PRODUCT SELECTION GUIDE
Service Provider of Power Transmission Distribution System
CORPORATE INFORMATION
劳伦斯电气有限公司是一家专业生产输配电线路产品、高低压输配电成套开关设备等输配电产业为主导产业的集工业制造、进出口贸易于一体的高新科技型企业,主要生产的产品有:避雷器、熔断器、绝缘子、断路器、隔离开关、配电柜、电力金具等。
公司注册资本为5008万的无区域公司,旗下有多家分布在浙江,江西,非洲全资或控股生产和销售子公司。公司产品已在全球30多个国家和地区的供电系统安全运行10多年,也是中国国家电网和南方电网的合格供应商,获得多个国家和地区的供电公司优质产品推荐函。例如,肯尼亚的KPLC,REA,乌干达REAUMEME,坦桑尼亚的TANESCO,加纳的ECG,尼泊尔的NEA,津巴布韦的ZETDC,约旦供电局等。公司已经通过ISO9001质量管理体系认证和ISO14001环境管理体系、OHSAS18001职业健康安全管理体系认证,目前公司已经取得10多项专利和国家高薪企业。大部分产品已经通过第三方独立的CNAS实验室的测试报告。
劳伦斯电气秉着以质量求生存以信誉求发展以服务求永恒的理念期待和您的合作!
L&R Electric Group Co.,Ltd is one of the leading high technical enterprises professional deals in high medium and low voltage Switchgear, Surge Arresters, Insulators, Drop Out FuseCutouts, Load Break Switches, Auto-recloser,SF6Circuit Break Switches, Isolator switch, Line hardware and components develop, manufacture and sales.
Almost all our products had passed the test inspection that are from the famous CNAS accredited laboratories. And our enterprise also got ISO9001 Quality Management System certificate, as well as ISO14001 Environmental Management System and GB/T28001 Occupational Health and Safety Management System certificate.
We had an extensive experience with International Engineering Project materials supply, International trading and Electrical Equipment manufacturing, deeply committing ourselves into the development of global market and seeking extensive cooperation in the world.
CORPORATE CULTURE
企业愿景
输配电行业系统服务商
企业使命
让电安全点亮每个角落
企业精神
团队协作,勇于开拓, 持之以恒,共创辉煌
企业价值观
为客户创造价值,为员工创造美好生活,为社会做出应有贡献
CORPORATE VISION
Service Provider of Power transmission and distribution system
CORPORATE MISSION
Let Electricity safely light up every corner
CORPORATE SPIRIT
Teamwork,Courage to open up Preseverance, Create brilliance together
CORPORATE VALUE
Create value for customers create better life for employees make due contributions to society
| Name of country | Project name | Amount ofmoney | Delivery time |
| Guyana | 328 km distribution lines in Guyana-GPL | $2,600,000 | 2017-2020 |
| Ghana | Electrification project in five provinces of Ghana-ECG | $1530,000 | 2018-2021 |
| Kenya | Supply of Circuit breaker-KPLC | $1,257,000 | 2017-2018 |
| Uganda | Nangoma project(Uganda-Tanzania cross border project)-REA | $2,496,000 | 2018-2020 |
| Togo | Supply of line accessories, surge arresters & air break switch | $1,162,600 | 2019-2020 |
| Tanzania | Supply of SF6 circuit breakers complete with supporting structure-TANESCO | $360,000 | 2019-2020 |
| Tanzania | Rural Electrification for Peri-Urban Areas of Pwani Region and Kigamboni Districtlot 3-Mkuranga-TANESCO | $1,570,000 | 2019-2020 |
| Kenya | Supply of SF6 circuit breaker-KPLC | $660,000 | 2019-2020 |
| Nepal | Nepal 11/0.4kV PV Distribution Network Project-NEA | $1,730,000 | 2019-2020 |
| Zambia | Ndola New airport project | $1,172,000 | 2019-2020 |
| Kenya | Supply and installation of 33kV,11kV lines and associated transformers and LV networksin 5 regions-lot3-REREC | $1,406,000 | 2019-2021 |
| Nepal | Nuwakot Kavre and Dhading11/0.4KV Distribution Network Project in Nepal-NEA | $1,255,000 | 2019-2021 |
| Venezuela | Supply of Fuse cutout and insulator and line hardware | $1,234,300 | 2021-2022 |
| Guinea | Supply of High Voltage Switchgear and cable accessories | $1,370,000 | 2021-2022 |
| Mozambique | Supply of power and line hardware for lot 3-Manica, Tete & Zambezia-MPI | $2,600,000 | 2020-2022 |
| Ethiopia | Power distribution network upgrade and renovation project of six towns in Ethiopia-EEU | $940,000 | 2020-2022 |
| Kenya | The Supply of Fuse Cutout-KPLC | $245,000 | 2020-2021 |
| Zambia | Line hardware and accessories supply for ZESCO/133/2020-REA | $513,800 | 2020-2021 |
| Kenya | Supply of Fuse Cutout-and HRC LV fuse link-KPLC | $203,580 | 2020-2021 |
| Malta | Supply of line hardware | $626,630 | 2020-2022 |
| Uganda | Medium Voltage Networks and Last Mile Consumer Connections under Uganda RuralElectrification Access Project (UREAP): lot 3, lot 12-REA | $2,277,000 | 2020-2022 |
| Tanzania | Construction of Medium and Low Voltage Lines, Installation of Distribution Transformersand Connection of Customers in Un-Electrified Rural Areas of Mainland Tanzania onTurnkey Basis in Mara region-lot 13 & lot 14-TANESCO and REA | $5,490,000 | 2020-2022 |
| Uzbekistan | Uzbekistan Transmission Substation project | $1,265,000 | 2021-2022 |
| Cote d 'Ilvoire | Power engineering supply design and equipment installation project for 334 villages inCote d 'lvoire | $958,000 | 2021-2022 |
| Cambodia | Angkor Airport project in Cambodia | $832,000 | 2021-2022 |
Syutan ia in canfonmity with GWT48901-234980 48000:214 Catta cags à an nle
Hsazhong Imemational Certification &k Inspection Group Co Lad. Occsputional Health And Safety Managoent
实用新型专利证书
发明人:藏解款:除飞
科号:ZL 210 2 3941878.8
专用甲道日:2000年09月08日
专利数人:势给新电气有限公司
地址:35000 江西省南昌市上资市方年晶非收工业国区
覆极公告日,2001年04月27日 授权公告号:CN213070918号国东加识产政高做提中华人汉典和国中利器际过和步审类,由气教于书利核,理况实用
前哲当利证书界在专的登化得上平以整记,专利政自提权公告之日起生观,于利以确准为十
单、自中请日起算办利证书记政中内机整让时特法律状况,中利社的顾荐,质押,光源,终止、低复和市
利社人的社基反基称,自酶,地址觉更开事项记载基专利整记游上
成申雨
实用新型专利证书
实用新型专利证书
页哥新型名廓,一希避需源夹管机
发质人:杂民主:藏华文
专利号:2201821922
专利申语日:8018年11月28日
专剩权人,安伦期电气有限公司
专利审请目:2018年11月28日
地社:13500 江西着上银分万年县本教工业假区
实用新型专利证书
专利权人:势伦障电气有限公司
实用新型名存:一种碰流游体统温
授权公告日:2018年日7月05日 授权台合号,CN3902948E国家细识产机态你用中作人民办和简专利法结过彻争审费,决定妆于专利红,稍政自用新型专树证形开在节科要记源上于以整记,专利视自统组合争之日越生组,专利视测组务才利社人的地态成类物,国每,电治交质爷事项记感在骨利学心罪上。
