭火装置下方,手动控制
盘外壳底部距离地面 1.5m(装修后),可明确看到灭火
装置的位置。安装孔尺寸如图所示:
安装尺寸图
4.使用说明:
①、线路连接正确,此时如果灭火装置工作正常,则运行灯
闪烁。每次改变地址码后,手控盘都无需重新上电。
②、现场控制盘通过 CAN 总线可对灭火装置进行控制,现场
控制盘必须与被控制的灭火装置地址码一致。有关地址码设置请
参照附录“现场手动控制盘编码规则”。
③、现场控制盘通过 CAN 总线可对灭火装置进行上、下、左、
右、开阀、关阀、启动操作。当设备电磁阀打开后,阀状态指示
灯常亮;当设备电磁阀关闭时,阀状态指示灯常灭。
④、使用现场控制盘进行控制时请将钥匙开关转至“运行”
位置时才可以操作现场控制盘,停止位置则锁住禁止操作。
⑤、现场控制盘通过柱状、雾状键可对灭火装置的喷水方式
进行实时变换。
5.注意事项:
①、电源接线必须正确无误,以免损坏现场控制盘
②、现场控制盘操作时必须能明确看到灭火装置的运行方向,严
禁超限位控制,以免损坏灭火装置
附录
现场手动控制盘编码规则:
采用单片机 IC 内部地址码进行手动编码,编码方式:点按“地
址键”,当 LED 数码管编码号出现闪亮时,可通过上下方向键对
地址码进行设置,设置完成时常按“地址键”1S 后退出锁定地址,
控制盘锁定地址码后即可对对应地址的灭火装置进行手动控制:
如需重新设置地址码,可重复上述方式设置。
地址编码设置后,无需重新启动电源使设置生效。
无锡皓安安全技术有限公司研发部
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
24 小时服务热线:400-0496-119
HA-JMQ1002A 型电源解码器
安装使用说明
1.概述
HA-JMQ1002A 型电源解码器是自动跟踪定位射流灭火系统
的前端控制设备,与灭火装置配合使用。通过 CAN 总线实现与区
域控制箱、灭火装置控制器的实时数据传输,能够接收灭火装置
控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟
踪扫描定位火源,控制电磁(动)阀启闭,接受灭火装置、电磁
(动)阀的动作反馈信号,并传输给灭火装置控制器。
2.产品外观说明
HA-JMQ1002A 型电源解码器配置 1 个 12 芯专用航空线束插
头,用于与灭火装置无缝对接,简洁、方便、易安装,将通讯信
号进行解码;对水炮进行定位控制;对电磁阀进行打开关闭控制;
带有外部联动输出端口,可控制其他消防联动设备;可与通用火
灾自动报警系统连接.。
HA-JMQ1002A 型电源解码器
3.安装说明
①、电源解码器采用 AC220V 供电,从智能灭火装置控制器、
区域控制箱引线即可。线路连接如下图所示:
装置电源输入: AC220V L、N、E(火线、零线、地线)
启阀电源输入: AC220V L、N (火线、零线)
启阀电源输出: AC220V L、N (火线、零线)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
动作输出:开关量输出(动作后无源常闭信号)
外部启动:第三方火警启动输入信号(无源信号)
CANH/CANL:CAN 通讯线输入(注意 H/L 高低极性)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电磁阀无回答反馈线时,需将动作输出与电磁
阀反馈接口对应短接,不短接的话,开阀动作后控制器
及区控箱会报阀反馈故障。
②、采用明装方式安装在灭火装置附近,安装孔尺
寸如下图所示:
安装尺寸图
4.注意事项:
①、电源线接线必须正确无误,以免损坏电源解码器。
②、电源解码器必须就近安装于灭火装置的附近,以保证专用航
空线束有 360°的转动空间,严禁在空间不足的情况下运行灭火
装置,以免损坏灭火装置。
③、末端电源解码器必须在 P5 跳冒处插上短接跳冒,最末端处
短接,其他解码器不需要短接。
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
24 小时服务热线:400-0496-119
HA-JMQ1012A 型电源解码器
安装使用说明
1.概述
HA-JMQ1012A 型电源解码器是自动跟踪定位射流灭火系统
的前端控制设备,与灭火装置配合使用。通过 CAN 总线实现与区
域控制箱、灭火装置控制器的实时数据传输,能够接收灭火装置
控制器、区域控制箱、手动控制盘的指令,驱动灭火装置自动跟
踪扫描定位火源,控制电磁(动)阀启闭,接受灭火装置、电磁
(动)阀的动作反馈信号,并传输给灭火装置控制器。
2.产品外观说明
HA-JMQ1012A 型电源解码器配置 1 个 12 芯专用航空线束插
头,用于与灭火装置无缝对接,简洁、方便、易安装,将通讯信
号进行解码;对水炮进行定位控制;对电磁阀进行打开关闭控制;