发法人:兼医生:戴华头
授权公费日:209年07月26日 授机公告号:( 209187373 1
专利号:22082 19808.7
专利申谱日:208年11月28日
专科权人,劳伦期电气有限公司
周家和识产私局你质中净人民与和医专利治经过彻少审查,运定政于中利社,细交资用专型专利证书于在开利登记等上平以要记,中利批自软机分告之品相度期、卡刊机期模身十
公0200.91国家细识产机局体照中华人民表和国专利法控过细步哲查,决定投予号利机,磁发实用所型专利证率并在专利资记源上于以替证,专利社自股机分告也日超生效,专的批期限为于专到证书化最争利政势记特确油標欣况,导利权的游格、要行,无效,账业,核复和音
利号:23.200821580067.2
专利证格认疯者利拟登记时的活律激流,中期视的时移、遵钾、光现、外止,说复和号
发书人:杂园主:重华火
地址:53000 江百律上绩年方年品丰收主业园区
联申雨
中雨
请书号第9142996号
实用教型名体。一种迎需各局族综合额试型
证书号第130069号
实用新型专利证书
实用新型总称,概路器传动弹装结购
专号,2.200 2 2940807.3
专利申语日:200年09月08日
专科权人:劳轮康唯气有限合司
地 疑:350 江西智海器作上继市万年县本收工业服区
发申雨
证书号第13045455号
实用新型专利证书
实日新券名称:一种新型断路数
发明人:饶五旺:徐飞
专利号:21.2000 2 1940736.4
专利申谱日:2020年09月08日
专利权人,开伦廉电气有限公司
地址:3000 江西省南昌作上地作万年县书收工业间区
授权公传日:2021年64月.27日模视会告号:(5 213071027日
需常和识产批品体照中争人民要和国专利法经过和分审表,决化校于专利权,研成实用新型学利证学开表专利整记第上节山些记,专利批自提放公录之出越发效,中利社相维为十手的让害让教专利批资让时的业弹收化、专利纸的物移、质部,无效,终业,现直和者例批人的倾名点名称、国备,地的质更等事硕记载区专利登记排上。
联申雨
TYPE TEST
REPORT
国家陶瓷产品质量监督检验中心(江西)江西 有 检 中nng Cate of agk Pavse
MRA MGNAS tfape 1 ef
国家陶瓷产品质量监督检验中心(江西)江 西省陶宠检测中心
Provider power system LER L&RGR 劳伦斯电气
检验报告 TEST REPORT
国家高低压电器质量监督检验中心甘肃电器科学研究院国家高低压电器质量监督检验中心甘案电器科学研究院
检验报告 TEST REPORT
Spetm:3UAV SPGLOAD BREAE SMTICH 5homt11.W-33/00-32,5
Cm L&RELECTRC COP CO LID Bee Tópo Táge Tist
国家高低压电器质量监督检验中心首肃电器科学研究院
4. aa taed
280 × 280 × 76808
LARLICTRCGREFCOLLTD
datorice tot
检验 报 告 TEST REPORT
检验报告 TEST REPORT
TEST REPORT
AP0T: W1W-42 / 10a Sarioe Hgh Talsaps Patymar Surgs detestes CLESNT: LAM LCTRIC GRAP OL.\_ LI
CCT MWE
Regrm e 300678 HE 20 met , 1am T, Timg D Mla 201068
MME
实验室名称。 苏州电器科学研究院股徐有限公司国流电器产品质量排验检测中心Labe NsateNepsto hodars
检验(试验)报告 Test Report
单:Degpwe EetrisCo.Ead
CHlaai:
严名:SurgeAmier
Yue of Prodicr
产品型号:HY10W-18
Pradeet Type:
检检类利:Commision set
Test Catepory:
办常融重对角具的给带(优磨)结系质责,未综实质室布准洁意: 不得师分政复剩车损务。 The y pe he p sa Te po shl rsal ta isg e
INSULATOR
001-023
B SURGE ARRESTER
024-031
FUSE CUTOUT
032-038
D POLE MOUNTED SWITCH
039-056
E SUBSTATION SWITCH
057-067
FHIGH VOLTAGE SWITCHGEAR 068-077
G LOW VOLTAGE SWITCHGEAR 078-094
MV FITTINGS
095-114
I LV FITTINGS
115-136
J POLE FITTINGS
137-162
STAY FITTINGS
163-167
EARTHING MATERIALS
168-175
CABLE TERMINAL AND JOINTS
176-179
TOOLS
180-186
STREET LIGHT
187-188
Composite Insulator
Feature
●High mechanical strength, epoxy fiber glass rod tension strength is double of normal steel, 8-10 times of porcelain materials.
●High performance against pollution & flashover, the wet withstand voltage is 2-2.5 times of porcelain insulator at same creepage distance.
Good performance of hydrophobicity.
●Small volume & Light weight, easy for transportation. Therefore, it is a new generation for electric power line.
Structure
Composite insulator is made of Fibre Glass Core Rod, Silicone Rubber Shed and Metal Fitting. The silicone rubber shed adopt the whole pressure technique, which solves the main problem of interface electric spark puncture. Connection the fibreglass rod with metal fittings adopts advanced crimping technology. Galvanized end fittings can be anti corrosion.
| Model DesignationF □ □①② ③ ④ ⑤ ⑥ | ||
| ① | Composite Material | |
| ② | XB: Suspension /TensionZS: PostPQ: Pin | |
| ③ | W: Big/Small shedX: Hang type | |
| ④ | Creepage Distance Symbol | |
| ⑤ | Rated voltage (kV) | |
| ⑥ | Rated Mechanical Failing Load (kN) | |
Composite Suspension /Tension Insulator
End Fitting
The end fittings are in accordance with lEC 61466-1 (Composite string insulator units for overhead lines with a nominal voltage greater than 1000 V - Part 1: Standard strength and end fittings). ANSI standard also available.
Composite Suspension /Tension Insulator
| Model | RatedVoltage(kV) | RatedMechanicalFailing Load(KN) | Length(mm) | Minimum ArcDistance(mm) | MinimumCreepageDistance(mm) | LightningImpulseWithstandVoltage, peak (kV) | P.F 1minwet withstandvoltage(kV) | CouplingSize |
| FXB-11/70 | 11 | 70 | 330 | 160 | 300 | 95 | 45 | 16 |
| FXB-11/80 | 11 | 80 | 370 | 200 | 450 | 95 | 45 | 16 |
| FXB-24/70 | 24 | 70 | 410 | 240 | 750 | 125 | 65 | 16 |
| FXB-24/100 | 24 | 100 | 450 | 240 | 750 | 125 | 65 | 16 |
| FXB-24/120 | 24 | 120 | 450 | 240 | 750 | 125 | 65 | 16 |
| FXB-33/70 | 33 | 70 | 530 | 360 | 900 | 200 | 95 | 16 |
| FXB-33/80 | 33 | 80 | 590 | 425 | 1080 | 220 | 95 | 16 |
| FXBW-33/70 | 33 | 70 | 655 | 480 | 1260 | 220 | 105 | 16 |
| FXBW-33/100 | 33 | 100 | 695 | 480 | 1260 | 220 | 105 | 16 |
| FXBW4-66/70 | 66 | 70 | 870/940 | 710 | 2248 | 410 | 185 | 16 |
| FXBW4-66/100 | 66 | 100 | 870/940 | 710 | 2248 | 410 | 185 | 16 |
| FXBW4-110/100 | 110 | 100 | 1240/1440 | 1000/1200 | 3150/3860 | 550 | 230 | 16 |
| FXBW4-110/160 | 110 | 160 | 1340 | 1000 | 3380 | 550 | 230 | R20 |
| FXBW4-145/120 | 145 | 120 | 1480 | 1240 | 4123 | 725 | 355 | 16 |
| FXBW4-220/100 | 220 | 100 | 2240/2350/2470 | 2020/2080/2210 | 6450/6760/7150 | 1000 | 395 | 16 |
| FXBW4-330/160 | 330 | 160 | 2990 | 2600 | 9075 | 1425 | 570 | R20 |
| FXBW4-220/210(160) | 220 | 210/160 | 2350 | 2000 | 6800 | 1000 | 230 | R20 |
| FXBW4-330/210(160) | 330 | 210/160 | 2930 | 2650 | 8790 | 1425 | 570 | R20 |
| FXBW4-500/210(160) | 500 | 210/160 | 4450 | 4075 | 14860 | 2050 | 740 | R20 |
1.We can produce as per customer's requirements.
2.Corona Ring is necessary at 220kV system and above. For application at 220kV & 230kV, one corona ring should be assembled at the end of Suspension Insulator. While application at 330kV and above, two corona rings should be assembled at both end of insulator.
Composite Pin Insulator
| Model | RatedVoltage(kV) | RatedMechanicalBending Load(kN) | StructureHeight(mm) | Minimum ArcDistance(mm) | MinimumCreepageDistance(mm) | LightningImpulseWithstandVoltage, peak (kV) | P.F 1minwet withstandvoltage(kV) |
| FPQ-11/10 | 11 | 10 | 300 | 180 | 450 | 105 | 45 |
| FPQ-11/12.5 | 11 | 12.5 | 320 | 195 | 450 | 95 | 45 |
| FPQ-15/12.5 | 15 | 12.5 | 280 | 160 | 665 | 145 | 65 |
| FPQ-24/10 | 24 | 10 | 390 | 225 | 744 | 145 | 65 |
| FPQ-24/12.5 | 24 | 12.5 | 390 | 225 | 744 | 145 | 65 |
| FPQW-33/10 | 33 | 10 | 430 | 325 | 1080 | 200 | 70 |
| FPQW-33/10 | 33 | 10 | 495 | 380 | 900 | 200 | 116 |
| FPQW-33/10 | 33 | 10 | 510 | 340 | 1200 | 170 | 70 |
| FPQW-33/12.5 | 33 | 12.5 | 470 | 345 | 1200 | 230 | 95 |
| FPQW-33/20 | 33 | 20 | 545 | 405 | 1650 | 265 | 135 |
Composite Post Insulator
| Model | RatedVoltage(kV) | RatedMechanicalBending Load(kN) | StructureHeight(mm) | Minimum ArcDistance(mm) | MinimumCreepageDistance(mm) | LightningImpulseWithstandVoltage, peak (kV) | P.F 1minwet withstandvoltage(kV) |
| FZSW-11/10 | 11 | 10 | 255 | 175 | 600 | 145 | 45 |
| FZSW-24/10 | 24 | 10 | 300 | 210 | 630 | 145 | 65 |
| FZSW-33/10 | 33 | 10 | 450 | 270 | 900 | 200 | 95 |
| FZSW-33/10 | 33 | 10 | 400 | 285 | 1060 | 200 | 95 |
| FZSW-66/10 | 66 | 10 | 760 | 630 | 1940 | 350 | 185 |
| FZSW-110/10 | 110 | 10 | 1220 | 1060 | 3260 | 450 | 200 |
| FZSW-220/10 | 220 | 10 | 2550 | 2050 | 6520 | 950 | 395 |
Composite Line Post Insulator
| Model | RatedVoltage(kV) | RatedMechanicalBending Load(kN) | StructureHeight(mm) | Minimum ArcDistance(mm) | MinimumCreepageDistance(mm) | LightningImpulseWithstandVoltage, peak (kV) | P.F 1minwet withstandvoltage(kV) |
| FZSW-11/10 | 11 | 10 | 405 | 165 | 430 | 95 | 45 |
| FZSW-24/10 | 24 | 10 | 450 | 320 | 700 | 125 | 65 |
| FZSW-33/10 | 33 | 10 | 570 | 320 | 1080 | 220 | 145 |
| FZSW-33/20 | 33 | 20 | 590 | 358 | 1200 | 200 | 95 |
| FZSW-66/10 | 66 | 10 | 760 | 630 | 1940 | 350 | 185 |
| FZSW-66/12.5 | 66 | 12.5 | 1050 | 790 | 2248 | 350 | 185 |
Porcelain Suspension /Tension Insulator
52 Series Ball Socket & Clevis Tongue Type
STANDARD
ANSI C29.1, ANSI C29.2A,
ANSI C29.2B
VOLTAGE 6KV-33KV
| ANSI CLASS | 52-1 | 52-2 | 52-3 | 52-4 | 52-5 | |
| Porcelain Shell Diameter, D (mm) | 165 | 190 | 254 | 254 | 254 | |
| Unit Spacing, H (mm) | 140 | 146 | 146 | 146 | 146 | |
| Leakage Distance (mm) | 178 | 210 | 292 | 292 | 292 | |
| Mechanical Failing Load (kN) | 44 | 70 | 70 | 70 | 111 | |
| Power Frequency Flashover Voltage | Dry, kV | 60 | 65 | 80 | 80 | 80 |
| Wet, kV | 30 | 35 | 50 | 50 | 50 | |
| Critical Impulse Flashover Voltage | Pos., kV | 100 | 115 | 125 | 125 | 125 |
| Neg., kV | 100 | 115 | 130 | 130 | 130 | |
| Power Frequency Puncture Voltage, kV | 80 | 90 | 110 | 110 | 110 | |
| Radio influence voltage data | Test Voltage to Ground, kV | 7.5 | 7.5 | 10 | 10 | 10 |
| Max RIV at 1000 KHz, uV | 50 | 50 | 50 | 50 | 50 | |
| Net Weight (kgs) | 2.5 | 3.8 | 4.6 | 4.9 | 5.6 | |
Pin Type Insulator
55 Series LV & MV Type
STANDARD ANSI C29.1, ANSI C29.5
| ANSI CLASS | 55-2 | 55-3 | 55-4 | 55-5 | 55-6 | 55-7 | |
| Neck Type | C | C | F | F | J | J | |
| Leakage Distance (mm) | 127 | 178 | 229 | 305 | 381 | 381 | |
| Dry Arcing Distance (mm) | 86 | 114 | 127 | 159 | 203 | 203 | |
| Minimum Pin Length (mm) | 102 | 127 | 127 | 152 | 190 | 190 | |
| Cantilever Strength (kN) | 11 | 11 | 13 | 13 | 13 | 13 | |
| Power Frequency Flashover Voltage | Dry, kV | 45 | 55 | 65 | 80 | 100 | 100 |
| Wet, kV | 25 | 30 | 35 | 45 | 50 | 50 | |
| Critical Impulse Flashover Voltage | Pos., kV | 70 | 90 | 105 | 130 | 150 | 150 |
| Neg., kV | 85 | 110 | 130 | 150 | 170 | 170 | |
| Power Frequency Puncture Voltage, kV | 70 | 90 | 95 | 115 | 135 | 135 | |
| Radio influence Voltage Data | Test Voltage to Ground, kV | 5 | 10 | 10 | 15 | 22 | 22 |
| Max RIV at 1000 KHz, uV | 50 | 50 | 50 | 100 | 100 | 100 | |
| Net Weight (kgs) | 0.75 | 1.1 | 1.7 | 2.9 | 4.4 | 4.4 | |
Pin Type Insulator
BS 11KV 22KV 33KV Pin Type
STANDARD BS 137, IEC 60383
VOLTAGE 11KV-36KV
| BS CLASS | P-11-Y | P-15-Y | P-22-Y | P-33-Y | PW-15-Y P | W-22-Y P | W-33-Y | R90 | ||
| Creepage Distance, mm | 254 | 298 | 432 | 630 | 432 | 673 | 900 | 900 | ||
| Dimensions, mm | H - Height | 130 | 137 | 165 | 244 | 185 | 255 | 249 | 269 | |
| D - Diameter | 140 | 152 | 229 | 280 | 170 | 205 | 225 | 205 | ||
| h - Depth of Thread | 48 | 48 | 52.6 | 52.6 | 52.6 | 52.6 | 52.6 | 70 | ||
| d - Pin Diameter | 18.3 | 18.3 | 27.8 | 27.8 | 27.8 | 27.8 | 27.8 | 90 | ||
| Cantilever Strength, kN | 11 | 11 | 11 | 13 | 11 | 11 | 12 | 10 | ||
| Withstand | One minute Power | Dry, kV | 65 | 70 | 90 | 110 | 90 | 110 | 125 | 110 |
| Voltage | Frequency | Wet, kV | 40 | 50 | 55 | 75 | 60 | 90 | 90 | 95 |
| Impulse Withstand Voltage, kV | 90 | 110 | 150 | 170 | 140 | 180 | 200 | 185 | ||
| Radioinfluence | Test Voltageto Ground, kV | Dry, kV | 15 | 15 | 22 | 30 | 22 | 30 | 33 | 44 |
| VoltageData | Max RIV at1000 KHz, uV | Wet, kV | 8000 | 8000 | 12000 | 16000 | 12000 | 16000 | 20000 | 25000 |
| Power Frequency Puncture Voltage, kV | 150 | 150 | 145 | 210 | 150 | 199 | 210 | 210 | ||
Stay Insulator
54 Series
GY & BS Series
STANDARD BS 137
3 VOLTAGE
0.4KV-33KV
| ANSI CLASS | 54-1 | 54-2 | 54-3 | 54-4 | |
| Dimensionsmm | Height | 89 | 108 | 140 | 171 |
| Hole CentersSpacing | 44 | 57 | 79 | 67 | |
| Inner Diameter | 44 | 54 | 60 | 60 | |
| Outer Diameter | 64 | 73 | 86 | 89 | |
| Hole Diameter | 16 | 22 | 25 | 25 | |
| Height to Hole | Max 63 | Max 76 | Max 103 | Max 114.3 | |
| Mechanical Failing Load, kN | 44 | 53 | 89 | 89 | |
| PowerFrequencyFlashoverVoltage | Dry, kV | 25 | 30 | 35 | 40 |
| Wet, kV | 12 | 15 | 18 | 23 | |
| Net Weight, kgs | 0.5 | 0.65 | 1.2 | 2.2 | |
| Guy Strain Insulators for Lines | BS 137 | |||
| Type | 1075 | 0522 | 3257G | |
| Dimensionsmm | Height | 78 | 140 | 220 |
| Hole CenterDistance | 50 | 62 | 80 | |
| Inner Diameter | 37 | 60 | 120 | |
| Outer Diameter | 57 | 85 | 135 | |
| Hole Diameter | 19 | 19 | 22 | |
| Mechanical Failing Load, kN | 45 | 110 | 110 | |
| PowerFrequencyFlashoverVoltage | Dry, kV | 30 | 35 | 52 |
| Wet, kV | 15 | 20 | 48 | |
| Net Weight, kgs | 1 | 1.4 | 4.8 | |
Spool Insulator
53 Series
STANDARD ANSI C29.1, ANSI C29.3
| SPOOL INSULATORS | ANSI | |||||
| Type | 53-1 | 53-2 | 53-3 | 53-4 | 53-5 | |
| Mechanical Failing Load, kN | 8.9 | 13.3 | 17.8 | 20 | 26.7 | |
| Power frequencyDry Flashover, kV | 20 | 25 | 25 | 25 | 35 | |
| PowerFrequencyWetFlashover kV | Vertical | 8 | 12 | 12 | 12 | 18 |
| Horizontal | 10 | 15 | 15 | 15 | 25 | |
| Dimensionsmm | Height | 54 | 76 | 81 | 76 | 105 |
| Diameter | 57 | 79 | 76 | 105 | 102 | |
| Neck Diameter | 45 | 45 | 45 | 73 | 73 | |