带有外部联动输出端口,可控制其他消防联动设备;可与通用火
灾自动报警系统连接.。
HA-JMQ1012A 型电源解码器
3.安装说明
①、电源解码器采用 AC220V 供电,从智能灭火装置控制器、
区域控制箱引线即可。线路连接如下图所示:
装置电源输入: AC220V L、N、E(火、零、地线)
启阀电源输出: DC24V (端子左侧正极、右侧负极)
启泵接点:泵房启泵线或开关量输出(无源信号)
CANH/CANL:CAN 通讯线输入(注意高低极性)
外部启动:第三方火警启动输入信号(无源信号)
电磁阀反馈:电磁阀开启后动作回答信号(无源信号)
SYV 视频芯/屏蔽:灭火装置视频输入线
24V+/24V-:DC24V 电源输出
注意:当电磁阀无回答信号线时,需将启泵接点与
电磁阀反馈接口短接,不短接的话,开阀动作后控制器
及区控箱会报阀反馈故障
②、采用明装方式安装在灭火装置附近,安装孔尺
寸如下图所示:
安装尺寸图
4.注意事项:
①、电源线必须正确无误,以免损坏电源解码器。
②、电源解码器必须就近安装于灭火装置的附近,以保证专用航
空线束有 360°的转动空间,严禁在空间不足的情况下运行灭火
装置,以免损坏灭火装置。
③、末端电源解码器必须在跳冒 2 处插上短接跳冒,最末端处短
接,其他解码器不需要短接。
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
24 小时服务热线:400-0496-119
ZDM-HA06 总线联动模块
安装使用说明
1.概述
ZDM-HA06 总线联动模块应用于大空间智能型流量喷头以及
模拟末端试水装置,采用导轨式安装,接触可靠,方便安装、更
换,便于施工;采用低功耗设计,内嵌单片机,带干扰吸收、
反馈隔离电路、软硬件滤波技术,提高了模块的抗干扰能力
联动模块整体外形新颖美观,体积小、重量轻、耐腐蚀、防
潮、防尘、防油、有利于向高智能化方向发展。该
芯片集成、CAN 总线内核,使得系统更加稳定可靠。
2.产品外观
ZDM-HA06 总线联动模块装配有 3 个指示灯;
警指示灯、启阀指示灯;正常通讯时通讯指示灯间隔闪烁、报警
状态下火警指示灯常亮,启阀状态下启阀指示灯常亮。
ZDM-HA06 总线联动模块
3.安装说明
①、总线联动模块采用 DC24V 供电,线路连接如下图所示:
②、采用导轨方式安装在灭火装置附近
所示:
总线联动模块
安装使用说明
总线联动模块应用于大空间智能型流量喷头以及
采用导轨式安装,接触可靠,方便安装、更
内嵌单片机,带干扰吸收、
提高了模块的抗干扰能力。
、重量轻、耐腐蚀、防
潮、防尘、防油、有利于向高智能化方向发展。该模块采用 IC
总线内核,使得系统更加稳定可靠。
个指示灯;通讯指示灯、火
启阀指示灯;正常通讯时通讯指示灯间隔闪烁、报警
状态下火警指示灯常亮,启阀状态下启阀指示灯常亮。
供电,线路连接如下图所示:
附近,尺寸如图
产品
4.使用说明及接线方法
H、L:CAN总线连接,有极性
IN/24V+、24V-:DC24V电源输入端
OUT/24V+、24V-:DC24V电源输出端
探测组件:探测组件报警信号(无源)
火警信号:任意探测器报警信号(无源)
启阀信号:手动启阀输入信号(无源)
启阀输出【1·2】:启阀输出单开关量触点
火警输出【1·2】:火警输出单开关量触点
5.注意事项:
①、电源接线必须正确无误,以免损坏
②、联动模块的各输入触点严格按照使用说明及接线方法接线
以免损坏联动模块
附录
总线联动模块地址编码规则
使用二进制倒序进行编码(
拨码开关设置后,无需重新启动电源使设置生效。
地址:江苏省无锡市滨湖区胡埭路
电话:
24 小时服务热线:
0# 不拨 8# 5 16#
1# 8 9# 5、8 17#
2# 7 10# 5、7 18#
3# 7、8 11# 5、7、8 19#
4# 6 12# 5、6 20#
5# 6、8 13# 5、6、8 21#
6# 6、7 14# 5、6、7 22#
7#
6、7、
8
15#
5、6、7、
8
23#
产品尺寸图
及接线方法:
电源输入端,有极性
电源输出端,有极性
探测组件:探测组件报警信号(无源)
火警信号:任意探测器报警信号(无源)
启阀信号:手动启阀输入信号(无源)
:启阀输出单开关量触点
:火警输出单开关量触点
①、电源接线必须正确无误,以免损坏联动模块
联动模块的各输入触点严格按照使用说明及接线方法接线,
编码规则采用 8 位拨码开关编码规则。
二进制倒序进行编码(8421/8421);
拨码开关设置后,无需重新启动电源使设置生效。
地址:江苏省无锡市滨湖区胡埭路 8 号
电话:0510-83380119/0510-83390119
小时服务热线:400-0496-119
16# 4 24# 4、5
17# 4、8 25# 4、5、8
18# 4、7 26# 4、5、7
19# 4、7、8 27# 4、5、7、8
20# 4、6 28# 4、5、6