| Hole Diameter | 18 | 18 | 18 | 18 | 18 | |
| Grooves Radius | 11 | 18 | 11 | 16 | 11 | |
| Net Weight, kgs | 0.2 | 0.55 | 0.6 | 1.1 | 1.16 | |
| BS CLASS Type | ED-2 | ED-2B | ED-3 | 1617 | |
| Mechanical Failing Load, kN | 10 | 12.5 | 8 | 15 | |
| PowerFrequencyWetFlashover kV | Dry | 18 | 23 | 16 | 20 |
| Wet | 9 | 12 | 7 | 9 | |
| Dimensionsmm | Height | 75 | 76 | 65 | 65 |
| Diameter | 80 | 86 | 70 | 76 | |
| Neck Diameter | 42 | 48 | 36 | 46 | |
| Hole Diameter | 20 | 21 | 16 | 17.5 | |
| Grooves Radius | 10 | 10 | 8 | 9 | |
| Net Weight, kgs | 0.4 | 0.48 | 0.25 | 0.4 | |
Line Post Insulator
57 Series Tie Top Type
STANDARD ANSI C29.7
| ANSI CLASS | 57-1 | 57-2 | 57-3 | 57-4 |
| Creepage Distance, mm | 356 | 559 | 737 | 1015 |
| Dry Arcing Distance, mm | 165 | 241 | 311 | 368 |
| Cantilever Strength, kN | 12.5 | 12.5 | 12.5 | 12.5 |
| Power FrequencyFlashover - Dry, kV | 70 | 100 | 125 | 140 |
| Power FrequencyFlashover - Wet, kV | 50 | 70 | 95 | 110 |
| Critical Impulse FlashoverVoltage - Pos, kV | 120 | 160 | 200 | 230 |
| Test Voltage to Ground, kV | 15 | 22 | 30 | 44 |
| Maximum RIV at 1000KHZ, μv | 100 | 100 | 200 | 200 |
| Net Weight, kgs | 4.8 | 7.8 | 11.0 | 18.0 |
Glass Disc Suspension Insulator
STANDARD IEC 60383-1,IEC60383-2
3 VOLTAGE 6KV-33KV
| IEC CLASS | Normal Type | Anti-pollution Type | |||||
| U70BL | U100BL | U120B | U70BLP | U100BLP | U120BP | ||
| Type | XP-70 | XP-100 | XP-120 | XHP-70 | XHP-100 | XHP-120 | |
| Nominal Diameter (mm) | 255 | 255 | 255 | 255 | 255 | 255/280 | |
| Spacing, H (mm) | 146 | 146 | 146 | 146 | 146 | 146 | |
| Coupling Size | 16 | 16 | 16 | 16 | 16 | 16B | |
| Nominal Creepage Distance, mm | 295/320 | 295/320 | 295/320 | 432/450 | 432/450 | 432/450 | |
| Mechanical Failing Load, kN | 70 | 100 | 120 | 70 | 100 | 120 | |
| Power Frequency | Dry, kV | 70 | 70 | 70 | 80 | 80 | 80 |
| Withstand Voltage | Wet, kV | 40 | 40 | 40 | 42 | 42 | 42 |
| Dry Lightning ImpulseWithstand Voltage, kV | 100 | 100 | 100 | 120 | 120 | 120 | |
| Power Frequency PunctureVoltage, kV | 130 | 130 | 130 | 130 | 130 | 130 | |
| Net Weight (kgs) | 4.6 | 5.7 | 6 | 6.1/6.3 | 7.7|7.9 | 8/8.2 | |
Insulator Fitting
Aluminum Binding Wire
Aluminum BindingWire for use on Overhead Power Lines Operating at voltage of up to 33kV 50Hz. a)Aluminum BindingWire, Bare (BS 2627), 3.65mm (SWG 9) diameter plain aluminum for AAC & ACSR b)Aluminum Binding Wire, PVC Covered (BS 6746)
Preformed Top & Side Tie
Preformed Top & Side Tie are used for securing bare conductors into the top groove of insulators. Material:Aluminum-clad steel with an elastomer pad.
Insulators: Φ 57mmC Neck), Φ 73mm (F neck) and Φ 89mm (J neck)
Applicable conductor:ACSR, All-Aluminum, Aluminum Alloy and etc.
| Size | Length (mm) | Identification Mark | Color Code |
| 50mm² | 640 | Black | Yellow |
| 100mm² | 640 | Black | Orange |
| 150mm² | 889 | Black | Red |
| 200mm² | 889 | Black | Blue |
Insulator Fitting
Spindle
Material: Hot dip Galvanized Forged Steel Threads: Nylon Alloy, lead or Steel
Dimensions of small steel insulator pin head
Dimensions of large steel insulator pin head
Insulator Fitting
Insulator pin with small steel head (minimum failing load 10 kN)
Dimensions in millimetres
Insulator pin with large steel head
Small steel head
Note: A washer is required if an insulator pin with a 50 mm shank is to be used with a crossarm 7 mm or less in thickness.
Note: A washer is required if an insulator pin with a 50 mm shank is to be used with a crossarm 7 mm or less in thickness.
| Referencenumber | Minimumfailing loadkN | Amm | ∅ B min.mm | ∅Cmm | ∅ D min.mm | ∅Emm | Fmm | (RG)mm | XA)mm |
| 26 | 5 | 165 | 37 | 24 | 24 | 18 | 5 | 13 | 50 or 130 |
| 28 | 5 | 230 | 40 | 24 | 28 | 22 | 6 | 13 | 50 or 130 |
| 30 | 5 | 305 | 43 | 24 | 31 | 22 | 6 | 13 | 50 or 130 |
| 27 | 10 | 165 | 43 | 24 | 31 | 18 | 6 | 13 | 50 or 130 |
| 29 | 10 | 230 | 50 | 25 | 37 | 22 | 6 | 13 | 50 or 130 |
| 31 | 10 | 305 | 63 | 27 | 40 | 22 | 6 | 16 | 50 or 130 |
Insulator Fitting
Pilot insulator pin
Details of pilot insulator pin
| Reference number of pin | Type of head | Referencenumber of head | |
| Length | |||
| 400 mm | 500 mm | ||
| 1 | 49 | Small steel | 15 |
| 45 | 50 | Large steel | 16 |
| Stocknumber | A | E | G | K | M |
| LR7631 | 7 | 3" | 1" | 13/8" | 2 3/8" |
Insulator Fitting
Distribution Insulator Pins
| Stock number | A |
| LR7794Z | 1 3/8" |
| LR7795Z | 1 |
Insulator Fitting
Pole top pins
| Stock code number | Overall length | Size Steel | Mounting Holes | Approx. ShippingWeight Poundsper 100 Pieces | ||
| Number | Spacing | |||||
| A | ||||||
| B | C | |||||
| Pressed steel channel, 1 inch lead thread | ||||||
| LR8076 | 15 | 1 7/8 × 1 5/16 | 2 | 5 | - | 284 |
| LR8079 | 18 | 1 7/8× 1 5/16 | 3 | 8 | 5 | 340 |
| LR8083 | 24 | 1 7/8 × 1 5/8 | 3 | 8 | 6 | 620 |
| Pressed steel channel, | 1 3/8 inch lead thread | |||||
| LR8086 | 20 | 1 7/8 × 1 1/2 | 2 | 8 | - | 453 |
| LR8087 | 24 | 1 7/8× 1 5/8 | 2 | 8 | - | 680 |
| Straight channel, 1 3 | /8 inch lead thread | |||||
| LR8105 | 24 | 1 3/4×5/8×1/8 | 2 | 8 | - | 720 |
| Straight angle, 1 | inch lead thread | |||||
| LR8106 | 18 | 2×2×3/16 | 2 | 8 | - | 380 |
| LR8107 | 24 | 2×2×3/16 | 2 | 8 | - | 550 |
| LR8108 | 30 | 2×2×3/16 | 2 | 8 | 一 | 750 |
| Extra strong pipe, 1– | 3/8 inch lead thread | |||||
| LR8122 | 24 | 1-1/2 | 2 | 8 | - | 820 |
| LR8123 | 26 | 1-1/2 | 2 | 8 | - | 960 |
| LR8124 | 28 | 1-1/2 | 2 | 8 | 一 | 1035 |
| LR7788 | 22 | 1-1/2 | Custom dimensions | |||
Insulator Fitting
D iron
| Size | Dimensions | ||||
| T | H | L | ① | M | |
| 8×45×105×120 | 8 | 105 | 120 | 18 | M16 |
| 5×40×80×110 | 5 | 80 | 110 | 18 | M16 |
| 6×38×80×108 | 6 | 80 | 108 | 18 | M16 |
| 6×40×80×120 | 6 | 80 | 120 | 18 | M16 |
| 4×40×70×100 | 4 | 70 | 100 | 16 | M16 |
Insulated Secondary & Deadend
Features
●Clevis mounting holes are for 5/8”bolts
●Mounting holes are slotted to permit installation without removing insulators
●Insulators must be ordered separately
Material
Steel hot dip galvanized
| Catalog number | Weight /100 (lbs) |
| LR0313 | 118 |
| LR0342 | 152 |
Insulator Fitting
Insulated Secondary & Deadend
Features
●The LR250 has two sharp projections in the back to prevent it from twisting
●The cotter belt is held in position by means of the same type of tab that is used on the LR252
Material
Steel hot dip galvanized
| Catalog number | A | For use w/insulator catalog | Weight /100 (Ibs) |
| LR250 | LR151 or LR101 | 152 | |
| LR1398 | 31/2 | LR151 or LR101 | 240 |
| LR1399 | 4 | LR151 or LR101 | 254 |
Insulated Secondary & Deadend
The LR252 and LR255 Secondary Pulley Brackets are designed for use both as stringing pulleys and as secondary clevises, making them especially useful for stringing and sagging conductors.
The conductor is strung and sagged with the bracket in the pulley position where it cannot bind. The 908 slot in the base makes it possible to rotate the bracket into the clevis position before or after the conductor is tied to the spool.
Features
●LR252 light-type has a metal tab which contains the insulator bolt
The cotter bolt of the LR255 heavy duty-type threads into the bottom of the clevis, locking the special Twist-Lock head into a groove in the clevis top
●Both features eliminate the cotter pin
Material
| Catalog number | Width | For use w/insulator catalog | Weight /100 (lbs) |
| LR252 | 25/8 | LR151 or LR101 | 150 |
| LR255 | 3 | LR151 or LR101 or LR0101 | 260 |
Insulator Fitting
Insulated Secondary & Deadend
Features
●Economical secondary clevis for standard 3 inch spool insulator
Material
Steel hot dip galvanized
| Catalog number | For use w/insulator catalog | Weight /100 (lbs) |
| LR1394 | LR151 or LR101 | 124 |
Insulated, Swinging
Features
●The LR0322 and LR1614 are used with 5/8 inchor larger eyebolts or eyenuts giving a flexible mounting for equalizing strains at corners
●The LR1626 can be bolted to crossarms to provide an insulated deadend assembly
Material
Steel hot dip galvanized
| Catalog number | Weight /100 (lbs) |
| LR0322 | 160 |
| LR1614 | 45 |
| LR1626 | 95 |
Insulator Fitting
Secondary Rack
Application
Secondary Rack comes in three different class and type of application; either single, two or three spool type for light, medium and heavy duty class respectively. Insulator post struts are rounded to assure it will not damage insulation when stringing secondary. Struts are electricity arc welded and riveted for heavy and medium duty class respectively. ANSl class 52-3 and 52-2 insulator will fit the heavy and medium duty rack respectively.
| Stock No. | No.of Wire(mm) | Wire Spacing (mm) | Length (mm) | Approximate Ship Weight kg./100 Pcs. | Standard Pkg. Qty./Carton |
| LR0320-H3 | 3 | 200 | 605 | 360.00 | 5 |
| LR0320-H2 | 2 | 200 | 450 | 204.00 | 5 |
| Stock No. | No.of Wire(mm) | Wire Spacing (mm) | Length (mm) | Approximate Ship Weight kg./100 Pcs. | Standard Pkg. Qty./Carton |
| LR0321-M3 | 3 | 200 | 524 | 250.00 | 5 |
| LR0321-M2 | 2 | 200 | 340 | 160.00 | 5 |
| Stock No. | No.of Wire(mm) | Wire Spacing (mm) | Length (mm) | Approximate Ship Weight kg./100 Pcs. | Standard Pkg. Qty./Carton |
| LR0321-L3 | 3 | 200 | 524 | 360.00 | 5 |
| LR0321-L2 | 2 | 200 | 340 | 204.00 | 5 |
Surge Arrester
Application
Massive productions of surge arrester (MOA), either with porcelain or polymeric housing, are suitable in the systems of power generation, power transmission, power transformation, and power distribution under AC 220kV and below. They are mainly used to keep the amplitude of lighting impulse withstand voltage and switching impulse withstand voltage to the prescribed level.
Operating Principle
Surge arrester is the most advanced over-voltage protector in the world. Its core element, metal oxide varistor (MOV).
Under the circumstance of normal operating voltage, the current through the surge arrester is just on microampere degree. When suffered from over-voltage, the surge arrester's excellent nonlinear characteristic will make the current through the surge arrester increase to several thousand amperes. And the surge arrester will be under the circulating state and release overvoltage energy so as to protecting the power transmission equipment against the damage caused by the over-voltage.
Condition of Use
●Ambient air temperature within the range of -40℃ to +40℃;
●Altitude above sea level not exceeding 2,000m;
●Frequency of the A.C. power supply being 50Hz or 60Hz;
●Power frequency voltage applied continuously between the terminals of the arrester not exceeding its continuous operating voltage.
●Maximum wind speed not exceeding35m/s:
●The earthquake intensity not exceeding7 degrees.
Characteristics
●Low residual voltage
●Long protection distance
High energy input capacity
●Stable volt-ampere characteristic even after multiple strokes
●Proof against ageing
●Explosion and shatter-resistant design
●Pollution resistant and UV-stable
●Housing resistant to rough handling
●Maintenance free
●Stable against shock and vibration
●High mechanical resistance
| Model Designation①②③ ④ ⑤⑥Type categoryY-metal oxide typeHY-polymeric housed surge arrester | ||
| ② | Rated discharge current (kA) | |
| ③ | Design featureW-without gapsC-with series gaps | |
| ④ | Rated voltage of surge arrester (kV) | |
| ⑤ | Max residual voltage under rated current (kV) | |
| ⑥ | Additional featureL-disconnector | |
Technical Standard
The technical confirms to IEC60099-4.
Metal-oxide Varistor(MOV)
Application
Metal-oxide Varistors (MOVs) are the core element of an arrester, which are sintering mainly of ZnO powder with addition of Bio,, Co,0,, Cr.o, Sb,O, and insition.
Metal oxide varistors have good response to steep front surge, excellent volt-ampere characteristics and high discharge capability. which provides a very consistent protection merit at steep front surge, lighting surge and switching surge, and enhances protective capability.