21# 4、6、8 29# 4、5、6、8
22# 4、6、7 30# 4、5、6、7
23#
4、6、7、
8
31#
4、5、6、7、
8
安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
区域控制箱
HA-QKX1001
安装使用说明书
(HA.2017.6.1 V1.0)
目录
一、概述··················································································································1
性能特点·······································································································1
主要技术参数································································································1
二、结构特征与系统操作··························································································2
外形尺寸·······································································································2
面板说明·······································································································2
按键说明·······································································································2
LCD 显示说明································································································3
内部结构说明································································································5
三、安装要求···········································································································5
内部接线说明································································································5
安装说明·······································································································5
四、注意事项············································································································6
五、附件···················································································································6
[安装、使用产品前,请阅读安装使用说明书]
HA-QKX1001 区域控制箱
1
一:概述
区域控制箱是自动跟踪定位射流灭火系统的前端操作设备。其具有能够灵活设置灭火装置,手、自动控制功能切换、
指示现场灭火装置工作状态、设置灭火装置参数等功能,可与我公司所有产品配套使用,具有体积小、功能全、操作简单等
特点。
HA-QKX1001 区域控制箱
性能特点:
LCD 液晶显示屏
具有电磁阀手/自动控制功能
远程控制消防水泵启停动作
设有 1、2 级用户权限,防止误操作
实时显示电磁阀及灭火装置的工作状态
灵活设置灭火装置的参数
主要技术参数:
输入电压 AC220V/50Hz 工作环境 -10℃~+40℃,≤95%RH
输出电压 AC220V 防护等级 IP30
通讯方式 CAN 总线 安装方式 壁挂
通讯距离 ≤2000 米 外观尺寸 380x300x110