Typical Voltage-current(U-I) Characteristic Curve of Metal-oxide Varistor
Surge Arrester
Polymeric Housed Surge arrester without Gaps
Porcelain Housed Surge arrester without Gaps
LV surge arrester
Technical requirements
●System nominal voltage: 0.38KV
●Arrester's rated voltage: 0.50KV
●Continuous operating vohage: 0.42KV
●LightningImpulse current residual voltage(KV P.≤): 2.6KV
●DC IMa reference voltage(≥): 1.2KV
●Current throughput at rectangular current impulse 2ms-50A
●Creapage distance: 45mm
Surge Arrester
Drop out type surge arrester
| Type | Rated voltage | Maximun continuous operating voltage | 1/4us Lightning current impulse | 8/20us Lightning current impulse |
| kV | kV | kV(peak) | kV(peak) | |
| HY5W-12 | 12 | 10.2 | 42.2 | 36 |
| HY5W-36 | 36 | 29.0 | 123.0 | 108 |
| HY10W-12 | 12 | 10.2 | 42.2 | 36 |
| HY10W-36 | 36 | 29.0 | 123.0 | 108 |
| Type | Ratedvoltage | Maximun ContinuousOperating Voltage | 1/4us LightningCurrent impulse | 8/20us LightningCurrent impulse | 30/60us SwitchingCurrent impulse | 2ms Rectangularcurrent impulsewithstand | 4/10us High currentimpulse withstand |
| kV | kV | kV(peak) | kV(peak) | kV(peak) | A | kA(crest) | |
| HY5W-3 | 3 | 2.55 | 11.3 | 9 | 8.9 | 120-200 | 65-75 |
| HY5W-6 | 6 | 5.1 | 22.6 | 18 | 16.8 | 120-200 | 65-75 |
| HY5W-9 | 9 | 7.65 | 33.7 | 27 | 23.8 | 120-200 | 65-75 |
| HY5W-10 | 10 | 8.4 | 36.0 | 30 | 23 | 120-200 | 65-75 |
| HY5W-11 | 11 | 9.4 | 40.0 | 33 | 30 | 120-200 | 65-75 |
| HY5W-12 | 12 | 10.2 | 42.2 | 36 | 27 | 120-200 | 65-75 |
| HY5W-15 | 15 | 12.7 | 51.0 | 45 | 38.5 | 120-200 | 65-75 |
| HY5W-18 | 18 | 15.3 | 61.5 | 54 | 46.2 | 120-200 | 65-75 |
| HY5W-21 | 21 | 17.0 | 71.8 | 63 | 54.2 | 120-200 | 65-75 |
| HY5W-24 | 24 | 19.5 | 82.0 | 72 | 62 | 120-200 | 65-75 |
| HY5W-27 | 27 | 22.0 | 92.0 | 81 | 69.8 | 120-200 | 65-75 |
| HY5W-30 | 30 | 24.4 | 102.0 | 90 | 79 | 120-200 | 65-75 |
| HY5W-33 | 33 | 27.5 | 112.0 | 99 | 86.7 | 120-200 | 65-75 |
| HY5W-36 | 36 | 29.0 | 123.0 | 108 | 95.4 | 120-200 | 65-75 |
| HY5W-42 | 42 | 34.1 | 132.3 | 126 | 100.1 | 120-200 | 65-75 |
| Type | Ratedvoltage | Maximun ContinuousOperating Voltage | 1/4us LightningCurrent impulse | 8/20us LightningCurrent impulse | 30/60us SwitchingCurrent impulse | 2ms Rectangularcurrent impulsewithstand | 4/10us High currentimpulse withstand |
| kV | kV | kV(peak) | kV(peak) | kV(peak) | A | kA(crest) | |
| HY10W-3 | 3 | 2.55 | 11.3 | 9 | 8.9 | 250-400 | 100 |
| HY10W-6 | 6 | 5.1 | 22.6 | 18 | 16.8 | 250-400 | 100 |
| HY10W-9 | 9 | 7.65 | 33.7 | 27 | 23.8 | 250-400 | 100 |
| HY10W-10 | 10 | 8.4 | 36.0 | 30 | 23 | 250-400 | 100 |
| HY10W-11 | 11 | 9.4 | 40.0 | 33 | 30 | 250-400 | 100 |
| HY10W-12 | 12 | 10.2 | 42.2 | 36 | 27 | 250-400 | 100 |
| HY10W-15 | 15 | 12.7 | 51.0 | 45 | 38.5 | 250-400 | 100 |
| HY10W-18 | 18 | 15.3 | 61.5 | 54 | 46.2 | 250-400 | 100 |
| HY10W-21 | 21 | 17.0 | 71.8 | 63 | 54.2 | 250-400 | 100 |
| HY10W-24 | 24 | 19.5 | 82.0 | 72 | 62 | 250-400 | 100 |
| HY10W-27 | 27 | 22.0 | 92.0 | 81 | 69.8 | 250-400 | 100 |
| HY10W-30 | 30 | 24.4 | 102.0 | 90 | 79 | 250-400 | 100 |
| HY10W-33 | 33 | 27.5 | 112.0 | 99 | 86.7 | 250-400 | 100 |
| HY10W-36 | 36 | 29.0 | 123.0 | 108 | 95.4 | 250-400 | 100 |
| HY10W-42 | 42 | 34.1 | 133.0 | 126 | 100.1 | 250-400 | 100 |
| Type | Ratedvoltage | Maximun ContinuousOperating Voltage | 1/4us LightningCurrent impulse | 8/20us LightningCurrent impulse | 30/60us SwitchingCurrent impulse | 2ms Rectangularcurrent impulsewithstand | 4/10us High currentimpulse withstand |
| kV | kV | kV(peak) | kV(peak) | kV(peak) | A | kA(crest) | |
| HY10W-3 | 3 | 2.55 | 10 | 9 | 8 | 250-400 | 100 |
| HY10W-6 | 6 | 5.1 | 20 | 18 | 16 | 250-400 | 100 |
| HY10W-9 | 9 | 7.65 | 31 | 27 | 24 | 250-400 | 100 |
| HY10W-10 | 10 | 8.4 | 35 | 30 | 26 | 250-400 | 100 |
| HY10W-11 | 11 | 9.4 | 38 | 33 | 29 | 250-400 | 100 |
| HY10W-12 | 12 | 10.2 | 41 | 36 | 32 | 250-400 | 100 |
| HY10W-15 | 15 | 12.7 | 51 | 45 | 40 | 250-400 | 100 |
| HY10W-18 | 18 | 15.3 | 62 | 54 | 48 | 250-400 | 100 |
| HY10W-21 | 21 | 17.0 | 72 | 63 | 56 | 250-400 | 100 |
| HY10W-24 | 24 | 19.5 | 82 | 72 | 64 | 250-400 | 100 |
| HY10W-27 | 27 | 22.0 | 93 | 81 | 72 | 250-400 | 100 |
| HY10W-30 | 30 | 24.4 | 103 | 90 | 81 | 250-400 | 100 |
| HY10W-33 | 33 | 27.5 | 113 | 99 | 89 | 250-400 | 100 |
| HY10W-36 | 36 | 29.0 | 124 | 108 | 97 | 250-400 | 100 |
| HY10W-42 | 42 | 34.1 | 145 | 126 | 113 | 250-400 | 100 |
| Type | Ratedvoltage | Maximun ContinuousOperating Voltage | 1/4us LightningCurrent impulse | 8/20us LightningCurrent impulse | 30/60us SwitchingCurrent impulse | 2ms Rectangularcurrent impulsewithstand | 4/10us High currentimpulse withstand |
| kV | kV | kV(peak) | kV(peak) | kV(peak) | A | kA(crest) | |
| HY10W-60 | 60 | 48 | 208 | 180 | 160 | 2600-900 | 100 |
| HY10W-66 | 66 | 52.8 | 230 | 198 | 172 | 600-900 | 100 |
| HY10W-72 | 72 | 57.6 | 252 | 216 | 184 | 600-900 | 100 |
| HY10W-78 | 78 | 62.4 | 274 | 234 | 196 | 600-900 | 100 |
| HY10W-84 | 84 | 67.2 | 296 | 252 | 208 | 600-900 | 100 |
| HY10W-90 | 90 | 72 | 318 | 270 | 220 | 600-900 | 100 |
| HY10W-96 | 96 | 76.8 | 340 | 288 | 232 | 600-900 | 100 |
| HY10W-102 | 102 | 81.6 | 362 | 306 | 244 | 600-900 | 100 |
| HY10W-108 | 108 | 86.4 | 384 | 324 | 256 | 600-900 | 100 |
| HY10W-120 | 120 | 96 | 428 | 360 | 280 | 600-900 | 100 |
| HY10W-150 | 150 | 120 | 538 | 450 | 340 | 600-900 | 100 |
| HY10W-200 | 200 | 160 | 720 | 600 | 440 | 600-900 | 100 |
Accessories of Surge Arrester
Surge arrester Counter
When installed, the discharge counters series between the surge arresters and the ground, that is to say, paralleled on the two sides of the flange of the arrester insulated base. Firstly, scraping the paint surface of the two 10-hole installation holes of the flange of the discharge counter, in order to ensure good contact. Using M10\*40 bolts to install the discharge counter beside the base of the surge arrester, to facilitate the observation of head-up position and grounding as a client. Then, using M10\* 30 bolts andgeneratrix on High-pressure out-line side to connect on the upper part flange of the base of the surge arrester. Check the discharge counter after installation, there should be no obvious tilt phenomenon. If the discharge counter indicators don't point to zero, should mobilize in accordance with the user notice. At this point, the discharge count can be put into operation. Pay attention that during the installation, the red painted M10 nut and six M6\*20 bolts on the soleplate are not free loose, so as not to undermine the seal.
Green: Shows that the tested leakage current is in the range of nominal operating current, the surge arrester operates normally. Yellow: Shows that the tested leakage current is not in the range of nominal operating current, the circuitry and the surge arrester demand to be examined or replaced.
Red: Shows that the tested leakage current has overtopped the range of nominal operating current, the surge arrester must be examined and replaced.
| Maily Capability | Unit | Type of Product | |
| JCQ-2/800 | JCQ-5/1800 | ||
| Applicable Power SystemRated Voltage | kV (rms) | 6~220 | 330~500 |
| Nominal Discharge CurrentLevel 8/20μs | kA (crest) | 10 | 1020 |
| Count Current Range8/20μs | kA (crest) | 50~10000 | 50~1000050~20000 |
| Residual Voltage under NominalDischarge Current 8/20μ s | kA (crest) | ≤3.0 | ≤3.0 |
| 2000μs 18 times RectangularCurrent Impluse Withstand | A (crest) | 80015002000 | 80015002000 |
| 4/10 μ s 2 times High CurrentImpluse Withstand | A (crest) | 65 | 100 |
| Current Survey Range | mA | 0~2 | 0~5 |
| Count Range | Trinity (888) | ||
Accessories of Surge Arrester
Surge arrester disconnector
Both polymeric and porcelain housed surge arrester can put up the disconnector. The disconnector is equipped with the insulation base. The top bolt is directly connected with the bottom of surge arrester, the below bolt is connected with ground lead.
The disconnector shall break away automatically at the fault current while the surge arrester failure under the abnormal conditions and the failed lightning arrester will be separated.
Note: The last "L"in the designation means the disconnector. L:With disconnector
No L: Without disconnector.
The disconnector's ampere-second characteristics
| Current(A) | 800 | 200 | 20 | 5 | 0.5 | 0.05 |
| Operation time(s) | 0.01-0.02 | 0.02-0.05 | 0.1-0.2 | 0.5-1.0 | 20-50 | 200-500 |
Surge arrester insulation bracket
●Insulation bracket is for supporting and fixing arresters onto steel mounting bracket or cross arm, it's a insulation part of an Arrester.
●It has the characteristics of high insulation level, high mechanical strength, heat resistance and corrosion resistance.
Dustproof Cap
●For polymeric housed lightning arrester, the dust proof cap is on your choice.
●For porcelain housed lightning arrester, the dust proof cap is not required.
Dropout Fuse Cutout
Introduction
Dropout Fuse Cutout is a kind of outdoor used high voltage protective device. To be connected with incoming feeder of distribution transformer or distribution line it mainly protect transformer or lines from short circuit and overload, and on/off loading current.
Dropout Fuse Cutout is composed of insulator supports and fuse tube, static contacts is fixed on two sides of insulator support and moving contact is installed on two ends of fuse tube. Fuse tube is composed of inside extinguishing tube,outer phenolic compound paper tube or epoxy glass tube.Load switching fuse cutout provides enforced elastic auxiliary contacts and arc-extinguishing enclosure for switching on/off loading current. At normally working via fuse link tightened the fuse tube is fixed to form up of close position. In case system occur faults, fault current result in fuse melt immediately and take place electric arc, which let arc-extinguishing tube being heated and explode a lot of gas. This will produce high pressure and blow off the arc along with tube.
After fuse link melt moving contact has no tightened strength again, mechanism is locked and fuse tube dropout. Cutout now is in open position.
When it needs to switch off during cut out loading. Operator shall via insulating operating bar pull the moving contact, at its beginning main contact and auxiliary static contactis contacted still.
Whiling pulling the auxiliary contact is separated between auxiliary contacts there occur electric arc and the arc will be lengthened in arcextinguishing enclosure gap and meanwhile arc-extinguishing explode gas to blow off the arc during current passing zero.
Material: Silicone rubber or Porcelain.
Manufacturing Standard: IEC 60282-2.
Dropout Fuse Cutout
Structural characteristics
Drop-out fused cut out and load Switching fuse cutout are of outdoor used high voltage protective device. To be connected with incoming feeder of distribution transformer or distribution line it mainly protect transformer or lines from short circuit and overload, and on/off loading current.
Drop-out fuse cutout is com-posed of insulator supports and fuse tube, static contacts is fixed on two sides of insulator support and moving contact is installed on two ends of fuse tube. Fuse tube is composed of inside arc-estinguishing tube, outer phenolic compound paper tube or epoxy glass tube.
Load switching fuse cutout provides enforced elastic auxiliary contacts and arc-extinguishing enclosure for switching on/off loading current. At normally working via fuse link tightened the fuse tube is fixed to form up of close position.
In case system occur faults, fault current result in fuse melt immediately and take place electric arc, which let arcextinguishing tube being heated and ex-plode a lot of gas. This will produce high pressure and blow off the arc along with tube.
After fuse link melt moving contact has no tightened strength again, mechanism is locked and fuse tube dropout.
Cutout now is in open position.When it needs to switch off during cut out loading. operator shall via insulating operating bar pull the moving contact, at its beginning main contact and auxiliary static contact is contacted still.
Whiling pulling the auxiliary contact is separated between auxiliary contacts there occur electric arc and the arc will be lengthened in arc-extinguishing enclosure gap and meanwhile arc-extingushing explode gas to blow off the arc during current passing zero.
●Parallel-groove connector
Tin plated cast red brass. For ease of conductor connection, accommodates two conductors of unlike size in a single connector. Other styles of connectors are also available
●Bird proof-design insulator Higher insulation characteristics than ANSI distribution-cutout standards.
●Rugged attachment hooks for load buster guide tube during closing
●Upper contacts
Silver-to silver ;stainless-steel spring provides high contact pressure
● Fuse tube
Features Multi Wind liner that's virtually impervious to water ingress.Special UV resistant finish as-sureslonglife.Models also available with disconnect blade
●Trunnion
High-strength cast bronze, silver plated. Surfaces around trunnoon bear on bro hinge surfaces to keep tube in alignment during closing
●Lower contacts
(Not visible)-silver-to-silver;providedual current path, independent of hinge pivot. Stainless-steel backup springs prevent arcing when tube rises in hinge during recoil
● Connector
Reliable tripping after disconnecting
Sturdy ferrules
Pinned to top and bottom of tube for permanent alignment. Either the large, accessible lifting
● Fliper
Gives high-speed terminal separation, quick cable flip-out, and(in conjunction with the toggle joint) reduces transmission of forces to fuse link
●Trunnion pocket
Secures tube in hinge during closing
Dropout Fuse Cutout
●Parallel-groove connector Tinned for No.6 soild through 250 KC mil stranded copper or aluminum.
● Recoil bar Heavy galvanized steel(which is also used for inserts, hangers, structural bolts and nuts)
● Bria proor–aesign insuiator Higher insulation characteristics than ANSI distribution-cutout standards and equal in most cases to ANSl switch and bus standards
Notvisible-silver-to-silver,provide dual current path,independent of hingepivot,Stainless-steel backup springs prevent arcing when tube rises in hinge during recoil
●Upper Contacts Silver-to-siver at both surfaces
●Attachment hooks For load buster. Heavy construction also serves to guide tube during closing
● Fuse tube Fiber-lined epoxy fiber glass ● Toggle joint Collapses to permit dropout when link severs
Pinned to top and bottom of tube for permanent alignment, Large, accessible lifting ring.
●Trunnion pocket secures tube in hinge during closing
●Trunnion casting surfaces around trunnion bear on broad hinge surfaces to keep tube in alignment during closing
• Flipper
gives high-speed terminal separation, quick cable flip-out, and(in concoction with the toggle joint) reduces transmission of forces to fuse link during closing
1 Back plate
2 Long Bolts
3 Mounting Bracket
4 Mounting Bracker
5 Porcelain Insulator
6 Spring Washer
7 Upper Housing
8Fuse Tube
9 Lower Housing
10 Toggle Joint
11 Connector
12 Upper Contacts
13 Attachment Hooks
14 Operation Ring
Dropout Fuse Cutout
| Type model | Rated voltage(kV) | Rated current(A) | Breaking current(kA) | Impulse voltageBIL (kV) | Power frequencywithstand voltage (kV) | Leakage distance(mm/kV) | Material |
| (H)RW-11/100 | 11 | 100 | 6.3 | 100 | 35 | 25-31 | Polymer/Porcelain |
| (H)RW-11/200 | 11 | 200 | 10.0 | 100 | 35 | 25-31 | Polymer/Porcelain |
| (H)RW-11/400 | 11 | 400 | 12.5 | 100 | 35 | 25-31 | Polymer/Porcelain |
| (H)RW-12/100 | 12 | 100 | 6.3 | 110 | 40 | 25-31 | Polymer/Porcelain |
| (H)RW-12/200 | 12 | 200 | 10.0 | 110 | 40 | 25-31 | Polymer/Porcelain |
| (H)RW-15/100 | 15 | 100 | 6.3 | 125 | 45 | 25-31 | Polymer/Porcelain |
| (H)RW-15/200 | 15 | 200 | 10.0 | 125 | 45 | 25-31 | Polymer/Porcelain |
| (H)RW-18/100 | 18 | 100 | 6.3 | 130 | 50 | 25-31 | Polymer/Porcelain |
| (H)RW-18/200 | 18 | 200 | 10.0 | 130 | 50 | 25-31 | Polymer/Porcelain |
| (H)RW-21/100 | 21 | 100 | 6.3 | 140 | 58 | 25-31 | Polymer/Porcelain |
| (H)RW-21/200 | 21 | 200 | 10.0 | 140 | 58 | 25-31 | Polymer/Porcelain |
| (H)RW-24/100 | 24 | 100 | 6.3 | 150 | 65 | 25-31 | Polymer/Porcelain |
| (H)RW-24/200 | 24 | 200 | 10.0 | 150 | 65 | 25-31 | Polymer/Porcelain |
| (H)RW-27/100 | 27 | 100 | 6.3 | 160 | 68 | 25-31 | Polymer/Porcelain |
| (H)RW-27/200 | 27 | 200 | 10.0 | 160 | 68 | 25-31 | Polymer/Porcelain |
| (H)RW-30/100 | 30 | 100 | 6.3 | 170 | 70 | 25-31 | Polymer/Porcelain |
| (H)RW-30/200 | 30 | 200 | 10.0 | 170 | 70 | 25-31 | Polymer/Porcelain |
| (H)RW-33/100 | 33 | 100 | 6.3 | 175 | 75 | 25-31 | Polymer/Porcelain |
| (H)RW-33/200 | 33 | 200 | 10.0 | 175 | 75 | 25-31 | Polymer/Porcelain |
| (H)RW-33/400 | 33 | 400 | 12.5 | 175 | 75 | 25-31 | Polymer/Porcelain |
| (H)RW-36/100 | 36 | 100 | 6.3 | 180 | 80 | 25-31 | Polymer/Porcelain |
| (H)RW-36/200 | 36 | 200 | 10.0 | 180 | 80 | 25-31 | Polymer/Porcelain |
Dropout Fuse Cutout
Maunting bracket.Adjustable for 3 " x 4" t04 \*x 5" crossarm.
Fumished only when catalog number suffix "b"or\*c"is specified.
Optional parallel groove connector shown furnished only when catalog number suffix,d, is specified.
Notes:
1. add connector suffix per table 1.
2. dimension shown is for'c'suffix(nema 'b' bracket)
3. dimension is 53/16 for 'b' suffix fuerte extended bracket.'d' suffix only.
Extended Mounting Braket-Adjustable for3\*x4"to 4 "x5'Crossarm
Table1
| Typeconnector | Wire size | Catalogno.suffix |
| Parallelgroove | No.6 solid cu. thru 250KCwill stranded cu Or al. Or 4/0 scsr. | -D |
| Eye bolt | No.6 solid cu. thru2/0stranded cu.Or al. | -J |
| Eye bolt | No.6 solid cu. thru 250KCwill stranded cu .Or al. Or 4/0 scsr. | -M |
| Style | Rating | leakage d~stancetogro. minmuninches |
| catalog KV, nom bil amps | ||
| Extraheavy duty | HRW 25 150 100 | 17 |
| Ultraheavy duty | HRW 25 150 100 | 17 |
| Heavy duty | HRW 14.4 150 100 | 17 |
Fuse Link
Introduction
The fuse have namely type K- fast fuse links and type T-slow fuse link;
The preferred rating of fuse links shall be: 11kV: 2A, 4A, 6A, 10A, 16A, 25A, 31.5A, 40A. 50A, 80A and 100A 33kV: 2A.4A.6A, 10A, 16A, 25A. 40A. 50A, 80A and 100A.
The minimum overall length of the fuse links shall be: 11kV: 533 mm
33kV: 787 mm.
Manufacturing standard: IEC 60282-2
Technical characteristics
| Rated current | 300-or 600 Second Melting Current | 10 Second Melting Current | 0.1 Second Melting Current | Speed Ratio | |||
| Min | Max | Min | Max | Min | Max | ||
| 2 | 4 | 4.8 | - | 10 | - | 58 | - |
| 4 | 8 | 9.6 | - | 10 | - | 58 | - |
| 6 | 12 | 14.4 | 13.5 | 20.5 | 72 | 86 | 6.0 |
| 10 | 19.5 | 23.4 | 22.5 | 34 | 128 | 154 | 6.6 |
| 16 | 33 | 40 | 39.5 | 58.5 | 230 | 275 | 6.9 |
| 25 | 50 | 60 | 60 | 90 | 350 | 420 | 7.0 |
| 31.5 | 66 | 80 | 81 | 120.5 | 469 | 573 | 7.1 |
| 40 | 80 | 96 | 96 | 146 | 565 | 680 | 7.1 |
| 50 | 101 | 121 | 126 | 188 | 719 | 862 | 7.1 |
| 80 | 160 | 192 | 205 | 307 | 1180 | 1420 | 7.4 |
| 100 | 200 | 240 | 258 | 388 | 1520 | 1820 | 7.6 |
| Rated current | 301-or 600 Second Melting Current | 10 Second Melting Current | 0.1 Second Melting Current | Speed Ratio | |||
| Min | Max | Min | Max | Min | Max | ||
| 2 | 4 | 4.8 | - | 11 | - | 100 | - |
| 4 | 8 | 9.6 | - | 11 | - | 100 | - |
| 6 | 12 | 14.4 | 15.3 | 23 | 120 | 144 | 10.0 |
| 10 | 19.5 | 23.4 | 26.5 | 40 | 224 | 269 | 11.5 |
| 16 | 33 | 40 | 47.5 | 71.5 | 413 | 497 | - |
| 25 | 50 | 60 | 73.5 | 109 | 635 | 762 | 12.7 |
| 31.5 | 66 | 80 | 98 | 149 | 852.5 | 1023 | 12.9 |
| 40 | 80 | 96 | 120 | 178 | 1040 | 1240 | 13.0 |
| 50 | 101 | 121 | 152 | 226 | 1310 | 1570 | 13.0 |
| 80 | 160 | 192 | 248 | 370 | 2080 | 2500 | 13.0 |
| 100 | 200 | 240 | 319 | 475 | 2620 | 3150 | 13.1 |
Service Fuse Cutout Single/double Phase
Introduction
Service Cutout is made of DMC type glass reinforced polyester thermoset material havinghigh mechanical and dielectric strength, the body posses non-hydroscopic and non-tracking quantities. Electrolytic Copper with phosphor bronze back up compression springs capable of providingflawless service for years of use. In the service cutout, the terminals for aluminium/copper conductors with a sectional area up to 35mm
Manufacturing Standard: IEC 60269
Technical characteristics
| Rated voltage | 415V |
| Rated current | 60/80A |
| Rated frequency | 50Hz |
| Breaking capacity | 33kA |
| Protection against short-circuit | Type aR |
| Temperature range | -1℃ to +40℃ |
| Height above sea level | ≤2000m |
| Humidity | Up to 90% |
| Color | Light grey |
| Protection range | IP23 |
Cylindrical HRC Fuse Link
Technical characteristics
| Dimension | 22x57 | 30x27 |
| Rated voltage | AC 415V | AC 415V |
| Rated breaking capacity | 80kV | 80kV |
| Standard | IEC 60269 BS 1361 | IEC 60269 BS 1361 |
| Rated current | 30A, 60A ,80A | 30A, 60A ,80A |
Overhead LV Fuse Cutout
Introduction
The cutout bases and fuse carriers shall have the following current ratings at 230/400V: Three phase and neutral for transformers up to 500kVA: 400A; and Three phase and neutral for transformers above 500kVA: 630A.
Housing
The outer housing of the units shall be comprised of Grey insulating material of sufficient mechanical strength as to prevent it from becoming damaged. The material shall be resistant to ultra violet degradation and have flame retardant properties. The Grey colour shall be RAL 7035 code system according to DNA(German Standards Board, Frankfurt, Germany).
Fuse Carrier
The fuse carrier shall be required to take J.P. type cartridge fuse links with 82mm centers, conforming to BS 88. Tightening screws shall have insulated tops to enable the fuse carrier to be removedwithout safety devices (rubber gloves, etc.)
Wedge fuse link
Technical characteristics
| Item | JHU | JPU | JSU |
| Rated voltage | 415/500V AC | 415/500V AC | 415/500V AC |
| Rated breakingcapacity | 50kV | 50kV | 50kV |
| Standard | IEC 60269-2-1BS 88-2 | IEC 60269-2-1BS 88-2 | IEC 60269-2-1BS 88-2 |
| Rated current | Gg/Q1 | Gg/Q1 | Gg/Q1 |
| Rated current | 20A-800A | 20A-800A | 20A-800A |
Pole-mounted Air Breaker Switch
General
The (H)GW series outdoor Air/Load breaker switch is a three-phase AC 50Hz /60Hz outdoor medium-voltage switchgear, which can open and close the power line and can see the obvious disconnect distance.
Application voltage levels include: 12kV, 24kV and 36kV.
Application standard: IEC62271-102
Service and Installation Conditions
●Height above sea level:≤3000m
●Air temperature:-40℃\~+50℃
●Relative humidity: Daily mean 95%Monthly average 90%
●Maximum wind speed:≤34m/ s
●Earthquake intensity: < 8 degree
●Icing thickness: < 10mm
●Thickness of snow: < 35mm
●Irradiance:<0.1W/cm2
●Pollutiongrade:class、IVclass
●Installation site: No fire disaster, explosion danger, chemical corrosion and frequent strenuous vibration places
Technical characteristics
| Item | Unit | Data | ||
| Rated voltage | kV | 12 | 24 | 36 |
| Rated frequency | Hz | 50/60 | ||
| Rated current | A | 400/630 | ||
| Rated short-circuit withstand/breaking current | KA | 12.5 | ||
| Rated short-circuit makingcurrent (peak) | kA | 31.5 | ||
| Rated peak withstand current | kA | 31.5 | ||
| Rated short-circuit time | Sec | 1 | ||
| Mechanical Operations | Times | 5000 | ||
| Power frequency withstandvoltage (1 min) | kV | 28/32 | 50/60 | 70/80 |
| Lightning impulse withstandvoltage (peak) | kV | 76/85 | 125/145 | 170/190 |
| ① | Silicone rubber |
| ② | Product name G- Isolating switch W- Outdoor |
| ③ | Rated Voltage ( kV) |
| ④ | Rated continuous Current ( A) |